Fluke Calibration 5322A-LOAD Instructions Manual Download Page 4

5322A-LOAD 

Instructions

 

Use the Load for Leakage Current 
Tests 

Select the load resistor based on the appropriate 
voltage amplitude for the test or the value 
recommended in the hipot tester’s calibration 
procedure. A load resistor is connected to the Output 
terminals when a resistor's red and black terminals 
are shorted together using a high-voltage shrouded 
banana jumper lead. 
See 

Paralleling Resistors

 for making additional 

resistance values. See the 

5322A Operators Manual

 

for more detailed application information. 

W

 Caution 

To avoid damage, never exceed the 
maximum rated voltage, power, and 
current limit of the Product. 

Usage Limits for Safe Operation for Each 
Load Resistor 

Safe operation of the Product depends on the amount 
of voltage and the length of time it is applied to the 
Product. For the 10 k

Ω

, 35 k

Ω

, 50 k

Ω

, 100 k

Ω

, and 

250 k

Ω

 resistors, there are time limits where the 

higher-voltage levels can be safely applied. This is 
graphically shown in Figure 4 for the 10k, 25k, 50k, 
100k, and 250k resistors.The maximum voltages can 
be applied for up to 3 minutes for these resistors. Due 
to self heating, exceeding the 3-minute limit for high 
voltages can cause both degradation of performance 
and a permanent shift in the resistor value. However, 
reduced-voltage levels can be safely applied for 
increasing longer times. At specific levels, sustained 
voltages can be applied indefinitely. The other 
resistors (500k, 1M, 5M and 10M) do not have a time 
limit for the maximum voltage (5500V). See Figure 4. 

Safe Area

0

1000

2000

3000

4000

5000

6000

1

10

100

Time (min)

V

o

lt

ag

e (

V

)

250 k

100 k

35k/50k

10k

                                                                                

ehq101.eps

 

Figure 4. Safe Area Chart 

Example 

The 100 k

Ω

 resistor can withstand 5500 V for 

3 minutes while it can withstand 4000 V for 
60 minutes or longer.  

Paralleling Resistors 

The Product can output additional values by placing 
combinations of the nine resistors in parallel as shown  
in Table 2. 
To place resistors in parallel, short together 
combinations of the given resistors’ red and black 
terminals using the supplied high-voltage shrouded 
banana jumper leads. For example, to parallel the 
10 k

Ω

 and 25 k

Ω

 resistors, short the 10 k

Ω

 red and 

black terminals, and the 25 k

Ω

 red and black 

terminals. This places these two resistors in parallel at 
the Product Output terminals. The resultant output is 
7.14 k

Ω

, for a 70 mA leakage current at 500 V, as 

shown in Table 2.  
In Figure 5, the 10k Ohm, 25k Ohm, and 50k Ohm 
resistors are in parallel, giving an output of 6.25 k

Ω

HiPot 
Tester

 

Ieu003.eps 

Figure 5. Leakage Current Test Connection 

The maximum applicable working voltage for parallel 
combinations is the maximum voltage of the resistor 
with the lowest voltage rating. 

W

Caution 

Do not exceed the specified 
voltage limits of any given 
resistor. 

Summary of Contents for 5322A-LOAD

Page 1: ...this use the supplied high voltage jumper leads to short the resistor s red terminal to the resistor s corresponding black terminal The Product withstands a maximum voltage of 1 2 kV to 5 5 kV depend...

Page 2: ...gure 2 comes with a power line adapter to run the cooling fans a ground cable three shorting cables and these instructions The power line adapter comes with five mains plug adapters that are compatibl...

Page 3: ...nel switch to the I side of the switch to turn on the cooling fans A light on the front panel illuminates and indicates that power is on Turn off the power switch when the Product is no longer being u...

Page 4: ...ge levels can be safely applied for increasing longer times At specific levels sustained voltages can be applied indefinitely The other resistors 500k 1M 5M and 10M do not have a time limit for the ma...

Page 5: ...tors Versus Voltage Versus Current Current mA 500 V 1000 V 2000 V 5000 V 0 05 10M 0 1 5M 10M 0 2 5M 10M 0 3 5M 10M 0 4 5M 0 5 1M 10M 0 6 1M 5M 5M 10M 1 500k 1M 5M 1 5 500k 1M 5M 10M 2 250k 500k 1M 2 5...

Page 6: ...test voltage across each resistance between the respective input and COM terminals The resulting current through the resistor is measured and the value of the resistance is calculated Use a calibrato...

Page 7: ...0 20100 mA DCV ACV DCI ACI TRIG FREQ PERIOD TEMP ZERO INSTR SETUP MEAS SETUP RANGE F1 F2 F3 F4 F5 BACK MEMORY ANALYZE INPUT SENSE HI LO FRONT REAR 10A 1V 400 mA 4W HI LO 2W 4W V 300V FUSED 1000V CAT I...

Page 8: ...050 m 10 000 ft Storage 12 200 m 40 000 ft Dimensions 430 mm X 462 mm X 95 mm 16 9 in X 18 2 in X 3 7 in Weight net 3 kg 8 lb 4 5 oz Power Consumption 5 W maximum Safety class I according to EN 61010...

Reviews: