User Instructions - Logix® 520MD+ Series Digital Positioner
FCD LGENIM0105-00
© Flowserve Corporation
14
Field Trial Version – Printed October 28, 2011
6 TUBING
After mounting has been completed, tube the positioner to
the actuator using the appropriate compression fitting
connectors.
6.1
Determine Air Action
The port labeled “Y1” delivers air when an air supply is
present and the relay is energized. (For positioners with
double acting relays, this is port A. For positioners with
single acting relays, this is port B.) Typically, the port labeled
“Y1” should be tubed to the pneumatic side of the actuator
(the side that would result in the air compressing the actuator
spring). When tubed this way, the spring is designed to
return the valve to the fail safe state should supply air or
power to the unit fail.
Tube the port labeled “Y1” to the side of the actuator that
must receive air to begin moving away from the fail safe
state.
If air from “Y1” should open the valve, set the Air Action
configuration switch on the positioner to Air-to-Open,
otherwise set it to Air-to-Close.
The Air-to-Open and Air-to-Close selection is determined by
the actuator tubing, not the software. When air action
selection is made during configuration, the selection tells the
control which way the actuator has been tubed.
If the valve is double acting, port the valve labeled “Y2” to the
other side of the actuator.
DANGER: Proper tubing orientation is critical for the
positioner to function correctly and have the proper failure
mode.
Example: Linear Double-Acting Actuators
For a linear air-to-open actuator, the “Y1” port of the
positioner is tubed to the bottom side of the actuator (closest
to the valve). The “Y2” port of the positioner is tubed to the
top side of the actuator. For a linear air-to-close actuator the
above configuration is reversed.
Example: Rotary Double-acting Actuators
For a rotary actuator, the “Y1” port of the positioner manifold
is tubed to the bottom side of the actuator. The “Y2” port of
the positioner manifold is tubed to the top side of the
actuator. This tubing convention is followed regardless of air
action. On rotary actuators, the transfer case orientation
determines the air action.
Example: Single-acting Actuators
For single-acting actuators, the “Y1” port is always tubed to
the pneumatic side of the actuator regardless of air action. If
a double acting - spool style relay is installed in the
positioner, plug port B (Y2). If a single acting - poppet style
relay is installed, port A can be plugged or may be used for
purging. See Purging Single Acting Actuators below.
6.2
Connect Supply Port
The positioner ports are threaded with either G ¼ or ¼
NPTF as indicated on the housing.
In order to maintain the recommended air quality, a
coalescing filter should always be installed in the supply gas
line. An air filter is highly recommended for all applications
where dirty air is a possibility. The positioner passage ways
are equipped with small filters, which remove medium and
coarse size dirt from the pressurized air. If necessary, they
are easily accessible for cleaning.
A supply regulator is recommended if the customer will be
using the diagnostic features of the Logix 520MD+ but is not
required. In applications where the supply pressure is higher
than the maximum actuator pressure rating a supply
regulator is required to lower the pressure to the actuator’s
maximum rating.
6.3
Purging Single Acting Actuators
Purging allows the non-pressurized side of a single acting
actuator to fill with exhaust gas instead of atmospheric air.
This configuration helps prevent corrosion of actuator
components in harsh environments. When a single acting
relay is used, a special procedure can be performed to
configure the positioner to purge properly using port A.
Contact your local Field Service Technician for more
information regarding the purging option.
6.4
Vented Design
A standard Logix 520MD+ positioner is vented directly to the
atmosphere. When supply air is substituted with sweet
natural gas, piping must be used to route the exhausted
natural gas to a safe environment.
The housing chamber exhaust port is located on the
backside of the positioner. The actuator exhaust port is
located on the bottom of the positioner. Both ports are
tapped with either ¼ NPTF or G ¼ threads and covered with
a protective cap. To control vented gas, remove the caps
and connect the necessary tubing/piping to these ports. See
Figure 5: Exhaust Vents.
Figure 5: Exhaust Vents
This piping system may cause some positioner back
pressure. Back pressure in the housing chamber is from the
modulator and regulator. Back pressure in the exhaust port
is from the actuator.
The maximum allowable back pressure from the housing
chamber is 0.14 barg (2.0 PSIG). For flow rates, see section
3.2 Air Supply.
The maximum allowable back pressure from the exhaust port
is 0.55 barg (8.0 PSIG) for double acting relays and is 0.14
barg (2.0 PSIG) for single acting relays. Higher pressure
may result in decreased performance. For output flow rates,
see section 3.3 Pneumatic Output.
WARNING: The back pressure in the main housing must
never rise above 0.14 barg (2.0 PSIG). This could cause the
positioner
to
become
unresponsive
under
some
circumstances.
Housing
Chamber
Exhaust
(0.14 barg Max)
Actuator
Exhaust
(0.55 barg Max)
Summary of Contents for Logix 520MD+
Page 53: ......