background image

www.fmiproducts.com

123492-01F

8

IMPORTANT:

 Vent-free gas log heaters add 

moisture to the air. Although this is beneficial, 
installing  firebox  in  rooms  without  enough 
ventilation air may cause mildew to form from 
too  much  moisture.  See 

Air  for  Combustion 

and Ventilation

, page 5. 

IMPORTANT:

 Make sure firebox is level. If fire-

box is not level, log set will not work properly. 

Note: Your firebox is designed to be used in zero 
clearance installations. Wall or framing material can 
be placed against any exterior surface on the rear, 
sides, top or bottom of your firebox, except where 
standoff spacers are integrally attached. If standoff 
spacers are attached to your firebox, these spac-
ers can be placed directly against wall or framing 
materials. Use the dimensions shown for rough 
opening to create the easiest installation.

Use  dimensions  shown  for  rough  openings 
to create the easiest installation (see 

Built-In 

Firebox Installation

, page 9).

INstAllAtIoN cleARANces

  WARNING:  maintain  the 

minimum clearances. if you can, 

provide greater clearances from 

floor, ceiling and adjoining wall.

Carefully  follow  these  instructions. This  will 
ensure safe installation.

Minimum wall and Ceiling Clearances (see 
figure 4)

A.  Clearances  from  the  side  of  fireplace 

cabinet to any combustible material and 
wall should follow diagram in Figure 4.

 

Example:

 The face of a mantel, bookshelf, 

etc. is made of combustible material and 
protrudes 3 

1

/

2

" from the wall. This com-

bustible material must be 4" from the side 
of the fireplace cabinet (see Figure 4).

B.  Clearances from the top of firebox opening 

to ceiling should not be less than 42".

C.  When firebox is installed on carpeting or 

other  combustible  material,  other  than 
wood flooring, firebox should be installed 
on a metal or wood panel extending the 
full width and depth of enclosure.

D.  Clearances from bottom of firebox to the 

floor is 0".

These fireboxes can be installed as freestanding 
units against a wall with the approved, optional 
cabinet mantels (s

ee 

Accessories

, page 14

) or as 

a built-in unit. Clearances are the same for either 
installation method. 

INSTALLATION

Continued

Figure 4 - Minimum Clearance for 

Combustible to Wall 

*Minimum 16" from Side Wall 

*

 Caution: Do not install fire

-

box directly on carpet or vinyl.

Example

mantel clearances for built-In Installation

If placing custom mantel above built-in firebox, 
you must meet the minimum allowable clear-
ance between mantel shelf and top of firebox 
opening shown in Figure 5, page 9. These are 
the minimum allowable mantel clearances for 
a safe installation. Use larger clearances wher-
ever possible to minimize the heating of objects 
and materials placed on the mantel.

  cAutIoN:  do  not  allow 

the  vent-free  gas  log  heater 

to touch or extend beyond the 

fireplace screen.

notiCe:  surface  temperatures 

of adjacent walls and mantels be

-

come hot during operation. walls 

and  mantels  above  the  firebox 

may  become  hot  to  the  touch. 

if installed properly, these tem

-

peratures meet the requirement 

of the national product standard. 

Follow all minimum clearances 

shown in this manual.

NotIce: If your installation does 

not meet the minimum clearances 

shown, you must do one of the 

following:

•  raise the mantel to an accept

-

able height

•  remove the mantel

Summary of Contents for BV36

Page 1: ...pe unvented room heater for the minimum fireplace size requirement Do not install an appliance in this firebox unless this firebox meets the minimum dimen sions required for the installation This firebox has been tested and approved under ANSI Z21 91 for use with any ANSI Z21 11 2 approved gas logs INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future reference UNVE...

Page 2: ...drafts that alter burner flame patterns Altered burner patterns can cause sooting WARNING Donotuseablow er insert heat exchanger insert orotheraccessorynotapproved for use with this firebox WARNING Improper instal lation adjustment alteration service or maintenance can causeinjuryorpropertydamage Refer to this manual for correct installation and operational procedures For assistance or additional ...

Page 3: ...ids or vapors are used or stored under dusty conditions 6 Do not use this firebox to cook food or burn paper or other objects 7 Turn firebox off and let cool before servic ing Only a qualified service person should service and repair firebox 8 Operating firebox above elevations of 4 500 feet could cause pilot outage 9 Do not use firebox if it has been under water due to shock hazard that could res...

Page 4: ...tall the firebox Before installation consider the following 1 Where the firebox will be located Allow for wall and ceiling clearances see Installa tion Clearances page 8 Product Specifications Figure 1 Firebox Dimensions Right Side View Firebox Top View Front View Outside Air Kit Location Optional Left Side View with Air Kit 2 Everything needed to complete installation 3 These models CANNOT be ins...

Page 5: ...mmunicating directly with the space in which the appliances are installed through openings not furnished with doors are considered a part of the un confined space Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them WARNING This heater shall notbeinstalledinaroomorspace unless the required volume of in door combustion air is provided by the me...

Page 6: ...om the outdoors and vents to the outdoors Example Gas water heater __________ Btu Hr Vent free heater _________ Btu Hr Total _________ Btu Hr Air For Combustion and Ventilation Continued 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _ _________Btu Hr maximum the space can support _ _________Btu Hr actual amount of Btu Hr used Example 63 360 Btu Hr maximum...

Page 7: ...n for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermo stat controlled power vent Heated air entering the attic will activate the power vent Installation Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 Ventilation Grills Into Adjoining Room Option 1 12 12 Outlet Air Ve...

Page 8: ...ce cabinet see Figure 4 B Clearances from the top of firebox opening to ceiling should not be less than 42 C When firebox is installed on carpeting or other combustible material other than wood flooring firebox should be installed on a metal or wood panel extending the full width and depth of enclosure D Clearances from bottom of firebox to the floor is 0 These fireboxes can be installed as freest...

Page 9: ...holes in nailing flange see Figure 7 page 10 6 If using an optional perimeter trim kit install the trim after final finishing and or painting of wall See instructions included with trim accessory for attaching trim 7 Install and properly test gas log heater Follow installation instructions included with the vent free gas log heater that is being installed IMPORTANT When finishing your firebox comb...

Page 10: ... Out One Hole Gas Line Hole Equipment Shutoff Valves Install One Installing Firebox USING OPTIONAL ACCESSORY MANTELS WARNING A qualified ser vicepersonmustinstallfirebox Follow all local codes This firebox may be installed using a cabinet mantel accessory against a wall in your home The firebox and cabinet mantel can be installed directly on the floor A trim kit is included with the mantel accesso...

Page 11: ...rom Illustration Screws Hood 1 2 Thick Liner Side View Firebrick Side Wall Knockout Remove This Area Using optional fiber panels There is a gas knockout in each side panel for the gas line to feed through Determine on which side the gas connection will be located Using a utility knife or cutting blade remove the identified gas knockout CAUTION Do not use ex cessive force to remove the knockout Too...

Page 12: ...ucts com 123492 01F 12 Parts Non Circulating Models BV36 b VBV36 BV42 B and VBV42 Circulating Models BV36L B VBV36L BV42L B and VBV42L 10 13 13 23 4 3 2 1 12 5 14 18 7 9 22 20 21 20 17 16 15 11 8 6 19 24 26 25 24 ...

Page 13: ...4 15 11418 Push On Nut 2 16 107127 01 Screen 2 108424 01 Screen 2 17 20806 Screen Rod 2 108780 01 Screen Rod 2 18 Side Damper Weldment 1 19 107128 01 Gas Conduit 4 20 Firebox Legs Rear 2 21 Firebox Leg Left 1 22 Firebox Leg Right 1 23 123494 01 Hood 1 123494 02 Hood 1 24 124483 01 Side Refractory 2 25 124484 01 Rear Refractory 1 124485 01 Rear Refractory 1 26 20027 Refractory Bracket 2 Not a field...

Page 14: ... part to the factory Parts Not Under Warranty Contact authorized dealers of this product If they can t supply original replacement part s call FMI PRODUCTS LLC at 1 866 328 4537 for referral information A list of authorized dealers can be found by visiting www fmiproducts com When calling FMI PRODUCTS LLC have ready model and serial numbers of your heater the replacement part number Technical Serv...

Page 15: ..._______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________...

Page 16: ...is product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material labor and incidental costs associated with warranty repairs unless expressly covered by this warranty are not reimbursable under this warranty and are the responsibility of the owner Excluded ...

Reviews: