• Do not use the Product if it operates incorrectly.
• Do not touch voltages >30 V ac rms, 42 V ac peak, or 60 V dc.
• Use this Product indoors only.
• Examine the case before you use the Product. Look for cracks or missing
plastic. Carefully look at the insulation around the terminals.
• Do not apply more than the rated voltage, between the terminals or between
each terminal and earth ground.
• All appliances or equipment on the circuit being tested should be unplugged
to help avoid erroneous readings.
• Do not use this Product as a comprehensive diagnostic instrument. Use it as a
simple instrument to detect nearly all probable common improper wiring
conditions.
• Refer all indicated problems to a qualified electrician.
• Do not use the Product to indicate the quality of ground.
• Do not use the Product to detect 2 hot wires in circuit.
• Do not use the Product to detect a combination of defects.
• Do not use the Product to indicate reversal of grounded and grounding
conductors.
• Consult the GFCI manufacturer’s installation instructions to determine that
the GFCI is installed in accordance with the manufacturer’s specifications.
• Check for correct wiring of receptacle and all remotely connected receptacles
on the branch circuit.
• Operate the test button on the GFCI installed in the circuit. The GFCI must trip.
If it does not – do not use the circuit – consult an electrician. If the GFCI does
trip, reset the GFCI. Then, insert the Product into the receptacle to be tested.
• Push the GFCI button on the Product for a minimum of 6 seconds to test the
GFCI condition. An audible or visible indication on the Product must cease