www.fmiproducts.com
117437-01F
12
WARNING: This appliance,
when installed must be electri
-
cally grounded in accordance
with local code or in the absence
of local code, with the current
National Electric Code, ANSI/
NFPA 70.
HIGH ALTITUDE INSTALLATION
Your FMI PRODUCTS, LLC B-vent fireplace
has been tested and approved in the USA for
elevations from 0-2,000 feet.
VENTING INSTALLATION
Continued
When installing a non-high altitude fireplace
at an elevation above 2,000 feet, you may
need to decrease the input rating by changing
the existing burner orifice to a smaller size.
Reduce input 4% for each 1,000 feet above
sea level. Check with your local gas company
for proper orifice size identification.
Consult your local gas company to help deter-
mine the proper orifice for your location.
For assistance with any high altitude installa-
tion contact FMI PRODUCTS, LLC’s Custom
-
er Service Department at 1-866-328-4537.
INSTALLING OPTIONAL CONTROLS
INSTALLING OPTIONAL WALL
MOUNT SWITCH - GWMS2
1. Connect one terminal of 15 foot wire from
wall switch to male connector on high limit
harness. Connect remaining wire terminal
to TH terminal on valve. Make sure that
wire terminals are in positions on unit as
pictured in Figure 14. If wires are not con
-
nected as shown switch will not work.
2. Route 15 foot wire through hole openings
with bushings provided on either side of
fireplace cabinet.
3. Connect one bare wire end to each of
terminals of GWMS2 wall switch.
4. Install wall switch and cover in wall.
IMPORTANT:
Do not use any other wire than
that provided with GWMS2 wall switch kit. Do
not exceed 15 feet of distance from valve con-
nection. Using wire of higher gauge or turns
or exceeding minimum distance will increase
resistance at control valve causing unreliable
performance of fireplace controls.
Remote Receiver
or Wall Switch to
Terminal Marked “TH”
Wire Harness From
High Limit Switch
Male Connector to
Remote Receiver
or Wall Switch
Figure 14 - Connecting Remote Receiver
or Wall Switch to the Gas Control Valve