background image

 

4

          OWNER 

MANUAL 

 
AIR FOR  
COMBUSTION AND 
VENTILATION 

 

Continued 

 

DETERMINING FRESH-AIR FLOW FOR FIREBOX LOCATION 

 

Determining if You Have a Confined or Unconfined Location 

 

Use this work sheet to determine if you have a confined or unconfined space. 

 

Space: 

Includes the room in which you will install firebox plus any adjoining rooms with odorless passageways or ventilation grills 

between the rooms. 

 

1.  Determine the volume of the space (length x width x height). 

Length x width x height = _______________________ cu. Ft. (volume of space) 
EXAMPLE: Space size 22 ft. (length) x 18 ft (width) x 8 ft. (ceiling height)= 3168 cu. ft. (volume of space) 
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of 
the space. 

 

2.  Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support. 

______________________ (volume of space) divide by 50 cu. ft. = 63.3 or 63,300 (maximum Btu/Hr the space can support) 

 

3.  Add the Btu/Hr of all fuel burning appliances in the space. 

Gas water heater* 

 

__________________   Btu/Hr 

Gas furnace   

 

__________________   Btu/Hr  

EXAMPLE: 

Vented gas heater 

 

__________________   Btu/Hr 

 

Gas water heater     40,000  Btu/Hr 

Gas firebox heater 

 

__________________   Btu/Hr 

 

Gas firebox 

    

Other gas appliances*  

+  ________________   Btu/Hr 

 

Logs 

 

 + 39,000  Btu/Hr 

Total 

 

 

=  ________________   Btu/Hr  

 

Total 

 

 = 79,000  Btu/Hr 

 

*Do not include the direct vent gas appliances. Direct Vent draws combustion air from the outdoors and vents to the outdoors. 

4.  Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used. 
        ______________ Btu/Hr (maximum the space of Btu-Hr can support) 
        ______________ Btu/Hr (actual amount of Btu/Hr used)  
 

EXAMPLE:   63,300 Btu/Hr (maximum the space can support) 

 

 

         79,000 Btu/Hr (actual amount of Btu/Hr used) 

 
The space in the above example is a confined space because the actual Btu/Hr used is more that the maximum Btu/Hr the space can 
support. You must provide additional fresh air. Your options are as follows: 

A.  Rework work sheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove the 

door to adjoining room or add ventilation grills between rooms. See 

Ventilation Air from Inside Building

, page 5. 

B.  Vent room directly to the outdoors. See 

Ventilation Air from Outdoo

rs, page 5. 

C.  Install a lower Btu/Hr gas log heater, if lower Btu/Hr size makes room unconfined. 

 

If the actual Btu/Hr used is less that the maximum Btu/Hr the space can support, the space is an unconfined space. You will 
need no additional fresh air ventilation.  
 

 

WARNING: If the area in which the firebox and gas log heater may be operated is smaller than

that defined as an unconfined space or if the building is of unusually tight constructions, provide
adequate combustion and ventilation air by one of the methods described in the National Fuel Gas
Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes. 

Summary of Contents for FGPN

Page 1: ...ly call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a...

Page 2: ...n hot for a time after shutdown Allow surfaces to cool before touching 13 Carefully supervise young children when they are in the same room with the firebox 14 Turn the firebox off and let cool before...

Page 3: ...d without the blower the firebox requires no electricity making it ideal for emergency back up heat BLOWER ACCESSORY The firebox will accept the CBKUVPN accessory The variable blower allows you to sel...

Page 4: ...fy your space provide adequate ventilation Unusually Tight Construction The air that leaks around door and windows may provide enough fresh air for combustion and ventilation However in buildings of u...

Page 5: ...Total 79 000 Btu Hr Do not include the direct vent gas appliances Direct Vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with...

Page 6: ...ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor Con...

Page 7: ...the floor is 0 inches E Clearances from the open end of the firebox to the facing wall should not be less than 36 inches Minimum clearances to combustible are Back of outer casing 0 min Drywall to sid...

Page 8: ...rances shown in Figure 7 Follow the instructions below to install the firebox in this manner 1 Frame in rough opening The firebox framing should be constructed of 2 x 4 lumber or heavier Construct fra...

Page 9: ...rebox combustible materials such as wall board gypsum board sheet rock drywall plywood etc may be butted up next to the side and top of the firebox Combustible materials should never overlap the fireb...

Page 10: ...coming NPT black iron gas line You may also route the eincoming NPT black iron gas line directly to the appliance regulator Remove the gas line cover plate from the vent free firebox s outer surround...

Page 11: ...ing provided see Figure 15 The receptacle may be relocated to either side when necessary However the cover plate must be replaced over the unused access point Be certain to properly ground the vent fr...

Page 12: ...erly 5 Apply gentle force between hook and loop mounting strips to seat blower 6 Remove control knob and lock nut from blower speed control shaft 7 Place the speed control shaft through 3 8 hole provi...

Page 13: ...alter the setting on the pilot assembly See the operating instructions supplied with your vent free log heater for additional cleaning instructions IMPORTANT Turn off the gas supply at the external s...

Page 14: ...rn the defective part to the factory PART NOT UNDER WARRANTY Contact authorized dealer of this product If they can t supply original replacement part s call Fireplace Manufacturer s Part Department at...

Page 15: ...t circulation and may be be installed during or after firebox installation POLISHED BRASS HOOD FGA6017 For End 02240 FGA6054 For Sides 02239 Replaces the standard black hoods to provide a more formal...

Page 16: ...15 ILLUSTRATED PARTS BREAKDOWN Model FGPN UNVENTED VENT FREE FIREBOX...

Page 17: ...de Refractory Retainer 2 9 12125 Screen 4 10 26752 Louver Assy Black 2 11 26733 Lower Door Panel 2 12 14200 Receptacle 1 13 21171 Access Hole Cover 3 14 12126 Screen 1 15 26771 Louver Assy End 1 16 11...

Page 18: ...BURNING CONVENTIONAL FIREPLACE FUELS SUCH AS WOOD COAL OR ANY OTHER SOLID FUEL WILL CAUSE DAMAGE TO THE GAS APPLIANCE WILL PRODUCE EXCESSIVE TEMPERATURES AND WILL RESULT IN A FIRE HAZARD LIMITATION OF...

Reviews: