HF131PEN_v0501_05
Page 37
Explanation Intrinsically Safe options:
Option AF - Intrinsically Safe floating 4-20mA analog output:
A floating 4-20mA signal proportional to the flowrate is available with this option.
When the output is disabled, a 3.5mA signal will be generated.
Max. driving capacity 1000 Ohm @ 30V DC.
Option PD - Intrinsically Safe power supply and sensor supply - Terminal GND- 01 and 11.
O
PTION
SENSOR SUPPLY
T
erminal
GND
01
02
PD
Input voltage:
8-30V DC
3,2 - 8,1V
L-
L+
output voltage is according
the input voltage; internally
linked with terminal 01.
Terminal 02: this terminal offers the same voltage as connected to terminal 01.
Terminal 11: this terminal offers a 3.2V or 8.1V to power the sensor.
This voltage is selected with the switch(es) inside the enclosure. First, remove the terminals after
which the internal plastic cover can be removed.
Switch position
Switch position
terminal 11
no function
SWITCH
1
VOLTAGE
SWITCH
2
on
8.1 V DC
not available
off
3.2 V DC
Fig. 14: Switch position voltage selection option PD-XI.