FlowLine LI1 Series Instruction Manual Download Page 5

Model LI1X Universal Process Meter

Instruction Manual

RESET

User Select:
1. Automatically when input passes reset point.
2. Automat Manually (via user supplied 

switch or front panel ACK button). Manual 
reset resets all manually resetable relays. 

DEADBAND

0-100% of full scale, user selectable.

HIGH OR LOW 

User may program any alarm for a high or low

ALARM

trip point.

FAIL-SAFE 

Relay coils are energized in non-alarm 

OPERATION

condition. In case of power failure, relays will 
go to alarm state. Fail-safe operation may be 
disabled, by removing jumper J2 located on the
Options PCB.

AUTO 

When power is applied to the meter, relays will

INITIALIZATION

always reflect the state of the input to the meter.

Isolated 4-20 mA Transmitter Output

CALIBRATION

The transmitter output can be calibrated so that

RANGE

a 4 mA output is produced for any number 
displayed by the meter. The 20 mA output may 
correspond to any number that is at least 501 
counts greater or smaller than the number 
corresponding to 4 mA. (Ex. 4 mA = 0, 20 mA = 
501) If the span between 4 and 20 mA is less 
than 501 counts, an error message will appear.

EQUIPMENT

The 4-20 mA output is calibrated without

NEEDED

the use of a calibrator. No equipment needed.

OUTPUT

(AC Meters only), Isolated 24 VDC ± 5% @ 20

LOOP-POWER

mA regulated. Maximum loop resistance is 
1200 ohms. Available for either signal input or
4-20 mA output, but not both.

ACCURACY

± 0.1% F.S., ± 0.004 mA.

ISOLATION

500 VDC or peak AC, input-to-output or
input/output-to-power line.

EXTERNAL LOOP-

35 VDC  max.

POWER SUPPLY
OUTPUT LOOP 

Power supply

Min. loop 

Max loop

RESISTANCE

resistance

resistance

24 VDC

10 ohms

600 ohms

35 VDC (external) 600 ohms

1000 ohms

8

Model LI1X Universal Process Meter

Instruction Manual

9

Display Messages and Functions 

The following table describes the various messages displayed by the
meter during programming and operation:

Display

Parameter

Description/Comments

E-

C

AL

Select External 

Set meter for calibration using 

Calibration

an external calibration source.

I-

C

AL

Select Internal 

Set meter for calibration (scaling)

Calibration

using Internal calibration source.

C

ALIb

Perform External 

Calibrate meter using an external 

Calibration

calibration source.

S

C

ALE

Perform Internal 

Calibrate meter (scale) using 

Calibration

internal calibration  source. 

(scaling)

(Signal source not required).

InPt 1

Input 1

Set Input 1 calibration value.

Dspy 1

Display 1

Set Display 1 calibration value.

Inpt 2

Input 2

Set Input 2 calibration value.

Dspy 2

Display 2

Set Display 2 calibration value.

DE

C

Pt

Decimal Point

Set decimal point or light up 
extra "0".

No. PtS

Number of Points

Set meter for 2 to 11 
calibration points.

L or S

Linear or Square

Set meter for Linear or Square Root
calibration/scaling.

C

vtoFF

Low-flow Cutoff

Set meter to display zero below 
programmed cutoff point.

Alars

Alarms

Program alarm/relay set and 
reset points.

OvtPvt

Output

Set  4-20 mA output values.

19999

Overrange

Indicates input signal exceeds 
full-scale range of meter.

-19999

Underrange

Indicates input signal is below the 
negative range of meter.

Error

Error

Indicates calibration was not 
successful.

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Summary of Contents for LI1 Series

Page 1: ...Display to 199 990 11 Point Linearization Square Root Extraction with Low flow Cutoff 41 2 Digit Extra Zero Type NEMA 4X Front Panel 2 or 4 Relays 4 20 mA Output Options Lockout Feature Non volatile M...

Page 2: ...nt dECPt 21 Select Linear Input L or S 21 Select Number Of Calibration Points no PtS 21 General Calibration Scaling Instructions 22 Scale Using Internal Calibration I Cal 22 Calibrate Using an Externa...

Page 3: ...rs valves etc It is recommended to use this meter in a fail safe system that accommodates the possibility of meter failure or power failure WARNING Hazardous voltages exist within enclosure Installati...

Page 4: ...Cutoff point will CUTOFF result in a display of zero May be set from 1 count to 100 of full scale user selectable 6 11 POINT Input Range Minimum Span LINEARIZATION Between Inputs 4 20 mA 1 6 mA Number...

Page 5: ...POWER SUPPLY OUTPUT LOOP Power supply Min loop Max loop RESISTANCE resistance resistance 24 VDC 10 ohms 600 ohms 35 VDC external 600 ohms 1000 ohms 8 Model LI1X Universal Process Meter Instruction Ma...

Page 6: ...on Manual 11 10 SETUP AND PROGRAMMING Power Signal External Functions Options Connections Disconnect power to the meter before making any connections Do not connect power or earth ground to any unused...

Page 7: ...AC 4 20 mA Transmitter 3 2 1 Signal Input Selection Array Lockout Jumper L L P P S S C H A O L C M D K Signal Input Selection Array Loop Power Supply 4 20 mA Transmitter AC 3 2 1 Lockout Jumper L L P...

Page 8: ...Powered Meters Power Signal External Functions Figure 6 Transmitter and Meter Powered from Same DC Power Supply Figure 7 Transmitter and Meter Powered from Separate DC Power Supplies 14 15 24 VDC Powe...

Page 9: ...tely programmed using just the ENTER button The general method behind SBS is to push ENTER when the meter reads the desired value This value may be a menu title the entire display or just a single dig...

Page 10: ...ore it starts to scroll to accept it 4 If a flashing digit is not OK or if ENTER was not pushed in time to accept it wait for the digit to scroll and push ENTER when OK 5 Digits will scroll until ENTE...

Page 11: ...is necessary to first complete an Initial Calibration see Initial Calibration with External Source If Needed on page 20 Scale or Calibrate the Meter To select a Calibration Method apply power with AC...

Page 12: ...uction Manual 22 23 General Calibration Scaling Instructions Calibration is performed from the front panel using the ENTER but ton It does not require any tools or disassembly of the meter A calibrate...

Page 13: ...ero flow rate usually zero the high flow rate and the Low flow Cutoff point To program the meter for square root extraction push ENTER When L or S appears push ENTER again The meter will flash L or S...

Page 14: ...put option can be programmed without a calibrator This option can be calibrated so that a 4 mA out put is produced for any number displayed by the meter The 20 mA output may be programmed to correspon...

Page 15: ...ct on the alarm status LEDs Automatic Manual Reset Programming There are two ways to reset the relays 1 Automatically when the signal passes through the reset point 2 Automatically manually via the fr...

Page 16: ...ng inductive loads However installing Resistor Capacitor RC Networks improves this performance and prolongs the life of the meter s relay contacts This suppression can be obtained with RC networks ass...

Page 17: ...ur screws and washers 11 Reassemble front covers and install connectors Figure 18 Removing Front Bezel Model LI1X Universal Process Meter Instruction Manual Figure 19 Internal View of Meter Option Car...

Page 18: ...ut 7 set point display 7 Input 8 set point display 8 Input 9 set point display 9 Input 10 set point display 10 Input 11 set point display 11 Alarms Alarm 1 set point reset point Alarm 2 set point rese...

Page 19: ...truction Manual LIM690FL Rev B 6 99 10500 Humbolt Street Los Alamitos CA 90720 Tel 562 598 3015 Fax 562 431 8507 Spec Tech Industrial Electric www spectechind com 888 773 2832 Spec Tech Industrial Ele...