A
3-pole Selective Earth Resistance Measurement with
Current Clamp
The R
A
3-pole Selective Earth Resistance Measurement with Current Clamp
procedure is useful for measuring the resistance of different parallel sections of
an earth/ground system. Refer to Figure 6.
A
Select function R
A
3-pole
A
.
Display as shown below.
B
Connect test leads.
Connect the supplied test lead (1.5 m) to terminal E/C1 and its other
end to the ground system to be measured. Place 2 ground stakes in
earth/dirt. Minimum distance between earth electrode (E/C1), probe
(S/P2) and auxiliary earth (H/C2) should be at least 20 m!
Connect stakes with 25 m and 50 m wires to H/C2 and S/P2 as
shown. Connect current clamp with adapter cable as shown.
C
Press
START.
The “active” symbol indicates that measurement is in progress. For
continuous measurement keep START pressed.
D
Symbol
“
9
” indicates completed measurement. The result is kept on
display until a new measurement is started or the rotary switch is
turned.
S
E
H
e
v
i
t
c
a
E
H
S
s
u
l
p
V
0
5
x
a
m
2
P
S
E
H
S
FLUKE
1
2
3
4
edv005.eps
Figure 6. R
A
3-pole Selective Earth Resistance Measurement with Current
Clamp
Shop for Fluke products online at:
1.877.766.5412
www.
MyFlukeStore
.com
Summary of Contents for 1623
Page 4: ...1623 Users Manual ii Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Page 6: ...Users Manual iv Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Page 8: ...Users Manual vi Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...