4

TERMINATIONS:

 

The fireplace system must be terminated with the listed round 
top or chase terminations.  In any case, refer to the installation 
instructions supplied with the termination.  The termination 
approved for this fireplace are the RT-8DM and RTL-8DM, 
which can be used for flashing or chase and ET-8DM and 
ETO-8DM for chase style termination only.  Figure 11 shows 
a RT-8DM round top termination. 

 
CAUTION:  DO NOT SEAL OPENINGS ON THE ROOF 
TOP FLASHING.  FOLLOW THE INSTALLATION 
INSTRUCTIONS PROVIDED WITH THE TERMINATION 
BEING USED. 
Terminations with 16” slip pipe sections are available.  The 
RTT-8DM and RTTL-8DM are approved for flashing or chase 
installations.  The ETL-8DM and ETLO-8DM are 
terminations that may be used with chase installations only.  
When needed, these adjustable terminations may be used in 
combination with the pipe assembly to achieve the correct 
chimney height. 
 

CHASE INSTALLATIONS 

Instructions for chase installations are included with the chase 
style termination chosen.  In a multiple chase installation, be 
sure to provide adequate distance between terminations to 
prevent smoke spillage from one termination to another.  We 
suggest that terminations be separated at least 30 inches, 
center to center, and stacked at  vertical height difference of 
18 inches (see figure 12).  
 
 
 
 
 
 
 
 
 
 
 
 
 

10 FOOT RULE:

 

All chimney terminations must extend a minimum of 3 feet in 
height above the highest point where it passes through the roof 
and must be at least 2 feet above the peak of the roof if within 
a horizontal distance of 10 feet from the peak. (SEE FIG 13). 

OUTSIDE AIR KIT  (MODEL AK4E) 

The installation of an outside air kit must be installed during 
the rough framing of the fireplace due to the nature of its 
location.  Outside combustion air can be accessed through an 
exterior wall or a vented crawl space  (see figures 14a & 14b). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
CAUTION:  AIR DUCTS MUST NOT TERMINATE IN 
ATTIC SPACE

  

Avoid installing outside air eyebrow in areas where inlet 
opening may be blocked by snow, bushes or other obstacles.  
It should also be located beyond the reach of children.  The 
maximum height of air inlet above platform of fireplace is 3 ft. 
below the termination flue gas outlet. 
For further details on the installation of the outside air kit, 
please refer to the instructions included with the air kit.  For 
operating instructions, please refer to your owner’s manual. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 11

 

 
 
 
 
 
 
 
 
 

Figure 13 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
Figure 14a 

 
 
 
 
 
 
 
 
 
 

Figure 12 

 
 
 
 
 
 
 
 
Figure 14b 

Summary of Contents for 36ECD

Page 1: ...ional accessory items when needed Keep it with your other important papers This Fireplace is approved for use as a Wood Burning Fireplace or for use with a vented gas log approved to ANS Z21 60 Z21 84 or RGA 2 72 Standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard WARNING ALWAYS LEAVE GLASS DOORS FULLY OPENED OR FULLY CLOSED WHEN OPERATING THIS FIREPLACE 36 Wood ...

Page 2: ...chimney sections and the effective height of the termination assembly INSTALLING THE FIREPLACE STEP 1 Frame the opening for the fireplace using the dimensions shown in FIGURE 1 2 or 3 STEP 2 If the fireplace is to be installed directly on carpeting tile other than ceramic or any combustible material other than wood flooring the fireplace must be installed upon a metal or wood panel extending the f...

Page 3: ...REPLACE MUST NOT BE OBSTRUCTED NEVER USE BLOWN INSULATION TO FILL THE CHIMNEY ENCLOSURE SEE FIG 5 Continue to assemble chimney sections as outlined above making sure that both the inner and outer pipe sections are locked together When installing double wall snap lock chimney together it is important to assure the joint between the chimney sections is locked Check by pulling chimney upward after lo...

Page 4: ...r a given span usually 12 inches A 6 12 pitch means that the roof drops 6 inches for each 12 inches one measures horizontally down the roof STEP 3 Use the roof opening chart below to determine the correct opening length and flashing required see figure 8 STEP 4 Remove the shingles around the opening measured and cut out this section STEP 5 Add the next sections of the pipe until the end penetrates...

Page 5: ...t smoke spillage from one termination to another We suggest that terminations be separated at least 30 inches center to center and stacked at vertical height difference of 18 inches see figure 12 10 FOOT RULE All chimney terminations must extend a minimum of 3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the peak of the roof if within a ...

Page 6: ... per chimney system SEE FIGE 17 Figure 17 TYPICAL OFFSET INSTALLATION Figure 15 OFFSET RISE A B 48 36 24 18 12 4 3 8 16 3 8 9 3 4 25 1 2 1 12 3 4 30 3 4 1 15 34 3 4 1 18 40 1 1 21 1 4 46 1 4 1 23 3 4 49 1 4 1 1 27 3 4 56 3 4 1 30 60 3 4 1 1 33 66 1 1 36 71 1 1 38 1 4 75 2 41 1 4 80 1 4 1 1 1 45 86 3 4 2 46 3 4 89 1 2 1 1 1 51 97 1 1 53 1 4 101 2 1 56 1 4 106 1 4 2 59 1 4 111 1 2 1 1 1 61 3 4 115 1...

Page 7: ...fractory knockout hole with refractory cement or commercial furnace cement Install the decorative gas appliance or cap off gas line if desired The gas pipe is intended for connection to a decorative gas appliance vented gas log If you wish to install an unvented gas log set ONLY UNVENTED GAS LOG SETS WHICH HAVE BEEN FOUND TO COMPLY WITH THE STANDARD FOR UNVENTED ROOM HEATERS ANS Z21 11 2 ARE TO BE...

Page 8: ...facturer or supplier of the non combustible material If the hearth extension is to be covered use non combustible material such as tile slate brick concrete metal glass marble stone etc Fasten the hearth extension to the floor to prevent shifting and seal the gap between the fireplace frame and hearth extension with a non combustible material see figure 22 WARNING HEARTH EXTENSION IS TO BE INSTALL...

Page 9: ... OPERATION The damper handle to open and close the damper blade is located inside the firebox at the center towards the back wall Pushing the handle back in the keyway slot will free the damper blade to automatically open To close reach in and push the handle back into the keyhole slot then pull down and forward to lock it in place see figure 26 WARNING Damper handle will remain hot even after the...

Page 10: ...9 REPLACEMENT PARTS ACCESSORY PARTS ...

Reviews: