2 Fluke Corporation Solar Tools Kit with 393 FC Clamp Meter, Irradiance Meter and Solar Test Leads
https://www.fluke.com/en-us/product/electrical-testing/clamp-meters/solar-tools-393-irrsol
DC power measurement, showing readings in kVA
Logging and reporting of test results via Fluke Connect software
Make instantaneous measurements to determine the watts per square meter solar irradiation, required by IEC 62446-1
standard
MC4 leads comply to IEC / EN 61010-031
Specifications: Solar Tools Kit with 393 FC Clamp Meter, Irradiance
Meter and Solar Test Leads
Specifications: Fluke 393 FC CAT III 1500 V True-rms Solar Clamp Meter
General
Maximum voltage between any Terminal and Earth Ground
AC
1000 V
DC
1500 V
Batteries
2 AA IEC LR6 alkaline
Display
Dual display with backlight
Automatic Power Off
20 minutes
Electrical
Accuracy
Accuracy is specified for 1 year after calibration, at operating temperatures of 18 °C to 28 °C, relative humidity at 0 % to 75 %. Accuracy specifications take the form
of: ±([% of Reading] + [Number of Least Significant Digits]).
Temperature Coefficients
Add 0.1 x specified accuracy for each °C > 28 °C or < 18 °C
AC Current: Jaw
Range
999.9 A
Resolution
0.1 A
Accuracy
2 % + 5 digits (10 Hz to 100 Hz)
2.5 % + 5 digits (100 Hz to 500 Hz)
Crest Factor (50/60 Hz)
2.5 @600.0 A
3.0 @500.0 A
1.42 @999.9 A
Add 2 % for C.F. >2
AC Current: Flexible Current Probe
Range
999.9 A
2500 A
Resolution
0.1 A (≤999.9 A)
1 A (≤2500 A)
Accuracy
3 % RD + 5 digits (10 Hz to 500 Hz)
Crest Factor (50/60Hz)
2.5 @1400 A
3.0 @1100 A
1.42@2500 A
Add 2 % for C.F. >2
Position Sensitivity