StarPac Intelligent Control System FCD VLENIM0066-02 02/10
28
®
release the locking sleeve of the Lemo™ connector by moving the collar away
from the sensor and disconnect the connector from the sensor. Swing the sen-
sor conduit out of the way (refer to Figure 10).
Figure 10: Disconnecting Lemo
TM
Connector
4.
Unscrew the sensor from the sensor boss.
5
. Remove the sensor O-ring or gasket and replace with a new one. Make sure
the environmental O-ring seal is in good condition and in place on the new
sensor.
6.
Install the new sensor into the sensor port making sure the O-ring or gasket
remains properly in place while tightening the sensor. Tighten the sensor until
it seats metal-to-metal at the gasket section of the sensor port, ensuring the
proper compression of the process O-ring or gasket seal.
7.
Plug the pressure sensor cable connector into the pressure sensor. Align the
red dots on the sensor and connector to reconnect the Lemo™ connector to
the pressure sensor. Fully seat the connector until the locking sleeve latches.
Replace the sensor nut and tighten.
8
. Pressurize the valve body to make sure the sensors are properly seated before
attaching the sensor conduit and tightening.
9.
Reattach the conduit lines and securely tighten the fittings.