Terminal 03-05; Flowmeter input

:

 

Three basic types of flowmeter signals can be connected to the unit: pulse, active pulse or coil. The 
screen of the signal wire must be connected to the common ground terminal 03 (unless earthed at 
the sensor itself). The maximum input frequency is approximately 10 kHz (depending on the type of 
signal). The input signal type has to be selected with the correct SETUP-function (read par. 3.2.3.) 
  

Coil-signal

:

 

The F113-P-OS is suitable for use with flowmeters which have a coil output signal. Two sensitivity 
levels can be selected with the SETUP-function:  

COIL LO: sensitivity from about 120mVp-p. 
COIL HI: sensitivity from about 20mVp-p. 

Type ZF offers for setting COIL HI : sensitivity from about 10mVp-p. 
Type ZG offers for setting COIL HI : sensitivity from about 5mVp-p.

 

 
Pulse-signal NPN / NPN-LP: 

The F113-P-OS is suitable for use with flowmeters which have a NPN output signal. For reliable 
pulse detection, the pulse amplitude has to go below 1.2V. Signal setting NPN-LP employs a low-
pass signal noise filter, which limits the maximum input frequency - read par. 3.2.3.  
 

 

Pulse-signal PNP / PNP-LP: 

The F113-P-OS is suitable for use with flowmeters which have a PNP output signal. 3.2V is offered 
on terminal 5 which has to be switched by the sensor to terminal 4 (SIGNAL). For a reliable pulse 
detection, the pulse amplitude has to go above 1.2V. Signal setting PNP-LP employs a low-pass 
signal noise filter, which limits the maximum input frequency - read par. 3.2.3. 
A sensor supply voltage of 8.2, 12 or 24V DC can be provided as well (see sensor supply). 

INTERNAL

EXTERNAL

Coil signal input

5

4

COIL

Common ground unit

COIL

3

GND

Input

sensitivity

selectable:

coil high / low

+

V ref.

1.2V DC

shielding

INTERNAL

EXTERNAL

NPN signal input

4

Common ground unit

SIGNAL

3

GND

shielding

NPN

+ 3.2V DC

100K

low-pass filter

selection NPN-LP

Summary of Contents for F113-P-PD-OS

Page 1: ...TOR TOTALIZER with high low alarms analog and pulse outputs ADDENDUM INSTALLATION GUIDE FOR TYPE PD OS 4 MECHANICAL RELAY OUTPUTS F Series Field mounted indicators for safe and hazardous areas More info www fluidwell com fseries ...

Page 2: ...ife equipment shall be disposed of according to the local regulations regarding waste of the electrical and the electronic equipment Please contact your local dealer national distributor or the manufacturer s Technical helpdesk for information on the product disposal SAFETY RULES AND PRECAUTIONARY MEASURES The manufacturer accepts no responsibility whatsoever if the following safety rules and prec...

Page 3: ...safety hazard or damage of the F113 P or connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the F113 P or connected instruments A note indicates actions or procedures which if not performed correctly may indirectly affect operation or may lead to an instrument response which is not planned WARRANT...

Page 4: ...ures 2 About the manual 3 Warranty and technical support 3 Contents manual 3 4 Installation 5 4 1 General directions 5 4 2 Installation surrounding conditions 5 4 3 Dimensions Enclosure 6 4 4 Installing the hardware 8 4 4 1 General installation guidelines 8 4 4 2 Protective Earth PE connections 9 4 4 3 Sensor supply 10 4 4 4 Terminal connectors 10 ...

Page 5: ...cautionary measures at the front of this manual 4 2 INSTALLATION SURROUNDING CONDITIONS Take the relevant IP classification of the enclosure into account see identification plate Even an enclosure rated for IP67 TYPE 4 X should NEVER be exposed to strongly varying weather conditions When used in very cold surroundings or varying climatic conditions inside the instrument case take the necessary pre...

Page 6: ...15 mm 0 6 deeper rear cover 75 mm 2 95 130 mm 5 12 112 mm 4 40 120mm 4 72 M20 x 1 5 PG9 PG9 30mm 30mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm M20 x 1 5 M20 x 1 5 M20 x 1 5 25mm 25mm 1 2 NPT 0 9 3x 1 2 NPT 0 12 0 12 HA HM HN HO HP HT HU 6 x M12 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 115 mm 4 53 HB 29 1 mm 1 15 31 mm 1 22 HZ 4x M20 x 1 5 15 15 HV 23 23 16 mm 1 2 NPT 1 2 NPT 25mm 25mm 22 5mm HL 22 5...

Page 7: ...0 mm 2 36 120 mm 4 72 HD HK HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm 2 95 118 mm 4 65 104 mm 4 09 HJ 0 9 0 12 0 12 3x D 22mm 0 866 115 mm 4 53 98 mm 3 86 29 1 mm 1 15 31 mm 1 22 ...

Page 8: ... applications the terminal 00 shall not be connected to avoid earth loops For V DC applications the terminal 00 shall be connected to the common do NOT use for PE The wire screens shield are meant to prevent electromagnetic interference and shall be galvanic isolated connected to the common ground terminals that belong to the specific sensor connection The wire screens shall be terminated at one s...

Page 9: ...h national and local electrical codes To ground the field mounted unit the PE conductor must be connected to the PE stud which is located in the metal back cover as indicated in the image below To connect the conductor a screw M4 x 6mm with a serrated washer a terminal and a washer is used torque 2 Nm The metal front cover is connected to the Protective Earth by the mounting screws with serrated w...

Page 10: ...switch 1 voltage selection sensor internal 3 2V or external switch 3 4 Function switch 3 4 the combination of these switches determine the voltage as indicated 4 4 4 TERMINAL CONNECTORS The following paragraphs describe the terminal connections and configurations that are specific for type PD OS 4 mechanical relay outputs For all other types of supply PM PF PD PX in combination with types OA OT an...

Page 11: ...lse signal NPN NPN LP The F113 P OS is suitable for use with flowmeters which have a NPN output signal For reliable pulse detection the pulse amplitude has to go below 1 2V Signal setting NPN LP employs a low pass signal noise filter which limits the maximum input frequency read par 3 2 3 Pulse signal PNP PNP LP The F113 P OS is suitable for use with flowmeters which have a PNP output signal 3 2V ...

Page 12: ... reed switch it is advised to select REED LP low pass filter read par 3 2 3 NAMUR signal The F113 P OS is suitable for flowmeters with an Namur signal The standard F113 P OS is can offer a 8 2V at terminal 5 INTERNAL EXTERNAL PNP signal input 4 Common ground unit SIGNAL 3 GND shielding PNP 100K 5 3 2V DC option 8 1V 12V 24V low pass filter selection PNP LP INTERNAL EXTERNAL Active signal input 4 C...

Page 13: ...utput passive A passive 4 20mA signal proportional to the flowrate is available as standard When a power supply is connected but the output is disabled a 3 5mA signal will be generated Max driving capacity 1000 Ohm This output does loop power the unit as well but is NOT able to power the mechanical relays Terminal 10 11 relay output R3 This output is an alarm or pulse output according setup 83 Ter...

Page 14: ...ion option When using the RS232 communication option terminal 27 is used for supplying the interface Please connect the DTR or the RTS signal of the interface to this terminal and set it active 12V If no active signal is available it is possible to connect a separate supply between terminals 26 and 27 with a voltage between 8V and 24V INTERNAL EXTERNAL Mechanic relay output R1 R2 R3 R4 10 11 R3 R3...

Page 15: ...FW_F113POS_v1901_02_EN addendum docx Page 15 ...

Page 16: ... Fluidwell B V PO box 6 Voltaweg 23 Website www fluidwell com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative www fluidwell com representatives The Netherlands The Netherlands 2017 Fluidwell B V FW_F113POS_v1901_02_EN addendum docx ...

Reviews: