Fluke 435-II Technical Data Manual Download Page 7

7  Fluke Corporation     Fluke 430 Series II Three-Phase Energy and Power Quality Analyzers

Environmental

Operating temperature 

0 °C ~ +40 °C; +40 °C ~ +50 °C excl. battery

Storage temperature 

-20 °C ~ +60 °C

Humidity 

+10 °C ~ +30 °C: 95 % RH non-condensing
+30 °C ~ +40 °C: 75 % RH non-condensing
+40 °C ~ +50 °C: 45 % RH non-condensing

Maximum operating altitude 

Up to 2,000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V
Up to 3,000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V
Maximum storage altitude 12 km (40,000 ft)

Electro-Magnetic-Compatibility 

(EMC) 

EN 61326 (2005-12) for emission and immunity

Interfaces

mini-USB-B, Isolated USB port for PC connectivity

SD card slot accessible behind instrument battery

Warranty 

Three years (parts and labor) on main instrument, one year on accessories

Included accessories

Power options

BC430 Power Adapter 

International plug adapter set

BP290 (Single capacity Li-ion battery) 28Wh (7 hours or more)

Leads

TL430 Test lead and Alligator clip set

Color coding

WC100 color coding clips and regional decals

Flexible current probes

i430flex-TF, 24 inch (61cm) length, 4 clamps

Memory, Software and  

PC connection

8 GB SD card

PowerLog on CD (includes operator manuals in PDF format)

USB cable A-Bmini

Carrying case

C1740 Soft Case for 434-II and 435-II

C437 Hard Case with rollers for 437-II

  * ± 5 % if ≥ 1 % of nominal voltage ± 0.05 % of nominal voltage if < 1% of nominal voltage 

  ** 50Hz/60Hz nominal frequency according to IEC 61000-4-30

 *** 400Hz measurements are not supported for Flicker, Mains Signaling and Monitor Mode.

**** for nominal voltage 50 V to 500 V

Wiring configurations

1Ø + NEUTRAL

Single phase with neutral

1Ø SPLIT PHASE 

Split phase

1Ø IT NO NEUTRAL 

Single phase system with two phase voltages without neutral

3Ø WYE

Three phase four wire system WYE

3Ø DELTA 

Three phase three wire system Delta

3Ø IT 

Three phase system without neutral WYE

3Ø HIGH LEG 

Four wire three phase Delta system with center tapped high leg

3Ø OPEN LEG 

Open delta three wire system with 2 transformer windings

2-ELEMENT 

Three phase three wire system without current sensor on phase L2/B (2 watt meter method)

2½-ELEMENT 

Three phase four wire system without voltage sensor on phase L2/B

INVERTER EFFICIENCY

dc voltage and current input with ac output power (automatically displayed and selected in Inverter Efficiency mode)

General specifications

Case

Design Rugged, shock proof with integrated protective holster

Drip and dust proof IP51 according to IEC60529 when used in tilt stand position

Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g

2

/Hz according to MIL-PRF-28800F Class 2

Display

Brightness: 200 cd/m

2

 typ. using power adapter, 90 cd/m

2

 typical using battery power

Size: 127 mm x 88 mm (153 mm/6.0 in diagonal) LCD

Resolution: 320 x 240 pixels

Contrast and brightness: user-adjustable, temperature compensated

Memory

8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32GB optionally

Screen save and multiple data memories for storing data including recordings (dependent on memory size)

Real-time clock 

Time and date stamp for Trend mode, Transient display, System Monitor and event capture

Shop for Fluke products online at:

1.877.766.5412

www.

MyFlukeStore

.com

Summary of Contents for 435-II

Page 1: ...models capture 100 120 cycles 50 60Hz of each event that is detected in all modes without set up Automatic Transient Mode 435 and 437 Series II analyzers capture 200 kHz waveform data on all phases s...

Page 2: ...fect of unevenly loading each phase in three phase systems Unbalance can often be corrected by reconnect ing loads on different phases to ensure the current drawn on each phase is as equal as possible...

Page 3: ...luded i430flex TF with sensitivity 10x 5 Arms to 6000 Arms with included i430flex TF with sensitivity 1x 0 1 mV A to 1 V A and custom for use with optional ac or dc clamps Input impedance 1 M Bandwidt...

Page 4: ...z Transients 435 II and 437 II only Transient waveforms 4x Voltage 4x Amps triggers Vrms Arms Pinst Mains Signaling 435 II and 437 II only Relative signaling voltage and absolute signaling voltage ave...

Page 5: ...mV A 1x 5 A to 2000 A 1A 0 5 5 counts 1mV A 10x 0 5 A A to 200 A ac only 0 1 A 0 5 5 counts Hz Hz Fluke 434 50 Hz nominal 42 50 Hz to 57 50 Hz 0 01 Hz 0 01 Hz Fluke 434 60 Hz nominal 51 00 Hz to 69 00...

Page 6: ...alue over 10 12 cycle period var Fundamental reactive power display Calculates reactive power on fundamental positive sequence components Capacitive and inductive load is indicated with capacitor and...

Page 7: ...g and Monitor Mode for nominal voltage 50 V to 500 V Wiring configurations 1 NEUTRAL Single phase with neutral 1 SPLIT PHASE Split phase 1 IT NO NEUTRAL Single phase system with two phase voltages wit...

Page 8: ...subject to change without notice Printed in U S A 8 2011 2643006D D EN Pub ID 11858 eng Modification of this document is not permitted without written permission from Fluke Corporation Flexible Curre...