![Fluke 435-II Technical Data Manual Download Page 7](http://html1.mh-extra.com/html/fluke/435-ii/435-ii_technical-data-manual_2309631007.webp)
7 Fluke Corporation Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers
Environmental
Operating temperature
0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery
Storage temperature
-20 °C ~ +60 °C
Humidity
+10 °C ~ +30 °C: 95 % RH non-condensing
+30 °C ~ +40 °C: 75 % RH non-condensing
+40 °C ~ +50 °C: 45 % RH non-condensing
Maximum operating altitude
Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft)
Electro-Magnetic-Compatibility
(EMC)
EN 61326 (2005-12) for emission and immunity
Interfaces
mini-USB-B, Isolated USB port for PC connectivity
SD card slot accessible behind instrument battery
Warranty
Three years (parts and labor) on main instrument, one year on accessories
Included accessories
Power options
BC430 Power Adapter
International plug adapter set
BP290 (Single capacity Li-ion battery) 28Wh (7 hours or more)
Leads
TL430 Test lead and Alligator clip set
Color coding
WC100 color coding clips and regional decals
Flexible current probes
i430flex-TF, 24 inch (61cm) length, 4 clamps
Memory, Software and
PC connection
8 GB SD card
PowerLog on CD (includes operator manuals in PDF format)
USB cable A-Bmini
Carrying case
C1740 Soft Case for 434-II and 435-II
C437 Hard Case with rollers for 437-II
* ± 5 % if ≥ 1 % of nominal voltage ± 0.05 % of nominal voltage if < 1% of nominal voltage
** 50Hz/60Hz nominal frequency according to IEC 61000-4-30
*** 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode.
**** for nominal voltage 50 V to 500 V
Wiring configurations
1Ø + NEUTRAL
Single phase with neutral
1Ø SPLIT PHASE
Split phase
1Ø IT NO NEUTRAL
Single phase system with two phase voltages without neutral
3Ø WYE
Three phase four wire system WYE
3Ø DELTA
Three phase three wire system Delta
3Ø IT
Three phase system without neutral WYE
3Ø HIGH LEG
Four wire three phase Delta system with center tapped high leg
3Ø OPEN LEG
Open delta three wire system with 2 transformer windings
2-ELEMENT
Three phase three wire system without current sensor on phase L2/B (2 watt meter method)
2½-ELEMENT
Three phase four wire system without voltage sensor on phase L2/B
INVERTER EFFICIENCY
dc voltage and current input with ac output power (automatically displayed and selected in Inverter Efficiency mode)
General specifications
Case
Design Rugged, shock proof with integrated protective holster
Drip and dust proof IP51 according to IEC60529 when used in tilt stand position
Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g
2
/Hz according to MIL-PRF-28800F Class 2
Display
Brightness: 200 cd/m
2
typ. using power adapter, 90 cd/m
2
typical using battery power
Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD
Resolution: 320 x 240 pixels
Contrast and brightness: user-adjustable, temperature compensated
Memory
8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally
Screen save and multiple data memories for storing data including recordings (dependent on memory size)
Real-time clock
Time and date stamp for Trend mode, Transient display, System Monitor and event capture
Shop for Fluke products online at:
1.877.766.5412
www.
MyFlukeStore
.com