User name
: Username, only if authentication on the SMTP server is set
Password
: Password, only if authentication on the SMTP server is set
Network port
: Set
25
here (SMTP server)
Pop account id
: leave empty; sequential number, only necessary for "Account Authorization" and "POP3"
(Account type)
Max. bytes per mail
: If there is a specified limit to the size of the email, such a limit is to be entered in bytes.
The email is then split if the size is exceeded.
Use SSL
: Set the encryption method (SSL, STARTTLS or NONE) here if necessary
l
To conclude, click on <Save Settings> and confirm the following message with <OK>.
Email configuration
You can configure the email to be sent in this section.
l
Click on <Edit> under "Email configuration" to edit an existing configuration or click on <Add New> to create
a new configuration. The input mask for the email configuration appears:
Email configuration (type and subject)
Email ID
: Sequential number
Email type
: "Status", "System" and "Unknown” can be selected:
Status
: Channel status e.g. sensor error, warning, alarm etc. An email of this type is sent directly to a
user.
System
: System status e.g. alive and data transmission. These emails are intended for communication
between the CMS and the OMNITREND Center software.
Unknown
: This type can contain any information for a recipient.
Set the type to “Unknown” for the
Test transmission
.
Email Subject
: Email subject line; this should have a meaningful reference to the content.
Attachment type
: If you want the email to contain an attachment, select whether a specific file ("File") or all
measurement data ("All Measurement Data") is to be sent.
VIBGUARD IIoT
24
Commissioning