Focal Point ALVOR FULL DEPTH RADIANT Installation & User'S Instructions Download Page 10

The spark gap (shown in figure 19) between the spark electrode and the thermocouple

should be 3.5 - 4.5mm to produce a good spark. 

There should be no need to adjust this. 

If under any circumstances the electric spark fails, the pilot may be lit manually by proceed-

ing with the ignition sequence as previously described, and after turning the control knob

through the spark position, the knob should be held in and the pilot lit with a taper.

Release the pressure test point screw, and attach a pressure gauge. Light the fire on

the HIGH setting. To commission the appliance, the operating pressure must be in

accordance with the figures stated in section 2.0 of these instructions. The fire is

factory set to achieve the correct flow rates at the specified inlet pressure. 

Any significant variation in the inlet pressure could indicate a supply problem. If the

inlet pressure is too high, the gas supply meter/governor may be set incorrectly.

This should be checked with the fire running and if necessary reset by the gas sup-

plier.  If the inlet pressure is too low, then check the meter/governor pressure with

the appliance running.  If this is less than the inlet pressure stated in section 2.0 of

these instructions it will need to be reset by the gas supplier.  If the inlet pressure

is too low, but the meter/governor pressure is acceptable, then a problem in the

supply pipework is to be suspected.  Upon satisfactory checking of the inlet pressure, turn the fire off, disconnect the pressure gauge

and refit the test point screw. Light the fire and check for gas soundness. In the event that the inlet pressure is not in accordance with

the figures stated in the data section of these instructions, the appliance must not be commissioned, and the problem investigated and

rectified.

Slide control models : The pressure test point is located directly above the gas valve in the centre of the burner.

Remote control models : The pressure test point is located on the right hand side of the burner, between the burner legs. 

Release the pressure test point screw, and attach a pressure gauge. Light the fire on the HIGH setting. To commission the appliance, the

burner pressure must be in accordance with the figures stated in section 2.0 of these instructions. 

The fire is factory set to achieve these pressures and any significant variation could indicate a supply problem. If the pressure is too high,

the gas supply meter may be set incorrectly.  This should be checked with the fire running and if necessary reset by the gas supplier. 

Upon satisfactory checking of the burner pressure, turn the fire off, disconnect the pressure gauge and refit the test point screw. Light

the fire and check for gas soundness. In the event that the burner pressure is not in accordance with the figures stated in the data sec-

tion of these instructions, the appliance must not be commissioned, and the manufacturer should be contacted for guidance.

This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent reason then several things

may be suspected. If a door or window has been opened creating a draught, then pilot disturbance is the problem, and removal of the

draught should resolve this. The gas pressure reaching the fire must also be checked (again, recall your installer to check and rectify any

problem). The thermocouple connection into the back of the gas control valve may also have worked loose during installation, simply

get the installer to tighten. If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance

OFF, check the flue and carry out any remedial work required. Relight the fire and carry out a spillage test. 

DO NOT allow the appliance to be used if it continues to fail a spillage test. The aeration hole of the pilot must be carefully cleaned out

on each annual service to ensure continued function of the ODS.The spillage monitoring system shall not be adjusted, modified, or put

out of operation by the installer. Any spare parts fitted MUST be of a type supplied for the purpose by the appliance manufacturer. If the

fire is not spilling, then further guidance should be sought, using the Troubleshooting section as a guide..

12.5 OPERATING PRESSURE

- MANUAL, SLIDE & REMOTE CONTROLS

Figure 19

Spark gap

12.4 SPARK GAP

© 2013 Focal Point Fires plc.

10

12.6 FLUE SPILLAGE MONITORING SYSTEM

GB IE

 

    FIN:

A

   

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

   

 

 

 

 

 

Figure 20

Summary of Contents for ALVOR FULL DEPTH RADIANT

Page 1: ...ekeeping Please note Except where otherwise stated all rights including copyright in the text images and layout of this booklet is owned by Focal Point Fires plc You are not permitted to copy or adapt...

Page 2: ...and under normal usage will need a new battery approximately every twelve months Burner spark generator requirements 1 x AA 1 5 volt Refer to the appropriate section of these instructions for details...

Page 3: ...rom dam aging wall surfaces Pre cast flues must be checked for mortar fangs and correct installation of joints flue sections in loft space and ter minals These appliances have been tested for use with...

Page 4: ...may be fixed to the wall above the fire providing that it complies with the dimensions given below A non combustible shelf may be fitted to within 10mm of the top edge of the fireframe Combustible ma...

Page 5: ...ox does not obscure the flue box outlet The firebox base of the flue box and hearth below may be drilled to allow plugs and screws to secure installation It is important that the sealing requirements...

Page 6: ...provided figure 4 The screws should locate into the pre punched holes in the sides of the firebox SUPPLY PIPE ENTRY All models Knockout holes are provided in the rear and sides of the firebox for use...

Page 7: ...siliconed When the opening is ready for installation of the fire the gas supply may be routed as per the examples shown in figure 9 IMPORTANT Wherever a concealed connection is made a rubber grommet...

Page 8: ...suitable gas route can be achieved Purge the gas supply thoroughly to remove air and dirt debris before connection Disconnect the inlet restrictor elbow from the inlet pipe Connect the previously inst...

Page 9: ...mediate position To turn the fire OFF move the slide control knob upwards fully to the position marked O The pilot is visible through the left hand side of the ceramic fuel bed When cold the coals or...

Page 10: ...the HIGH setting To commission the appliance the burner pressure must be in accordance with the figures stated in section 2 0 of these instructions The fire is factory set to achieve these pressures a...

Page 11: ...ded during this time Advise that the fire is fitted with a spillage safety device O D S If the fire shuts down this system may be in operation If spillage is suspected SWITCH APPLIANCE OFF and call in...

Page 12: ...t must be used If a large amount of debris is present in the filter then the pipework and con trol should be thoroughly cleaned before re assembly Remove the burner unit as in relevant section and pil...

Page 13: ...e an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If the pilot will not stay lit t...

Page 14: ...e appliance is installed the chimney should be swept All flues should be checked by the installer to ensure there are no defects or obstructions that may prevent the flow of combustion products This a...

Page 15: ...control knob in fully and turn anti clockwise through both of the SPARK positions keeping fully depressed hold there for a few seconds If the fire has not been used for some time hold the knob in this...

Page 16: ...lot is extinguished during use of the fire you MUST wait ten minutes before repeating the ignition procedure To turn the main burner OFF whilst keeping the pilot flame lit turn the ignition control kn...

Page 17: ...igure 11 Care should be taken to ensure that the coals bridge the gap between the front coal and the four coal supports at the front of the matrix Care should also be taken not to push the coals right...

Page 18: ...oals or change them for a different type Never throw rubbish or other matter onto the coal bed 1 Refer back to section 6 0 Fuel bed layout coal effect and follow steps 1 and 2 The front strip and fuel...

Page 19: ...ld be checked on an annual basis to ensure all of the products of combustion are entering the flue and that there is no excessive build up of soot The frequency of service will depend on usage but MUS...

Page 20: ...em Part number Pack of 16 coals F550038 Pack of 16 pebbles F550050 Pack of 9 ceramic logs F550084 Front ceramic strip coal F780008 Front ceramic strip pebble F780017 Front ceramic strip Log F780050 Ce...

Page 21: ...GI Gas Safe registered installer evidence of which must be provided such as the receipt Please note all consumable items such as any ceramics including coals pebbles the matrix front strips side cheek...

Reviews: