Fluke VIBGUARD IIoT Commissioning Download Page 1

VIBGUARD

®

IIoT

Commissioning

Edition: 01.10.2018
Doc. no.: LIT 78.221.EN
Translation of the German manual

Type:

 

VIB

 

7.800,

 

VIB 7.810,

 

VIB

 

7.811,

 

VIB

 

7.815,

 

VIB 7.820,

 

VIB

 

7.825

 

Serial

 

number

 

and

 

year

 

of

 

manufacture:

 

see

 

type

 

plate

 

PRODUCER:

 

Fluke Deutschland GmbH, Freisinger Str. 34, 85737 

Ismaning, Germany, + 49 89 99616-0, www.pruftechnik.com

This manual is only intended for use with GL-
certified VIBGUARD CMS on wind turbines.

Summary of Contents for VIBGUARD IIoT

Page 1: ...VIB 7 800 VIB 7 810 VIB 7 811 VIB 7 815 VIB 7 820 VIB 7 825 Serial number and year of manufacture see type plate PRODUCER Fluke Deutschland GmbH Freisinger Str 34 85737 Ismaning Germany 49 89 99616 0...

Page 2: ...loss ari sing from using the product or from using these instructions even if the authors have identified the potential for such a loss The authors do not accept any liability for potential faults in...

Page 3: ...ing personnel 10 2 7 Residual hazards and protective measures 11 3 Preliminary remark 12 3 1 Notebook system requirements 12 3 2 Additional components 12 4 Visual inspection 13 4 1 RPM sensor function...

Page 4: ...9 Process signals 21 10 Configuring Email transmission 22 10 1 Configuration 22 11 Sending a test email 26 4 Edition 10 2018...

Page 5: ...afety notes Warnings are introduced with the keyword CAUTION if there is a danger of personal injury Failure to observe these warnings may result in minor or moderate injury If there is a danger of da...

Page 6: ...available at the following Internet address https www pruftechnik com com About us Company Certificates and Material Safety 2 2 Intended use VIBGUARD IIoT is a stationary condition monitoring system...

Page 7: ...S the safety labels must be attached at a suitable point in the control cabinet 1 Vorsicht Spannung Attention Danger VIB 7 8xx SDH A yellow sticker each on the housing lock and below the power supply...

Page 8: ...umber 239 variant LD LineDrive of the built in board Protective housing The type plate on the protective housing or on the power supply cabling contains the following information about the entire syst...

Page 9: ...ains power supply to the system all other connected circuits must be SELV cir cuits Ensure that the following requirements are noted Use the system in accordance with the intended use Only operate the...

Page 10: ...via the SYSTEM LED The LED lights up orange while the sys tem module is starting up and changes to green normal operation l Check the following points at regular intervals Is there any identifiable d...

Page 11: ...stumble over an improperly laid cable and injure themselves The cable can be damaged due to external influences l Lay the cable in such a way that no one can stumble over it l Use cable ties or a Vel...

Page 12: ...Dual Core 2 4 GHz or equivalent processor Memory RAM at least 3 GB of which at least 1 5 GB is free for the application Hard disk 5 GB free Ethernet interface address can be adjusted CD ROM drive for...

Page 13: ...cor rect CAUTION Danger of property damage Check the distance between the installed sensor and the trigger mark The permissible range is 2 3 to 8 mm If the distance is too small the sensor and trigge...

Page 14: ...retained and the notebook can be connected to the hub using a stan dard network cable If the network is set up on the system module with single wires terminals 8 12 the LAN socket must not be used If...

Page 15: ...System Status block compare the serial number in the Serial Number line with the delivery docu mentation The serial number has 7 digits and starts with 95xxxxx e g 9515054 If the numbers are identical...

Page 16: ...connection to the CMS l Enter the valid IP address of the CMS in the browser A login dialog appears l Enter the login details l Access to the configuration pages is only possible for user level 3 high...

Page 17: ...the specific system during startup l Enter the following address in the browser http IP address of the CMS maintenance A login dialog appears l Enter the login details for user level 3 Access to the c...

Page 18: ...edited for PRUFTECHNIK sensors as the values are fixed in this regard If necessary set the process variables in the Process Signals section l Set the signal type in the Sensor column Voltage or curre...

Page 19: ...ization Display Input Storage Location Values The following list appears List of online readings The left column states the number of the input memory in which the respective readings are stored The f...

Page 20: ...ant status LED flashes orange on the system module Status LED on the terminal block To simulate a cable break in the measuring section proceed as follows l Disconnect the cable connector plug from the...

Page 21: ...calculated 2 5 MW 16mA 6 3mA 4mA 0 36 MW 0 20mA signal Final value signal value see previous example Process value calculated 2 5 MW 20mA 6 3mA 0 79 MW 0 10V signal Final value generator power 2 5 MW...

Page 22: ...uration has been set up properly CMS is ready for operation When integrating the system in an existing network the following requirements are to be discussed with the ope rator or administrator of the...

Page 23: ...e place Email account The emails are usually sent via or directly to an SMTP server that contains the recipient s mailbox l Click on Edit under account configuration to edit an existing account or cli...

Page 24: ...uration to edit an existing configuration or click on Add New to create a new configuration The input mask for the email configuration appears Email configuration type and subject Email ID Sequential...

Page 25: ...ent name The recipient name corresponds to the addressee of the email If this information is not known any meaningful identifier can be entered Email Address Email address of the recipient l To conclu...

Page 26: ...etails of this can be found in the previous section This section describes how to send a test email via the existing network infrastructure Typical network structure Prerequisites The CMS is connected...

Page 27: ...a test email Depending on the connection setup it may take a few moments until the email is sent A confirmation page provides the response from the SMTP server l Note the outcome in the setup log In t...

Page 28: ...Printed in Germany LIT 78 221 EN 10 2018 Fluke Deutschland GmbH Freisinger Str 34 85737 Ismaning Germany 49 89 99616 0 www pruftechnik com Productive Maintenance Technology...

Reviews: