![Fluke 1623 User Manual Download Page 27](http://html1.mh-extra.com/html/fluke/1623/1623_user-manual_2310313027.webp)
Earth/Ground Tester
Specifications
19
Probe resistance (Rs):
max. 100 k
Ω
Auxiliary earth electrode resistance
(Rh):
max. 100 k
Ω
Monitoring of Rs, and Rh with error indicator.
Measurement is not performed if the current through the current clamp is too
low.
Automatic range selection.
R
A
4- pole selective ground resistance measurement with current clamp
(R
A
A
)
Switch
position
Resolution Measuring range Intrinsic error
Operating error
Ra 4-pole
A
0.001 ...
10
Ω
0.001
Ω
..
19.99 k
Ω
±
(7% rdg + 3 d)
±
(10% rdg + 5 d)
Measuring principle: Current/voltage measurement (with external current
clamp)
Measuring voltage:
Um = 48 VAC.
Short-circuit current:
> 50 mA
Measuring frequency:
128 Hz (125 Hz on request)
Probe resistance (Rs):
max. 100 k
Ω
Auxiliary earth electrode resistance
(Rh):
max. 100 k
Ω
Monitoring of Rs, and Rh with error indicator.
Measurement is not performed if the current through the current clamp is too low.
Automatic range selection.