l
Possible cause
: Network settings have been changed and have not been documented.
l
Remedy
:
l
Restart the system module with the
RESET
button.
l
Load the default network setting using the
IP PRESET
button.
The system module has two operating buttons: the IP PRESET button to load the default IP address and the RESET
button to restart the system.
Operating buttons on the VIBGUARD compact system module: RESET, IP PRESET
Restarting the system (RESET)
The RESET button can be reached via a small hole in the cover plate. You need a suitable object such as a screw-
driver with a 2.5 mm blade width to actuate the button.
Loading the default IP address (IP PRESET)
With regard to incorrect inputs, changes to the network settings can result in the system no longer being accessible.
In such cases, a standard network setting can be loaded in the system module via the IP PRESET button. This makes
communication possible again.
The IP PRESET button can be reached via a small hole in the cover plate. You need a suitable object such as a screw-
driver with a 2.5 mm blade width to actuate the button.
l
Restart the system module either by actuating the
RESET
button or by switching the mains supply on and
off.
l
The system module gradually starts up and the SYSTEM LED lights up orange as it is doing so.
l
While the system module is starting up, press and hold the
IP PRESET
button.
l
Release the
IP PRESET
button as soon as the SYSTEM LED lights up green. The system module is again reacha-
ble at the following network address:
IP address: 192.168.1.184
IP gateway: 192.168.1.13
IP subnet mask: 255.255.255.0
46