6

For more information, visit www.desatech.com

 

5.  Do not insulate on top of the firebox.  The opening in the 
collar around the chimney at the top of the fireplace must not 
be obstructed (see figure 11). 

 
6. Before finishing the fireplace enclosure, inspect all joints of 
the outer firebox.  Seal any gaps of the outer firebox with a 
non-combustible material.  Caulk any gaps between the 
nailing flange and framing. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
   
 

CHIMNEY SYSTEM: 

 
CHIMNEY HEIGHT 
 
Minimum chimney height measured from bottom of fireplace 
to flue gas outlet-end of the termination is: 
Straight 

run 

   16 

feet 

Run with one elbow set   

 

16 feet 

Run with two elbow sets   

 

30 feet 

 
An elbow set is consist of one starter elbow and one return 
elbow.  Uncommon circumstances such as neighboring hills, 
tall trees, or strong wind areas can cause downdrafts in the 
chimney system.  In such cases, going beyond the minimum 

recommended height would be preferable to provide a better 
draw. 
Maximum height approved for any chimney run with this 
fireplace system is 60 feet as measured from the bottom of the 
fireplace to the flue outlet-end of the termination. 
 
ASSEMBLING AND INSTALLING THE DOUBLE WALL 
CHIMNEY SYSTEM 
 
The DESA chimney system consists of 12, 18, 24, 36 and 48-
inch, snap-lock double-wall pipe segments, planned for 
maximum adaptability to individual site requirements.  Actual 
lengths gained (lineal gain) after fitting overlaps must be taken 
into consideration (see figure 12). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Each double wall chimney section consists of a galvanized 
outer pipe, a stainless steel inner flue pipe and a wire spacer. 
The pipe sections must be assembled independently as the 
chimney is installed.  When attaching the chimney directly to 
the fireplace, the inner flue pipe section must be installed first 
with the female side up (see figure 12).  The outer pipe section 
can then be installed over the flue pipe section with the male 
end up. 
 
Press down on each pipe section until the lances securely   
engage the hem on the fireplace starter.  The wire will assure 
the proper spacing between the inner and outer pipe sections 
(see figure 12). 
 
Continue to assemble chimney sections as outlined above, 
making sure that both the inner and outer pipe sections are 
locked together. 
 
When installing double wall “snap-lock” chimney together, it 
is important to insure that the joint between the chimney 
sections is locked.  Check by pulling chimney upward after 
locking.  The chimney will not come apart if properly locked.  
It is not necessary to add screws to keep the chimney together.  
However, if desired, use screws per directions provided on 
page 7, figure 14.

 

 

Figure 10    COLD CLIMATE INSTALLATION 

Figure 11    FIREPLACE COLLAR OPENING 

Figure 12                    LINEAL GAIN 

Summary of Contents for BAJA 3600

Page 1: ...approved to ANS Z21 11 2 standard A DESA hood must be installed when using a vent free gas log set See accessories on pg 11 WARNING ALWAYS LEAVE GLASS DOORS FULLY OPENED OR FULLY CLOSED WHEN OPERATING THIS FIREPLACE DESA INTERNATIONAL 2701 INDUSTRIAL DRIVE P O BOX 90024 BOWLING GREEN KY 42102 9004 www desatech com PN 54139 REV C 3 01 SAVE THIS BOOK This book is valuable In addition to instructing ...

Page 2: ...ALLING THE FIREPLACE PG 3 8 HEARTH EXTENSION PG 4 9 OUTSIDE AIR KIT PG 4 10 GAS LINE INSTALLATION PG 4 11 VENT FREE GAS LOG INSTALLATION PG 5 12 COLD CLIMATE INSTALLATIONS PG 5 13 CHIMNEY PIPE PG 6 7 14 PENETRATING THE ROOF PG 8 15 FLASHING INSTALLATION PG 9 16 STORM COLLAR INSTALLATIONS PG 9 17 TERMINATIONS PG 9 18 FINISHING THE FIREPLACE PG 10 19 MANTEL CLEARANCES PG 10 17 REPLACEMENT AND ACCESS...

Page 3: ...tinuous operation of this fireplace SELECTING LOCATION To determine the safest and most efficient location for your fireplace consider the following guidelines The location must allow for all proper clearances see page 3 The location should be in a place where the fireplace will not be affected by drafts such as air condition ducts windows or doors A location that avoids the cutting of joists or r...

Page 4: ...ing flanges touch the side framing STEP 4 Check the level of the fireplace and shim with sheet metal if necessary STEP 5 Before securing fireplace to prepared framing the ember protector provided must be placed between hearth extensions not supplied and under the bottom front edge of the fireplace to protect against glowing embers falling through If the fireplace is to be installed on a raised pla...

Page 5: ...KIT MODEL AK4E The outside air kit must be installed during the rough framing of the fireplace due to the nature of its location Outside combustion air can be accessed through an exterior wall See figure 6 and Accessories on page 11 Avoid installing outside air eyebrow in areas where inlet opening may be blocked by snow bushes or other obstacles It should also be located beyond the reach of childr...

Page 6: ...t be installed when using an unvented gas log set see accessories on page 11 VENTED GAS LOG INSTALLATION If you install a decorative gas appliance vented gas log the decorative gas appliance must comply with the Standard for Decorative Gas Appliance for Installation in solid fuel burning fireplace ANS Z21 60 1996 Z21 84 or RGA 2 72 and shall also be installed in accordance with the National Fuel G...

Page 7: ...e wall pipe segments planned for maximum adaptability to individual site requirements Actual lengths gained lineal gain after fitting overlaps must be taken into consideration see figure 12 Each double wall chimney section consists of a galvanized outer pipe a stainless steel inner flue pipe and a wire spacer The pipe sections must be assembled independently as the chimney is installed When attach...

Page 8: ...as required by most codes When the double wall pipe passes through a framed opening into an attic space the firestop must be place into the attic floor as in figure 16 When the pipe passes through a framed opening into a living space above the firestop must be placed onto the ceiling from below as shown in figure 16 1 elbow set 16 to 60 ft system height 2 elbow sets 30 to 60 ft system height Figur...

Page 9: ...termine the correct opening length and flashing required STEP 4 Remove the shingles around the opening measured and cut out this section STEP 5 Add the next sections of the pipe until the end penetrates the roofline Check to see that the proper clearances are maintained Extend chimney by adding sections of double wall pipe until pipe is a minimum of 30 inches above the highest point of the roof cu...

Page 10: ...lashing or chase and ETL 8DM for chase style termination only Figure 21 shows an RTL 8DM round top termination FOLLOW THE INSTALLATION INSTRUCTIONS PROVIDED WITH THE TERMINATION BEING USED CHASE INSTALLATIONS Instructions for chase installations are included with the chase style termination chosen In a multiple chase installation be sure to provide adequate distance between terminations to prevent...

Page 11: ...e placed at least 9 inches above the opening of the fireplace see figure 25 Combustible materials above 9 inches and projecting more than 1 inches from the front face of the fireplace must be place at least 12 inches above the fireplace opening Ref NFPA std 7 3 3 3 Mantels or any other combustible material may butt up to the side of the black metal face of the fireplace The clearances from the sid...

Page 12: ...n visit www desatech com Desa International 2701 Industrial Drive P O Box 90024 Bowling Green KY 42102 9004 www desatech com 800 323 5190 CONTACT YOUR LOCAL DEALER ACCESSORY PARTS CONTACT YOUR LOCAL DEALER REPLACEMENT PARTS ...

Reviews: