i6000s English Instruction Sheet
Page 7
2. Wrap the flexible measuring head around the conductor
to be tested in a close coupling manner.
3. Energize the circuit under test.
4. For most accurate measurement, center the flexible
head around the conductor.
5. Locate coupling away from the nearby conductors.
Warning
To prevent electric shock or personal injury:
•
Do not use the flexible current Probes to
measure bare conductors unless wearing
protective clothing suitable for high voltage
work.
•
Always use appropriate equipment for personal
protection. When installed on bare
conductors/busbars, the product must be within
a suitable enclosure.
Ieb0002.eps
Operation
To turn on the unit, move the switch from ‘Off’ position to the
required measurement range. If the value of current being
measured is unknown, select the 6000 A current range and then
reduce accordingly.
Battery Status
Battery status is indicated by an LED on the front of the Probes.
This LED will flash one time when the unit is activated. The
length of time the LED is lit will increase as battery life
decreases. Momentary lighting of LED indicates batteries are
good. Continuous lighting of LED indicates low battery and