This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent reason then several things
may be suspected. If a door or window has been opened creating a draught, then pilot disturbance is the problem, and removal of the
draught should resolve this. The gas pressure reaching the fire must also be checked (again, recall your installer to check and rectify any
problem). The thermocouple connection into the back of the gas control valve may also have worked loose during installation, simply
get the installer to tighten. If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance
OFF, check the flue and carry out any remedial work required. Relight the fire and carry out a spillage test. DO NOT allow the appli-
ance to be used if it continues to fail a spillage test. The aeration hole of the pilot must be carefully cleaned out on each annual service
to ensure continued function of the ODS.The spillage monitoring system shall not be adjusted, modified, or put out of operation by the
installer. Any spare parts fitted MUST be of a type supplied for the purpose by the appliance manufacturer. If the fire is not spilling, then
further guidance should be sought, using the Troubleshooting section as a guide.
Close all doors and windows to the room containing the appliance. Let the fire run on HIGH for five minutes. Take a smoke match, light
it, and using a smoke match tube, hold it at the top edge of the fire opening, 25mm down and 25mm in. Starting 50mm in from either
side, run the smoke match across the opening.
All the smoke should be drawn away up the flue. Any smoke returning into the room indicates that spillage is occurring. If the initial
spillage test fails, run the fire for a further 10 minutes and repeat the test.
When the test has been completed satisfactorily, repeat with any extractor fans in the premises running on the highest setting, and any
communicating doors open. Finally, repeat with all doors open.
DO NOT allow the fire to be used until the test is satisfactorily passed.
All instructions must be handed to the user for safekeeping. Show the customer how to light and control the fire. After commissioning
the appliance, the customer should be instructed on the safe use of the appliance and the need for regular servicing. Frequency of serv-
ice depends on usage, but MUST be carried out at least once annually. Advise that cleaning of the fire may be achieved when the fire is
cold using a damp cloth and mild detergent on most surfaces.
Scratched and other superficial damage to the matt black paintwork of the appliance can be covered with matching heatproof spray. Use
only the manufacturers’ recommended spray paint. Paint only when the fire is OFF and cold. Always mask off the surrounding area to
prevent contamination with overspray. Ventilate the room during the use of the spray. DO NOT attempt to spray paint the coals or
ceramics, or wash them in water.
Advise that the fire will emit a “newness” smell for a time after initial commissioning and that extra ventilation may be needed during
this time. Advise that the fire is fitted with a spillage safety device (O.D.S.). If the fire shuts down, this system may be in operation. If
spillage is suspected, SWITCH APPLIANCE OFF and call in the installer to investigate any problems.
Isolate the fire from the gas supply. Ensure that the fire is fully cold before attempting service. A suggested procedure for servicing is
detailed below.
10
©
2010 Focal Point Fires plc.
12.5 FLUE SPILLAGE MONITORING SYSTEM
12.6 TESTING FOR SPILLAGE
Match
Crimp
Tube
Figure 18 : Cross section of smoke match tube
Make a smoke match tube from 10mm diameter
tube. Seal off one end and crimp the tube to prevent
the smoke match from sliding down inside.
Spillage test - Figure 19
A. 25mm down from top of
opening
B. 25mm in from front of open-
ing.
C. Disregard outer 50mm
either side of fireplace opening
C
C
B
A
Fireplace Opening
Smoke Match
In Tube
Figure 19
GB IE
12.7 BRIEFING THE CUSTOMER
13.0 SERVICING
1. Lay out the dust sheet and tools.
2. Carefully remove the ceramic components.
3. Remove the cast front fret or the combined frame and firefront (dependant on model).
4. Remove the two screws that retain the data/control plate.
5. Disconnect the gas supply, and remove the two securing screws in the tray legs.
6. Remove the burner tray.
7. Remove firebox as described.
8. Check the fireplace opening for rubble accumulation and remove. If debris is excessive, initiate remedial work on the flue.
9. Check the flue with smoke pellet for correct operation.
10. Refit firebox using new seals where necessary.
11. Strip off the burner pipes and clean thoroughly.