INSPECTING bURNERS

Continued

BURNER FLAME PATTERN

Burner flames will be steady, not lifting or float

-

ing. Flame patterns will be different from unit 
to unit and will vary depending on installation 
type and weather conditions.
If  vent  configuration  is  installed  incorrectly, 
flames will lift or "ghost". This can be danger

-

ous. Inspect flames after installation to ensure 
proper installation and performance.
Figure 47 shows a typical flame pattern.
If  burner  flame  pattern  differs  from  that  de

-

scribed:
•  turn fireplace off (see 

To Turn Off Gas to 

Appliance

, page 28)

•  see 

Troubleshooting

, page 32

Figure 47 - Typical Flame Pattern

CLEANING AND MAINTENANCE

Glass  must  be  cleaned  periodically.  During 
start-up it is normal for condensation to form 
on the inside of the glass causing lint, dust and 
other airborne particles to cling to the glass 
surface. During initial start-up a slight film may 
form  on  the  glass  due  to  paint  curing.  The 
glass should be cleaned several times with a 
non-ammonia, nonabrasive household clean

-

er and warm water after the first two weeks 
of operation. Thereafter, clean the glass two 
or three times during each heating season, 
depending on the usage and circumstances 
present. Refer to 

Removing/Replacing Glass 

Door

, page 24 of this manual when removing 

glass door for cleaning.

 WARNING: Only parts sup

-

plied by the manufacturer should 

be used when replacing broken 

or  damaged  glass  door  panel 

(see 

Replacement  Parts

,  page 

36).  This  glass  door  panel  is 

a  complete  unit.  No  substitute 

materials may be used.

 CAUTION: Wear gloves and 

safety  glasses  while  handling 

or  removing  broken  glass.  Do 

not remove if glass is hot. Keep 

children  and  pets  away  from 

glass.

 WARNING: Turn off fireplace 

and let cool before cleaning.

  CAUTION:  You  must  keep 

control  areas,  burners  and 

circulating air passageways of 

fireplace  clean.  Inspect  these 

areas  of  fireplace  before  each 

use.  Have  fireplace  inspected 

yearly  by  a  qualified  service 

person.  Fireplace  may  need 

more frequent cleaning due to 

excessive  lint  from  carpeting, 

bedding material, pet hair, etc.

GLASS DOOR

  WARNING:  Handle  glass 

door  panel  with  care.  Do  not 

strike, slam or otherwise abuse 

glass. Do not operate fireplace 

with the glass door unlatched, 

removed, cracked or broken.

 WARNING: Do not use abra

-

sive cleaners as this may damage 

glass. Use a nonabrasive house

-

hold glass cleaner to clean glass. 

Do not clean glass when hot.

Summary of Contents for KC42N series

Page 1: ...se gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not...

Page 2: ...c tive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble op erate or service this log set Improper use of this log set can cause serious injury or death from burn...

Page 3: ...accessory not approved for use with this fire place WARNING This appliance is only for use with the type of gasindicatedontheratingplate Thisapplianceisnotconvertible for use with other gases unless a...

Page 4: ...d pilot light before cleaning fireplace 6 Have venting system inspected annually by a qualified service person If needed have venting system cleaned or repaired See Cleaning and Maintenance page 30 7...

Page 5: ...r proper operation You must follow the venting instructions very carefully for either vertical or horizontal applications This fireplace may be installed in any room of your house provided all local c...

Page 6: ...to prevent accidental blockage of venting system When using snow blowers do not direct snow towards vent termination area For horizontal installations above 2 000 feet it is recommended that a 12 ext...

Page 7: ...l Vent C B A D E F G Top of Louver Opening 3 2 1 4 5 6 7 Wall Figure 5 Framing Clearances for Corner Installation Ref Mantel Depth Ref Mantel from Top of Louver Opening 1 14 A 16 2 12 B 14 3 10 C 12 4...

Page 8: ...n US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally...

Page 9: ...inate on the out side of the structure and can not be attached to a chimney or flue system serving a separate solid fuel or gas burning appliance Adirect vent appliance must have its own venting syste...

Page 10: ...on male ends of adjacent pipes Push pipe sections together and twist one section clockwise approximately one quarter turn until the sections are fully locked see Figure 8 Note Horizontal runs of vent...

Page 11: ...screws provided see Figure 11 Siding standoff must sit flush against exterior fascia material 7 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe before connecting hori...

Page 12: ...uired NOTICE Donotsealtermination cap to vent pipe Cap must be removable for vent inspection and maintenance WARNING Never run vent downward as this may cause excessive temperatures which could cause...

Page 13: ...Recommended Applications Installations requiring a vertical rise on building exterior Any installation using snorkel termination to achieve one foot above ground Snorkel terminations are available for...

Page 14: ...for a horizontal system using two 90 elbows Figure 18 Horizontal Termination Configuration for Venting Using Two 90 Elbows with Termination at 90 with Fireplace 45 Elbow Venting with Two 90 Elbows Ve...

Page 15: ...above ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insula tion from falling into required clearance space If area above ceiling is a living space instal...

Page 16: ...High Wind Termination Shown 45 Elbow Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 2 max 6 min 4 max 7 min 6 max 8 min 8 max 20 max 8 max Note Install restrictor into inner...

Page 17: ...elevations from 0 2000 feet Fireplaces for High Altitude models ending in HA are for installation above 4000 feet only These fireplaces are equipped with parts specific for higher altitudes When insta...

Page 18: ...m Collar Roof Flashing 0 12 6 12 26 Screws VKC 58 Corner Vent Kit Galvanized Includes 45 Elbow 7 12 Adjustable Pipe Wall Firestop Horizontal Termination 6 Pipe 90 Elbow 18 Screws HHTK 58 High Wind Rou...

Page 19: ...ed upward Blower will fit inside back opening and be held in position against back wall by magnets see Figure 26 4 Be certain that all wire terminals are securely attached to terminals on blower motor...

Page 20: ...ower cord outer insulation sleeve may have to be stripped slightly to allow enough wire length to reach and make all connec tions DO NOT trim excessive length away Enable just enough to make all conne...

Page 21: ...ue Variable Fan Switch Fan Switch N O Green White On 110 115 V A C Blower Motor Black Off 1 2 Black Installing Gas Piping to Fireplace Location WARNING A qualified service person must connect fireplac...

Page 22: ...you install a sediment trap drip leg in supply line as shown in Figure 32 Locate sediment trap drip leg where it is within reach for cleaning Install in piping sys tem between fuel supply and fireplac...

Page 23: ...gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air 4 Check all joints of gas supply piping sys tem Apply noncorrosive leak detection...

Page 24: ...3 Connect one bare wire end to each termi nal of the GWMS2 wall switch 4 Install wall switch and cover in the wall Fireplace Installation Continued Figure 37 Connecting Wall Switch to Control Valve To...

Page 25: ...screen door tabs with slot openings in upper face frame Swing door screen assembly in towards the bottom face 4 Remount new frame at hinge with five new screws before closing door This will ensure sea...

Page 26: ...n and close louvers see Removing Glass Door steps 5 through 7 page 25 WARNING The glass door mustbesecurelyinplacebefore runningthisfireplace Donotrun this fireplace if glass is missing or broken Fire...

Page 27: ...RE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to l...

Page 28: ...Push in gas control knob slightly and turn clockwise to OFF 5 Close lower louver panel MANUAL LIGHTING PROCEDURE 1 Remove glass door see Removing Re placing Glass Door page 24 2 Follow steps 1 through...

Page 29: ...osi tion blower will not operate Note for BKT Only If you are using BKT blower with optional thermostat wall mounted or remote control for fireplace your fireplace and blower will not turn on and off...

Page 30: ...peration Thereafter clean the glass two or three times during each heating season depending on the usage and circumstances present Refer to Removing Replacing Glass Door page 24 of this manual when re...

Page 31: ...lling Lava Rock and Glowing Embers page 26 to properly replace logs Use a vacuum cleaner to remove any carbon buildup on logs Replace log s if broken See Replacement Parts on page 36 Replace ember mat...

Page 32: ...en in stalled 5 Depleted gas supply pro pane LP models only 6 Pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or t...

Page 33: ...ny 2 Clean burner see Clean ing and Maintenance page 30 or replace burner orifice 1 Clean burner see Clean ing and Maintenance page 30 or replace burner orifice 2 Replace damaged burner 3 Replace gas...

Page 34: ...log grate removal 2 Check vent configuration specifications see Venting Installation page 9 1 This is normal If noise is excessive contact qualified service person 1 Replace 9 volt batteries in receiv...

Page 35: ...leak See Warning statement above 2 Control valve defective 1 Gas leak See Warning statement above OBSERVED PROBLEM Fireplace produces un wanted odors Fireplace shuts off in use Gas odor even when cont...

Page 36: ...8 x 23 1 2 102 x 122 x 60 cm Replacement Parts Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty Contact authorized dealers of this pr...

Page 37: ...supply these accessories call FMI PRODUCTS LLC at 1 866 328 4537 for information You can also write to the ad dress listed on the back page of this manual Brick Liner kit BL42D A Textured Refractory...

Page 38: ...www fmiproducts com 116239 01M 38 Parts Models V KC42 N P AND V KCC42 N P Series 6 7 20 17 18 13 2 12 19 8 1 4 24 11 9 14 3 16 5 15 21 10 23 25 26 22 27 28 28 29 29...

Page 39: ...ssembly 1 6 Fireplace Top 1 7 Fireplace Top Insulation 1 8 Fireplace Surround 1 9 109082 01 Heat Shield 1 10 116542 01 Burner Assembly NG See page 40 1 116542 02 Burner Assembly LP See page 40 1 11654...

Page 40: ...www fmiproducts com 116239 01M 40 PARTS Burner assembly models V KC42 N P AND V KCC42 N P Series 7 15 10 12 1 12 2 3 13 9 11 21 22 TPTH TP TH 6 12 14 18 17 17 18 19 20 16 14 8 4 5...

Page 41: ...11288 02 Flex Gas Line 1 10 108084 02 Pilot Assembly NG 1 108084 03 Pilot Assembly LP 1 108084 05 Pilot Assembly HA Models 1 11 14389 Natural Gas Valve 1 14390 Propane LP Gas Valve 1 117370 01 Natural...

Page 42: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Page 43: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Page 44: ...s product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic ma...

Reviews: