Page 31
FW-F018-P-M_v0404_01_EN.docx
Pulse-signal PNP / PNP-LP
The F018-P is suitable for use with flowmeters which have a PNP output signal. Terminal 3 offers
3.2V which has to be switched by the sensor to terminal 2 (SIGNAL). For a reliable pulse detection,
the pulse amplitude has to go above 1.2V. Signal setting PNP-LP employs a low-pass signal noise
filter, which limits the maximum input frequency (read chapter 3.3.2).
A sensor supply voltage of 8.1V DC can be provided with option PD on terminal 6.
Fig. 17: Terminal connections - PNP signal input.
Active signal
Active signal selection may well be desired in the case of option PD being supplied for sensor
supply.
Fig. 18: Terminal connections - Active signal input.
Reed-switch
The F018-P is suitable for use with flowmeters which have a reed-switch. To avoid pulse bounce
from the reed-switch, it is advised to select REED LP - low-pass filter (read chapter 3.3.2).
Fig. 19: Terminal connections - Reed-switch signal input.