background image

7

105073

OWNER’S MANUAL

LOG SIZING REQUIREMENTS

Minimum Firebox Size

Log

Front

Rear*

Size Height Depth

Width Width

18"

17"

14"

20"

14"

24"

17"

14"

26"

18"

30"

17"

14"

32"

22"

INSTALLATION AND
CLEARANCES

 WARNING: Maintain the mini-

mum clearances. If you can, pro-
vide greater clearances from
floor, ceiling, and adjoining wall.

MINIMUM FIREPLACE CLEARANCE

TO COMBUSTIBLE MATERIALS

Log Size Side Wall Ceiling Floor*

18", 24", 30”

16"

42"

5"

*See 

Floor Clearances, page 9.

 WARNING: Never install the

heater
• in a bedroom or bathroom un-

less installed as vented appli-
ance, see page 10

• in a recreational vehicle
• where curtains, furniture, cloth-

ing, or other flammable objects
are less than 42 inches from the
front, top, or sides of the heater

• in high traffic areas
• in windy or drafty areas

 CAUTION: This heater cre-

ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as to-
bacco smoke, aromatic candles,
cleaning fluids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls.

CHECK GAS TYPE

Use only propane/LP gas. If your gas sup-
ply is not propane/LP gas, do not install
heater. Call dealer where you bought heater
for proper type heater.

IMPORTANT:

 Vent-free heaters add mois-

ture to the air. Although this is beneficial,
installing heater in rooms without enough
ventilation air may cause mildew to form
from too much moisture. See Air for Com-
bustion and Ventilation
, pages 4 through 6.

 WARNING: A qualified ser-

vice person must install heater.
Follow all local codes.

INSTALLATION

NOTICE: This heater is intended
for use as supplemental heat. Use
this heater along with your pri-
mary heating system. Do not in-
stall this heater as your primary
heat source. If you have a central
heating system, you may run
system’s circulating blower while
using  heater. This will help circu-
late the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.

NOTICE: State or local codes may
only allow operation of this appli-
ance in a vented configuration.
Check your state or local codes.

 WARNING: Seal any fresh air

vents or ash clean-out doors lo-
cated on floor or wall of fireplace.
If not, drafting may cause pilot
outage or sooting. Use a heat-
resistant sealant. Do not seal
chimney flue damper.

 WARNING: Before installing

in a solid fuel burning fireplace,
the chimney flue and firebox must
be cleaned of soot, creosote,
ashes and loose paint by a quali-
fied chimney cleaner. Creosote
will ignite if highly heated. A dirty
chimney may create and distrib-
ute soot within the house. Inspect
chimney flue for damage. If dam-
aged, operate heater with flue
damper closed.

 WARNING: Make sure the se-

lector switch is in the OFF posi-
tion before installing heater.

*Measured at 14” depth

(Vent-Free Operation Only)

Continued

Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured fireplace, or
listed vent-free firebox.

Minimum Clearances For Side
Combustible Material, Side Wall,
and Ceiling

A. Clearances from the side of the fire-

place cabinet to any combustible ma-
terial and wall should follow the dia-
gram in Figure 4.

Example:

 The face of a mantel, book-

shelf, etc. is made of combustible ma-
terial and protrudes 3 

1

/

2

" from the wall.

This combustible material must be 4"
from the side of the fireplace opening
(see Figure 4).

Note:

 When installing your gas logs

into a manufactured firebox, follow
firebox manufacturer’s instructions for
minimum clearances to combustible
materials.

B. Clearances from the top of the fireplace

opening to the ceiling should not be less
than 42 inches.

Figure 4 - Minimum Clearance for
Combustible to Wall

.5

2

7/16

7/8

1

3

/

4

3

1

/

2

5

1

/

4

7

3

/

4

10

1

/

2

12

1

/

4

1

4

6

8

10 12 14

16

FIREBOX

INCHES

INCHES

*Minimum 16 inches from Side Wall

*

Example

Summary of Contents for VFP18R

Page 1: ...l information consult a qualified installer service agency or the gas supplier WARNING This appliance is for installa tion only in a solid fuel burning masonry UL127 factory built fireplace or in an ap proved ventless firebox It is design certi fied for these installations in accordance with ANS Z21 11 2 Exception Do not in stall this appliance in a factory built fire place that includes instructi...

Page 2: ...st open the vents before operating heater 7 To prevent the creation of soot follow the instructions in Cleaning and Main tenance page 17 8 This log heater is designed to be smoke less If logs ever appear to smoke turn offheaterandcallaqualifiedserviceper son Note Duringinitialoperation slight smokingmayoccurduetologcuringand heater burning manufacturing residues 9 Before using furniture polish wax...

Page 3: ...nt performance problems the useofapropane LPfueltankoflessthan 100 lb capacity is not recommended SAFETY INFORMATION Continued PRODUCT FEATURES OPERATION This heater is clean burning It requires no outsideventing Thereisnoheatlossoutavent or up a chimney Heat is generated by both realisticflamesandglowingcoals Thisheater is designed for vent free operation with flue damper closed It has been teste...

Page 4: ...e a walls and ceilings exposed to the outside atmosphere have a con tinuous water vapor retarder with a rating of one perm 6 x 10 11 kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added on openable windows and doors and c caulking or sealants are applied to areas such as joints around window and door frames be tween sole plates and floors be tween wall ...

Page 5: ...tion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the space can support _________________ Btu Hr actual amount of Btu Hr used Example 51 200 Btu Hr maximum the space can support 73 000 Btu Hr actual amount of Btu Hr used The space in the above example is a confined space bec...

Page 6: ... Gas Code NFPA 54 ANS Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts Figure 2 Ventilation Air from Inside Building Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two per manent openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the o...

Page 7: ...culatingblowerwhile using heater Thiswillhelpcircu late the heat throughout the house In the event of a power outage you can use this heater as your primary heat source NOTICE Stateorlocalcodesmay onlyallowoperationofthisappli ance in a vented configuration Check your state or local codes WARNING Seal any fresh air vents or ash clean out doors lo cated on floor or wall of fireplace If not drafting...

Page 8: ...way from your mantelshelf SeeFigure5andFigures6and 7 page 9 for minimum clearances Minimum Noncombustible Material Clearances If Not Using Mantel Note If using a mantel see If Using Man tel If not using a mantel follow the infor mation below You must have noncombustible material s above the fireplace opening Noncombus tible materials such as slate marble tile etc must be at least 1 2 inch thick Wi...

Page 9: ...hood When using a hood there are still certain minimum mantel clear ances required Follow minimum clearances shown in Figure 7 page 9 when using hood NOTICE If your installation does notmeettheminimumclearances shown you must do one of the following operate the logs only with the flue damper open raise the mantel to an accept able height remove the mantel Figure 6 Minimum Mantel Clearances Without...

Page 10: ... install the damper clamp accessory to order see Accessories page 24 This will insure vented operation see Figure 10 The damper clamp will keep damper open Installation instructions are included with clamp accessory See chart below for minimum permanent flue opening you must provide Attach damper clamp so the minimum permanent flue opening will be maintained at all times Area of Various Standard R...

Page 11: ...sistant to liquid pe troleum LP gas We recommend that you install a sediment trap in supply line as shown in Figure 14 Locate sediment trap where it is within reach for cleaning Install in piping system betweenfuelsupplyandheater Locatesedi ment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into heater controls If sedim...

Page 12: ...orrect all leaks at once WARNING Test all gas pip ing and connections for leaks after installing or servicing Cor rect all leaks at once CHECKING GAS CONNECTIONS CAUTION Make sure exter nal regulator has been installed between propane LP supply and heater SeeguidelinesunderCon necting to Gas Supply page 11 Test Pressures Equ al To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see F...

Page 13: ...the bottom of the log fit over the grate Bring the log forward next to the metal posts The pegs on the log must be on top see Figure 18 3 Slide the grooves in the back of the rear log 3 against the rear grate prongs Make sure the peg on the log is on top see Figure 19 4 Place the top middle log 4 on the bottom middle log 2 Make sure the pegs of the bottom middle log fit se curely in the holes of t...

Page 14: ...w these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas s...

Page 15: ...tructions included with the remote control Thermostat Control Operation Optional GHRCTA Series Only The thermostat control setting on the remote control unit can be set to any comfort level between WARMER and COOLER The burners will turn on and off auto matically to maintain the comfort level you select The ideal comfort setting will vary by household depending upon the amount of space to be heate...

Page 16: ...g at top of blue flame Pilot Burner Thermocouple Figure 27 Incorrect Pilot Flame Pattern Thermocouple Figure 26 Correct Pilot Flame Pattern Pilot Burner NOTICE Do not mistake orange flames with yellow tipping Dirt or other fine particles are burned by heater causing brief patches of orange flame If front burner flame pattern is incorrect as shown in Figure 29 page 17 turn heater off see To Turn Of...

Page 17: ...Inlet Air Hole Burner Tube Injector Holder Primary Air Inlet Holes Ports Slots Wealsorecommendthatyoukeeptheburner tube and pilot assembly clean and free of dustanddirt Tocleanthesepartswerecom mend using compressed air no greater than 30 PSI Your local computer store hard ware store or home center may carry com pressed air in a can You can use a vacuum cleaner in the blow position If using com pr...

Page 18: ...l damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind base panel 4 Replace ignitor cable 5 Replace piezo ignitor 6 Replace ignitor 7 Replace ignitor 1 Turn on gas supply or open equipment shutoff valve 2 Turn control knob to PILOT position 3 Press in...

Page 19: ...eplace 9 volt batteries in receiver and remote control OBSERVED PROBLEM One or both burners do not light after ODS pilot is lit Delayed ignition of one or both burners Burner backfiring during combustion Yellow flame in front burner during burner combustion Slight smoke or odor during initial operation Moisture condensationnoticedonwindows Heater produces a whistling noise when burners are lit Whi...

Page 20: ... fire department POSSIBLE CAUSE 1 Metal expanding while heating or con tracting while cooling 1 Heater burning vapors from paint hair spray glues cleaners chemicals new carpet etc See IMPORTANT state ment above 2 Low fuel supply 3 Gas leak See Warning statement above 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement above 2 Ga...

Page 21: ...umbers of your heater the replacement part number SPECIFICATIONS SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition heater will not produce specified heat propane LP gas supply may be low When Gas Quality Is Bad pilot will not stay lit burners will produce flames and soot heater will backfire when lit You may feel your gas pressure is too low or g...

Page 22: ...NVENTED PROPANE LP GAS LOG HEATER FIREPLACE MANUFACTURERS INC ILLUSTRATED PARTS BREAKDOWN VFP18R VFP24R VFP30R 29 6 7 8 9 10 7 7 24 12 11 12 22 13 25 26 29 29 15 18 20 21 28 23 16 19 14 27 17 9 1 9 2 4 5 3 2 1R 1L ...

Page 23: ... 1 12 098271 06 098271 06 098271 06 Ignitor Cable 1 13 102445 01 102445 01 102445 01 Piezo Ignitor 1 14 103588 01 103588 01 103588 01 Heat Shield 1 15 103782 01 103782 01 103782 01 Valve Bracket 1 16 M12461 26 M12461 26 M12461 26 Screw 5 17 103781 02 103781 02 103781 02 Gas Control 1 18 098264 02 098264 02 098264 02 Male Fitting 1 19 103784 02 103784 02 103784 02 Flame Adjustment Knob 1 20 103784 ...

Page 24: ... REMOTE CONTROL KIT GHRCT SERIES For all models Allows the gas log heater to be operated in a manually or thermostati cally controlled mode You can turn the gas log heater on and off without ever leaving the comfort of your easy chair RECEIVER AND HAND HELD REMOTE CONTROL KIT GHRC SERIES Forallmodels Allowsthegaslogheaterto be turned on and off by using a hand held remote control WALL MOUNT THERMO...

Page 25: ...____________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ ___________________________________________________________________________________________...

Page 26: ...des and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective h...

Reviews: