background image

8

105194

UNVENTED PROPANE/LP GAS LOG HEATER

FIREPLACE MANUFACTURERS INCORPORATED

INSTALLATION

Continued

Minimum Noncombustible
Material Clearances

If Not Using Mantel

Note:

 If using a mantel, proceed to If Using

Mantel. If not using a mantel, follow the
information below.

You must have noncombustible material(s)
above the fireplace opening. Noncombus-
tible materials (such as slate, marble, tile,
etc.) must be at least 1/2 inch thick. With
sheet metal, you must have noncombustible
material behind it. Noncombustible material
must extend at least 8" up (for all models). If
noncombustible material is less than 12", you
must install the fireplace hood accessory (24"
and 30" models only). See Figure 5 to the
right for minimum clearances.

IMPORTANT:

 If you cannot meet these

minimum clearances, you must operate
heater with chimney flue damper open. Go
to Installing Damper Clamp Accessory for
Vented Operation
, page 10.

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

Heat Resistant
Material 

(A)

Noncombustible

Requirements for

Material Distance (A)

Safe Installation

12" or more

Noncombustible material OK.

Between  8"  and  12"

24", or 30" Models: Install fireplace hood accessory
(GA6050, GA6052, or GA6053, see 

Accessories,

page 21).

18" Model: Noncombustible material OK.

Less than 8"

Noncombustible material must be extended to at
least 8". See 

Between 8" and 12", above. If you

cannot extend material, you must operate heater
with flue damper open.

NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney flue damper open.
If running heater with damper
open, noncombustible material
above fireplace opening is
needed. Go to 

Installing Damper

Clamp Accessory for Vented
Operation, page 10.

If Using Mantel

You must have noncombustible material(s)
above the fireplace opening. Noncombus-
tible materials (such as slate, marble, tile,
etc.) must be at least 1/2 inch thick. With
sheet metal, you must have noncombustible
material behind it. Noncombustible mate-
rial must extend at least 8 inches up (for all
models). If noncombustible material is less
than 12", you must install the fireplace hood
accessory (24" and 30" models only). Even

if noncombustible material is more than
12", you may need the hood accessory to
deflect heat away from your mantel shelf.
See Figure 5, and Figures 6 and 7, page 9,
for minimum clearances.

IMPORTANT:

 If you cannot meet these

minimum clearances, you must operate
heater with chimney flue damper open. Go
to Installing Damper Clamp Accessory for
Vented Operation
, page 10.

Summary of Contents for Heat Majic FVF18PW

Page 1: ...cause injury or property damage Refer to this manual for correct installa tion and operational procedures For as sistance or additional information con sult a qualified installer service agency or the gas supplier WARNING This appliance is for installa tion only in a solid fuel burning masonry or UL127 factory built fireplace or in an approved ventless firebox It is design certified for these inst...

Page 2: ... is closed before running heater Keeptheapplianceareaclearand free from combustible materials gasoline and other flammable vapors and liquids 1 This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases 2 Do not place propane LP supply tank s inside any structure Locate propane LP supply tank s outdoors 3 To prevent ...

Page 3: ...urner This could damage heater Always handle base assembly by grate 2 Remove all protective packaging ap plied to logs and heater for shipment 3 Check all items for any shipping dam age If damaged promptly inform dealer where you bought heater Figure 1 Product Identification Control Knob Piezo Ignitor One Piece Log Set Base Assembly Flame Adjustment Knob REMOTE CONTROL ACCESSORIES There are four o...

Page 4: ...R COMBUSTION AND VENTILATION Today s homes are built more energy effi cient than ever New materials increased insulation and new construction methods helpreduceheatlossinhomes Homeowners weather strip and caulk around windows and doorstokeepthecoldairoutandthewarmair in During heating months home owners want their homes as airtight as possible While it is good to make your home energy efficient yo...

Page 5: ...outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the space can support _________________ Btu Hr actual amount of Btu Hr used Example 51 200 Btu Hr maximum the space can support 71 500 Btu Hr actual amount of Btu Hr used The space in the above example is a confined space because the actual Bt...

Page 6: ...a fresh air by using ventilation grills or ducts You must provide two per manent openings one within 12 of the ceiling and one within 12 of the floor Connect these items directly to the outdoors orspacesopentotheoutdoors Thesespaces include attics and crawl spaces Follow the NationalFuelGasCodeANSIZ223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills...

Page 7: ...mps etc in the air exist may discolor walls or cause odors IMPORTANT Vent freeheatersaddmois ture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture See Air for Com bustion and Ventilation pages 4 through 6 CHECK GAS TYPE Useonlypropane LPgas Ifyourgassupply is not propane LP do not install heater Call de...

Page 8: ...e hood accessory GA6050 GA6052 or GA6053 see Accessories page 21 18 Model Noncombustible material OK Less than 8 Noncombustible material must be extended to at least 8 See Between 8 and 12 above If you cannot extend material you must operate heater with flue damper open NOTICE Manual control heaters maybeusedasaventedproduct If so you must always run heater with chimney flue damper open If running...

Page 9: ...ual NOTICE If your installation does notmeettheminimumclearances shown you must do one of the following operate the logs only with the flue damper open raise the mantel to an accept able height remove the mantel FLOOR CLEARANCES A If installing appliance on the floor level you must maintain the minimum dis tance of 14 to combustibles see Fig ure 8 B If combustible materials are less than 14 to the...

Page 10: ...ng Flexible Gas Hose to Heater Fitting Flexible Gas Hose if allowed by local codes CAUTION Do not remove the metal data plates attached to the heater base assembly The data platescontainimportantwarranty and safety information INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION Note When used as a vented heater appli ance must be installed only in a solid fuel burning fireplace with a working f...

Page 11: ... in Figure 14 page 12 Locate sediment trap where it is within reach for cleaning Install in piping system between fuel supply and heater Locate sediment trap where trapped matter is not likely to freeze A sediment trap traps moistureandcontaminants Thiskeepsthem from going into heater controls If sediment trap is not installed or is installed wrong heater may not run properly WARNING Usepipejoints...

Page 12: ...en installed between propane LP supply and heater SeeguidelinesunderCon necting to Gas Supply page 11 CHECKING GAS CONNECTIONS Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Figure 15 2 Pressurize supply piping system by ei ther using compressed air or opening propane LP supply tank valve 3 Check all joints from propane LP sup ply tank to equipment shutof...

Page 13: ...t in Chassis Chassis Control Valve Location Propane LP Supply Tank Equipment Shutoff Valve CAUTION After installation andperiodicallythereafter check to ensure that no flame comes in contact with any log With the heater set to High check to see if flames contact any log If so re position logs according to the loginstallationinstructionsinthis manual Flames contacting logs will create soot INSTALLI...

Page 14: ...r NOTICE During initial operation of new heater burning logs will give off a paper burning smell Open damper or window to vent smell Thiswillonlylastafewhours Note Home owners generally prefer to operate their heater with the chimney damper closed This will put all the heat into the room However there may be times you will desire the full flames of the HI heat setting but will find the heat output...

Page 15: ... The ideal comfort setting will vary by household depending upon the amount of space to be heated the output of the central heating system etc For wall thermostat operation follow in struction supplied with thermostat acces sory GWMT1 For wall switch operation followinstructionssuppliedwithGWMS2 1 Follow steps 1 through 6 under Light ing Instructions page 14 2 Depress control knob and light pilot ...

Page 16: ... comeblockedbydebrisorrust withnoflame present If so turn off heater and let cool Remove blockage Blocked burner flame holes will create soot Figure 23 Thermostat Hand Held Remote Control Unit Selections GHRCTA Series Only GHRCTA Series Operation 2b Press the AUTO ON OFF button on the hand held remote control see Figure 22 page 17 The lights to the left of the button will show AUTO ON or OFF In th...

Page 17: ...t ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set Nut is located behind base panel 4 Replace ignitor cable 5 Replace piezo ignitor 6 Replace pilot assembly 7 Replace pilot assembly 1 Turn on gas supply or open equipment shutoff valve 2 Turn control knob to PILOT position 3 Press in control knob...

Page 18: ...r for Combustion and Venti lation requirements page 4 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Observe minimum installation clear ances see pages 7 through 9 4 Clean burner see Cleaning and Mainte nance page 20 or replace burner orifice 1 Turn heater off when using furnit...

Page 19: ... most heaters If noise is excessive contact qualified ser vice person 1 Open window and ventilate room Stop using odor causing products while heater is running 2 Locate and correct all leaks see Check ing Gas Connections page 12 1 Open window and or door for ventilation 2 Contact local propane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 20 1 Locate and correct all leaks see ...

Page 20: ...LDER AND PILOT AIR INLET HOLE The primary air inlet holes allow the proper amount of air to mix with the gas This provides a clean burning flame Keep these holes clear of dust dirt lint and pet hair Clean these air inlet holes prior to each heating season Blocked air holes will cre ate soot We recommend that you clean the unit every three months during operation and have heater inspected yearly by...

Page 21: ... s technical service web site at www desatech com FIREPLACE HOOD Black GA6050 Brass GA6052 Antique Brass GA6053 For all models Helps deflect heat away from mantel or wall above fireplace Fits openings 28 to 48 wide WIRING DIAGRAM Note For proper operation of optional accessories the wires from the switch to the control must be connected exactly as shown RECEIVER AND HAND HELD THERMOSTAT REMOTE CON...

Page 22: ... FIREPLACE MANUFACTURERS INCORPORATED ILLUSTRATED PARTS BREAKDOWN HEAT MAJIC LOG MODELS FVF18PW FVF24PW AND FVF30PW 4 13 13 14 22 13 8 18 7 6 10 9 1 12 5 23 16 15 17 3 11 2 10 19 24 19 20 21 O F F P I L O T O N H I L O O F F P I L O T O N H I L O ...

Page 23: ...3345 01 103345 01 Lower Bracket 1 13 M11084 38 M11084 38 M11084 38 Screw 8 x 38 7 14 102775 10CK 102775 06CK 102775 08CK Painted Base Assy 1 15 098271 07 098271 07 098271 07 Ignitor Cable 1 16 102445 01 102445 01 102445 01 Piezo Ignitor 1 17 103587 02CK 103587 02CK 103587 02CK Plate Switch 1 18 104099 01 104099 01 104099 01 Heat Shield 1 19 098304 01 098304 01 098304 01 Screw 2 20 103784 02 103784...

Page 24: ... The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost la...

Reviews: