VENTING INSTALLATION

Continued

  WARNING:  Do  not  recess 

vent termination into any wall. 

This will cause a fire hazard.

6. 

Noncombustible Exterior Wall:

 Position 

horizontal vent cap in center of 8 

1

/

2

" round 

hole and attach to exterior wall with four 
wood screws provided. Before attaching 
vent  cap  to  exterior  wall,  run  a  bead  of 
non-hardening  mastic  (pliable  sealant) 
around  outside  edges  to  make  a  seal 
between it and outside wall.

 

Note: Four wood screws provided should 
be replaced with appropriate fasteners for 
stucco, brick, concrete or other types of 
sidings.

 

Combustible  Exterior  Wall:

  For  vinyl 

siding, stucco or wood exteriors, a siding 
standoff  may  be  installed  between  vent 
cap  and  exterior  wall.  Siding  standoff 
prevents excessive heat from damaging 
siding materials. Siding material must be 
cut  to  accommodate  standoff.  Bolt  vent 
cap  to  standoff.  Apply  non-hardening 
mastic around outside edge of standoff. 
Position standoff/cap assembly in center 
of 11 

1

/

2

" square hole and attach to exte

-

rior wall with wood screws provided (see 
Figure 11). Siding standoff must sit flush 
against exterior fascia material.

7. 

Connecting Vent Cap with Horizontal 
Vent Pipe:

 Slide wall firestop over vent 

pipe before connecting horizontal run to 
vent cap (see Figure 12).

 

Carefully  move  fireplace,  with  vent  as

-

sembly attached, toward wall and insert 
vent pipe into horizontal termination. Pipe 
overlap should be a minimum of 1

1

/

4

" (see 

Figure 13, page 12).

 

Slide  wall  firestop  against  interior  wall 
surface and attach with screws provided. 
See  Figure  13,  page  12,  for  horizontal 
termination details.

 

Place fireplace into position and shim with 
noncombustible material if needed. Nail or 
screw side flanges to framing to secure 
unit in place. 

IMPORTANT:

 Make sure fire

-

place is level before securing. If fireplace 
is not level it will not work properly.

Figure 10 - Installing Horizontal Vent Cap 

(Noncombustible Exterior)

Wood Screw

Vent Cap

Figure 11 - Installing Siding Standoff 

(Combustible Exterior Wall)

Cut Siding Away to 
Fit Standoff

Wood 
Screw

Screws

Standoff

Vent 
Cap

Apply Mastic to 
All Four Sides

Vent Cap 
(Horizontal 
Termination)

Interior Wall 
Surface

Wall 
Firestop

Horizontal 
Vent Pipe

Figure 12 - Connecting Vent Cap with 

Horizontal Vent Pipe

Screw

Apply 
Mastic to All 
Four Sides

Summary of Contents for KC42N series

Page 1: ...se gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not...

Page 2: ...c tive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble op erate or service this log set Improper use of this log set can cause serious injury or death from burn...

Page 3: ...accessory not approved for use with this fire place WARNING This appliance is only for use with the type of gasindicatedontheratingplate Thisapplianceisnotconvertible for use with other gases unless a...

Page 4: ...d pilot light before cleaning fireplace 6 Have venting system inspected annually by a qualified service person If needed have venting system cleaned or repaired See Cleaning and Maintenance page 30 7...

Page 5: ...r proper operation You must follow the venting instructions very carefully for either vertical or horizontal applications This fireplace may be installed in any room of your house provided all local c...

Page 6: ...to prevent accidental blockage of venting system When using snow blowers do not direct snow towards vent termination area For horizontal installations above 2 000 feet it is recommended that a 12 ext...

Page 7: ...l Vent C B A D E F G Top of Louver Opening 3 2 1 4 5 6 7 Wall Figure 5 Framing Clearances for Corner Installation Ref Mantel Depth Ref Mantel from Top of Louver Opening 1 14 A 16 2 12 B 14 3 10 C 12 4...

Page 8: ...n US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally...

Page 9: ...inate on the out side of the structure and can not be attached to a chimney or flue system serving a separate solid fuel or gas burning appliance Adirect vent appliance must have its own venting syste...

Page 10: ...on male ends of adjacent pipes Push pipe sections together and twist one section clockwise approximately one quarter turn until the sections are fully locked see Figure 8 Note Horizontal runs of vent...

Page 11: ...screws provided see Figure 11 Siding standoff must sit flush against exterior fascia material 7 Connecting Vent Cap with Horizontal Vent Pipe Slide wall firestop over vent pipe before connecting hori...

Page 12: ...uired NOTICE Donotsealtermination cap to vent pipe Cap must be removable for vent inspection and maintenance WARNING Never run vent downward as this may cause excessive temperatures which could cause...

Page 13: ...Recommended Applications Installations requiring a vertical rise on building exterior Any installation using snorkel termination to achieve one foot above ground Snorkel terminations are available for...

Page 14: ...for a horizontal system using two 90 elbows Figure 18 Horizontal Termination Configuration for Venting Using Two 90 Elbows with Termination at 90 with Fireplace 45 Elbow Venting with Two 90 Elbows Ve...

Page 15: ...above ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insula tion from falling into required clearance space If area above ceiling is a living space instal...

Page 16: ...High Wind Termination Shown 45 Elbow Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 2 max 6 min 4 max 7 min 6 max 8 min 8 max 20 max 8 max Note Install restrictor into inner...

Page 17: ...elevations from 0 2000 feet Fireplaces for High Altitude models ending in HA are for installation above 4000 feet only These fireplaces are equipped with parts specific for higher altitudes When insta...

Page 18: ...m Collar Roof Flashing 0 12 6 12 26 Screws VKC 58 Corner Vent Kit Galvanized Includes 45 Elbow 7 12 Adjustable Pipe Wall Firestop Horizontal Termination 6 Pipe 90 Elbow 18 Screws HHTK 58 High Wind Rou...

Page 19: ...ed upward Blower will fit inside back opening and be held in position against back wall by magnets see Figure 26 4 Be certain that all wire terminals are securely attached to terminals on blower motor...

Page 20: ...ower cord outer insulation sleeve may have to be stripped slightly to allow enough wire length to reach and make all connec tions DO NOT trim excessive length away Enable just enough to make all conne...

Page 21: ...ue Variable Fan Switch Fan Switch N O Green White On 110 115 V A C Blower Motor Black Off 1 2 Black Installing Gas Piping to Fireplace Location WARNING A qualified service person must connect fireplac...

Page 22: ...you install a sediment trap drip leg in supply line as shown in Figure 32 Locate sediment trap drip leg where it is within reach for cleaning Install in piping sys tem between fuel supply and fireplac...

Page 23: ...gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace or using compressed air 4 Check all joints of gas supply piping sys tem Apply noncorrosive leak detection...

Page 24: ...3 Connect one bare wire end to each termi nal of the GWMS2 wall switch 4 Install wall switch and cover in the wall Fireplace Installation Continued Figure 37 Connecting Wall Switch to Control Valve To...

Page 25: ...screen door tabs with slot openings in upper face frame Swing door screen assembly in towards the bottom face 4 Remount new frame at hinge with five new screws before closing door This will ensure sea...

Page 26: ...n and close louvers see Removing Glass Door steps 5 through 7 page 25 WARNING The glass door mustbesecurelyinplacebefore runningthisfireplace Donotrun this fireplace if glass is missing or broken Fire...

Page 27: ...RE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to l...

Page 28: ...Push in gas control knob slightly and turn clockwise to OFF 5 Close lower louver panel MANUAL LIGHTING PROCEDURE 1 Remove glass door see Removing Re placing Glass Door page 24 2 Follow steps 1 through...

Page 29: ...osi tion blower will not operate Note for BKT Only If you are using BKT blower with optional thermostat wall mounted or remote control for fireplace your fireplace and blower will not turn on and off...

Page 30: ...peration Thereafter clean the glass two or three times during each heating season depending on the usage and circumstances present Refer to Removing Replacing Glass Door page 24 of this manual when re...

Page 31: ...lling Lava Rock and Glowing Embers page 26 to properly replace logs Use a vacuum cleaner to remove any carbon buildup on logs Replace log s if broken See Replacement Parts on page 36 Replace ember mat...

Page 32: ...en in stalled 5 Depleted gas supply pro pane LP models only 6 Pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or t...

Page 33: ...ny 2 Clean burner see Clean ing and Maintenance page 30 or replace burner orifice 1 Clean burner see Clean ing and Maintenance page 30 or replace burner orifice 2 Replace damaged burner 3 Replace gas...

Page 34: ...log grate removal 2 Check vent configuration specifications see Venting Installation page 9 1 This is normal If noise is excessive contact qualified service person 1 Replace 9 volt batteries in receiv...

Page 35: ...leak See Warning statement above 2 Control valve defective 1 Gas leak See Warning statement above OBSERVED PROBLEM Fireplace produces un wanted odors Fireplace shuts off in use Gas odor even when cont...

Page 36: ...8 x 23 1 2 102 x 122 x 60 cm Replacement Parts Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty Contact authorized dealers of this pr...

Page 37: ...supply these accessories call FMI PRODUCTS LLC at 1 866 328 4537 for information You can also write to the ad dress listed on the back page of this manual Brick Liner kit BL42D A Textured Refractory...

Page 38: ...www fmiproducts com 116239 01M 38 Parts Models V KC42 N P AND V KCC42 N P Series 6 7 20 17 18 13 2 12 19 8 1 4 24 11 9 14 3 16 5 15 21 10 23 25 26 22 27 28 28 29 29...

Page 39: ...ssembly 1 6 Fireplace Top 1 7 Fireplace Top Insulation 1 8 Fireplace Surround 1 9 109082 01 Heat Shield 1 10 116542 01 Burner Assembly NG See page 40 1 116542 02 Burner Assembly LP See page 40 1 11654...

Page 40: ...www fmiproducts com 116239 01M 40 PARTS Burner assembly models V KC42 N P AND V KCC42 N P Series 7 15 10 12 1 12 2 3 13 9 11 21 22 TPTH TP TH 6 12 14 18 17 17 18 19 20 16 14 8 4 5...

Page 41: ...11288 02 Flex Gas Line 1 10 108084 02 Pilot Assembly NG 1 108084 03 Pilot Assembly LP 1 108084 05 Pilot Assembly HA Models 1 11 14389 Natural Gas Valve 1 14390 Propane LP Gas Valve 1 117370 01 Natural...

Page 42: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Page 43: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Page 44: ...s product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic ma...

Reviews: