FoamPRO MultiFlo Installation And Operation Manual Download Page 12

12

Installation and Operation Manual

3. Select the discharge to be calibrated: A, B, C or D

by depressing the B FLOW button until the light

under the selected discharge is illuminated. If a

number other than ZERO shows on the control

module display, reset

the display by depressing both C FLOW and

D FLOW buttons simultaneously.

4. Establish water flow and collect the discharge in a

container of 250 gallons (946 liters)

or larger.

5. When the water flow is stopped and the total

volume of water collected is determined, adjust the

reading to match this value by pressing the C

FLOW or D FLOW buttons on the FoamPro

MultiFlo Control Module until the correct reading

shows on the control module display.

6. Repeat steps 2 through 5 for all other discharges

equipped with paddlewheel flowmeters.

7. Exit calibration mode as previously described to

lock the adjustments into the memory of the

FoamPro MultiFlo control module microprocessor.

Replace the o-ring and the cover screw to prevent

water and dust from entering the control module.

8. Proceed with the FoamPro foam proportioner

system calibration per the applicable manual.

Total Volume Method of Calibration

If a pitot gauge is not available, the total volume method

of calibration may be used.

NOTE: This method is intended only as a

temporary method of calibration since many

factors can create errors in measuring volume.

Some of the more obvious causes of error are:

• Water tank volumes may vary by as much as

±15% from their rated size.
• The fill level of a tank can significantly vary the

volume as will the amount of water left in the tank

when the pump begins to cavitate.

NOTE: As soon as a pitot gauge is available,

recalibrate the system using the flow method of

calibration to ensure optimal results and

accuracy.

1. Enter calibration mode as previously described.

The total indicator must be illuminated when total

volume method of calibration is used. Press the “A

FLOW” button to light the “TOTAL” indicator

showing the control module is set for total volume

calibration method.

2. Connect a discharge hose to the flowmeter

equipped discharge to be calibrated and secure the

other end of the hose in a container with a known

volume.

Summary of Contents for MultiFlo

Page 1: ...ly inspected and tested In order to maintain the high quality of your unit and to keep it in a ready condition it is important to follow the instructions on care and operation Proper use and good prev...

Page 2: ...OPERATION 13 6 DIAGNOSTIC PROCEDURES 14 7 PARTS IDENTIFICATION 15 8 INSTALLATION TEMPLATE 16 9 WARRANTY 20 NOTE TO SYSTEM INSTALLERS IMPORTANT Please provide a copy of the FoamPro manual to the end us...

Page 3: ...it Improper handling and forcing connections can damage these cables which could result in other system damage 1 Always disconnect the power source before attempting to service any part of the FoamPro...

Page 4: ...with foam concentrate by a single foam injection point Figure 1 FoamPro MultiFlo Control Module and Digital Display Control Module FoamPro MultiFlo Control Module Digital Display Control Module The F...

Page 5: ...ortioner being used For example If the FoamPro 2001 foam proportioning system is used the maximum foam concentrate flow will be 2 6 GPM 9 8 LPM When the foam concentrate injection is set to 0 1 the am...

Page 6: ...has five connectors on the back of the case see Figure 3 to connect the cables from the flowmeters and FoamPro Digital Display Control Module The FoamPro MultiFlo Control Module receives operating po...

Page 7: ...lowmeter see Figure 5 10 times is even better the longer the straight run the lower the turbulence Here are some examples of required straight run Pipe Recommended Size Straight Run Pipe 11 2 38 mm 71...

Page 8: ...mPro Digital Display Control Module Connect the cables from the flowmeter sensors to the connectors marked A B C or D on the back of the control module see Figure 3 If all connections are not used mak...

Page 9: ...aking round coils see Figure 8 Install clamp on beads at the locations indicated in Figure 7 Use a small amount of RTV silicone electrical tape or heat shrink tubing to keep the beads from moving afte...

Page 10: ...re 1 Remove the cover screw and the o ring to the left of the display readout panel on the MultiFlo Control 4 Calibration Procedures Module see Figure 9 Use a 3 32 allen wrench to remove the screw and...

Page 11: ...e cover screw and o ring to keep water and dirt from entering the control module as it can cause serious damage to the components Flow Method of Calibration The flow method of calibration is being use...

Page 12: ...dust from entering the control module 8 Proceed with the FoamPro foam proportioner system calibration per the applicable manual Total Volume Method of Calibration If a pitot gauge is not available th...

Page 13: ...l match is when water or foam solution is flowing through one paddlewheel flowmeter equipped discharge The FoamPro MultiFlo Control Module constantly monitors the flow signals from the flowmeter senso...

Page 14: ...control module display for any one of the paddlewheel flowmeters the flowmeter cable or flowmeter sensor could be defective and further diagnosis is required If no reading shows for any flowmeter the...

Page 15: ...ng 3 2660 0030 11 2 NPT Paddle Wheel Flowmeter Assembly Note 1 Bore 2660 0031 11 2 NPT Paddle Wheel Flowmeter Assembly 2660 0032 2 NPT Paddle Wheel Flowmeter Assembly 2660 0033 21 2 NPT Paddle Wheel F...

Page 16: ...ation and Operation Manual 8 4 25 2 75 4 25 78 3 50 3 70 10 24 x 44 DP 4 Holes Display requires a 3 875 inch 98mm diameter hole to be drilled in operator panel Additional space 3in 76mm required for c...

Page 17: ...1 2 8 NPT 3 Pipe 5 3 8 137 mm 4 9 16 116 mm 20 750 8 900 2600 0033B 2 1 2 11 BSP 3 Pipe 5 3 8 137 mm 4 9 16 116 mm 20 750 8 900 2660 0034 3 8 NPT 4 Pipe 5 1 2 140 mm 4 7 8 124 mm 30 1150 12 1380 2600...

Page 18: ...18 Installation and Operation Manual N O T E S...

Page 19: ...19 Installation and Operation Manual MultiFlo N O T E S...

Page 20: ...cts as above stated THERE ARE NO OTHER EXPRESS WARRANTIES ANY IMPLIED WARRANTIES INCLUDING IMPLIED WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED IN DURATION TO ONE YEA...

Reviews: