background image

This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent reason then several things
may be suspected. If a door or window has been opened creating a draught, then pilot disturbance is the problem, and removal of the
draught should resolve this. The gas pressure reaching the fire must also be checked (again, recall your installer to check and rectify any
problem). The thermocouple connection into the back of the gas control valve may also have worked loose during installation, simply
get the installer to tighten. If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance
OFF, check the flue and carry out any remedial work required. Relight the fire and carry out a spillage test. DO NOT allow the appli-
ance to be used if it continues to fail a spillage test. The aeration hole of the pilot must be carefully cleaned out on each annual service
to ensure continued function of the ODS.The spillage monitoring system shall not be adjusted, modified, or put out of operation by the
installer. Any spare parts fitted MUST be of a type supplied for the purpose by the appliance manufacturer. If the fire is not spilling, then
further guidance should be sought, using the Troubleshooting section as a guide.

Close all doors and windows to the room containing the appliance. Let the fire run on HIGH for five minutes. Take a smoke match, light
it, and using a smoke match tube, hold it at the top edge of the fire opening, 25mm down and 25mm in. Starting 50mm in from either
side, run the smoke match across the opening. 
All the smoke should be drawn away up the flue. Any smoke returning into the room indicates that spillage is occurring. If the initial
spillage test fails, run the fire for a further 10 minutes and repeat the test. 
When the test has been completed satisfactorily, repeat with any extractor fans in the premises running on the highest setting, and any
communicating doors open. Finally, repeat with all doors open.

DO NOT allow the fire to be used until the test is satisfactorily passed.

All instructions must be handed to the user for safekeeping. Show the customer how to light and control the fire. After commissioning
the appliance, the customer should be instructed on the safe use of the appliance and the need for regular servicing. Frequency of serv-
ice depends on usage, but MUST be carried out at least once annually. Advise that cleaning of the fire may be achieved when the fire is
cold using a damp cloth and mild detergent on most surfaces.
Scratched and other superficial damage to the matt black paintwork of the appliance can be covered with matching heatproof spray. Use
only the manufacturers’ recommended spray paint. Paint only when the fire is OFF and cold. Always mask off the surrounding area to
prevent contamination with overspray. Ventilate the room during the use of the spray. DO NOT attempt to spray paint the coals or
ceramics, or wash them in water.
Advise that the fire will emit a “newness” smell for a time after initial commissioning and that extra ventilation may be needed during
this time. Advise that the fire is fitted with a spillage safety device (O.D.S.). If the fire shuts down, this system may be in operation. If
spillage is suspected, SWITCH APPLIANCE OFF and call in the installer to investigate any problems.

Isolate the fire from the gas supply. Ensure that the fire is fully cold before attempting service. A suggested procedure for servicing is
detailed below.

10

© 

2010 Focal Point Fires plc.

12.5 FLUE SPILLAGE MONITORING SYSTEM

12.6 TESTING FOR SPILLAGE

Match

Crimp

Tube

Figure 18 : Cross section of smoke match tube

Make a smoke match tube from 10mm diameter
tube. Seal off one end and crimp the tube to prevent
the smoke match from sliding down inside.

Spillage test - Figure 19

A. 25mm down from top of

opening

B. 25mm in from front of open-

ing.

C. Disregard outer 50mm

either side of fireplace opening

C

C

B

A

Fireplace Opening

Smoke Match

In Tube

Figure 19

GB IE

12.7 BRIEFING THE CUSTOMER

13.0 SERVICING

1. Lay out the dust sheet and tools.
2. Carefully remove the ceramic components.
3. Remove the cast front fret or the combined frame and firefront (dependant on model).
4. Remove the two screws that retain the data/control plate. 
5. Disconnect the gas supply, and remove the two securing screws in the tray legs.
6. Remove the burner tray.
7. Remove firebox as described.
8. Check the fireplace opening for rubble accumulation and remove. If debris is excessive, initiate remedial work on the flue.
9. Check the flue with smoke pellet for correct operation.
10. Refit firebox using new seals where necessary.
11. Strip off the burner pipes and clean thoroughly.

Summary of Contents for ALVOR

Page 1: ...L CONTROL ONLY AVAILABLE WITH MANUAL OR SLIDE CONTROL FULL DEPTH INSET GAS FIRE Please note Except where otherwise stated all rights including copyright in the text images and layout of this booklet i...

Page 2: ...y or infirm are concerned a suitable fireguard should be used Consult ALL instructions before installation and use of this appliance This appliance is free from any asbestos material Refractories and...

Page 3: ...t vent more than one appliance i e not shared with a gas back boiler There must be no opening in the flue apart from the one that the appliance is installed into and the one venting the gases into the...

Page 4: ...either side of the fireplace opening providing the forward projection does not exceed 100mm 4in Any combustible side walls must be at least 500mm to the side of the radiant heat source As with all he...

Page 5: ...bscure the flue box outlet The firebox base of the flue box and hearth below may be drilled to allow plugs and screws to secure installation It is important that the sealing requirements of the appli...

Page 6: ...provided figure 4 The screws should locate into the pre punched holes in the sides of the firebox SUPPLY PIPE ENTRY Knockout holes are provided in the rear and sides of the firebox for use where conc...

Page 7: ...s during fixing When the opening is ready for installation of the fire the gas supply may be routed as per the examples shown in figure 8 IMPORTANT Wherever a concealed connection is made a rubber gro...

Page 8: ...the inlet restrictor elbow from the inlet pipe Connect the previously installed gas supply to inlet restrictor elbow Place the burner unit into the firebox making sure that the rear lugs locate prope...

Page 9: ...n To turn the fire OFF move the slide control knob upwards fully to the position marked O The spark gap shown in figure 16 between the spark electrode and the thermocouple should be 3 5 4 5mm to produ...

Page 10: ...ustomer should be instructed on the safe use of the appliance and the need for regular servicing Frequency of serv ice depends on usage but MUST be carried out at least once annually Advise that clean...

Page 11: ...e accu mulated The filter element should also be blown clean This component should not require replacement however if signs of deteriora tion are evident then a genuine spare part must be used If a la...

Page 12: ...e an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If the pilot will not stay lit t...

Page 13: ...here are no defects or obstructions that may prevent the flow of combustion products This appliance is fitted with a flue blockage safety device which will shut down the fire if abnormal flue conditio...

Page 14: ...HIGH setting move the slide control knob upwards to the HIGH flame setting The fire can also be set to operate anywhere between HIGH and LOW by moving the control knob to an inter mediate position To...

Page 15: ...rientated as desired to achieve a realistic effect Keep the spacing between the coals even and uniform The two coals at the ends of the row may be placed rearwards towards the back corners of the fuel...

Page 16: ...now complete IMPORTANT The fire is designed to operate correctly with the pebbles supplied when assembled according to the instructions Never add to the sixteen pebbles or change them for a different...

Page 17: ...0 of these instructions Slide control models only Ensure appliance is off and cool The battery is located underneath the ignition unit on the left hand side of the burner Insert 1 x PP3 9 volt battery...

Page 18: ...e hope therefore you will understand we must retain the right to amend details and or specifications without prior notice 6 F861020 GB IE Note Gas SafeTM registered operatives are the only class of pe...

Reviews: