Page 16
FW-F053-A-M_v0404_01_EN.docx
5.5
TUNE MAX / 20mA
With this setting it is possible to calibrate the input value for 20mA as
the signal from the sensor might not be exact 20.0mA at maximum
pressure ( span). This function will measure the real output
value at maximum pressure.
Be very sure that the offered signal is correct before calibration is
executed, as this has major influence on the accuracy of the system
After pressing PROG, three settings can be selected:
▪
CALIBRATE: with this setting, the input will be calibrated with the
actual "20mA" value. After pressing enter, CAL SET will be
displayed as soon as the calibration is completed. From that
moment, the analog value must be less than the calibrated value
for reliable measurements.
▪
DEFAULT: with this setting, the factory value is re-installed.
▪
CAL SET: to select the last calibrated value.
3.3.7
EXPLANATION OF SETUP-MENU 6 - OTHERS
SETUP
FUNCTIONS
AND
VARIABLES
6
OTHERS
6.1
TYPE / MODEL
For support and maintenance it is important to have information about
the characteristics of the F053-A.
Your supplier will ask for this information in the case of a serious
breakdown or to assess the suitability of your model for upgrade
considerations.
6.2
SOFTWARE VERSION
6.3
SERIAL NO.
6.4
PASS CODE
All SETUP-values can be pass code protected.
This protection is disabled with value 0000 (zero).
Up to and including 4 digits can be programmed, for example 1234.
6.5
TAGNUMBER
For identification of the F053-A and communication purposes, a
unique tag number of maximum 7 digits can be entered.