FlowLine LI1 Series Instruction Manual Download Page 15

Programming Confirmation

To verify that the alarm set and reset points have been programmed
as desired, push 

ENTER

, and push 

ENTER

again when

ALArS

appears. Before the display stops flashing #1 set point value, push

ENTER

again to advance the display to #1 reset point. Continue 

skipping through the remaining alarm set and reset points. To alter an
alarm point value, wait for the first digit to flash and program the
desired value using the 

Five Basic Digit/Display-setting Instructions on

page 19.

Alarm Operation

When the meter detects an alarm, a front panel LED illuminates to
indicate which alarm point has tripped. This LED will stay illuminated
until the meter display passes through the reset point.

Set Relays for Fail-safe Operation

In the fail-safe mode, the relay coils are energized and the Normally
Open (NO) contacts are connected to the Common (C) contacts under
normal operation. During an alarm condition, the relay coils are 

de-

energized, the Normally Closed (NC) contacts are connected to the
Common (C) contacts. During a power failure the relay contacts
reflect an alarm condition.

Figure 14: Option Card Installation

Model LI1X Universal Process Meter

Instruction Manual

Model LI1X Universal Process Meter

Instruction Manual

28

29

Alarm Acknowledgment

The ACK button on the front panel resets the optional relays only and
has no effect on the alarm status LEDs.

Automatic & Manual Reset Programming

There are two ways to reset the relays:
1. Automatically when the signal passes through the reset point.
2. Automat manually via the front panel ACK button, or a user

supplied momentary Normally Open push-button across terminals 
AK and CM at the rear of the instrument. That is, a relay may be 
manually reset prior to the signal passing through the reset point 
or it will automatically reset when the signal passes through the 
reset point.

A manual reset will reset all relays that are programmed for 
aut manual reset.

Figure 15: Relay Reset Jumpers

An array of jumpers located behind the front panel on the Display
PCB is used to program each relay for either automatic or aut
manual reset. Refer to page 32 for front panel removal instructions.
The top jumper is used for relay 1, the next for relay 2, etc. A relay
will automatically reset if no jumper is installed. A relay will automati-
cally reset, plus can be manually reset, if a jumper is installed over its
respective pins.

Example Above:

Relay 1 is programmed for automatic reset; 

Relays 2, 3, & 4 are programmed for aut manual reset.

Relays

Ribbon Cable

Front

J2

Screw 

T

erminals (Rear of PCB)

The failsafe
operation can
be disabled
by removing
jumper 

J2

located at the
front of the
relay option
card (see 
figure to left).
Refer page 32
for option
card installa-
tion and
removal.

1

2
3
4

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Spec Tech Industrial Electric

               www.spectechind.com

888-773-2832

Summary of Contents for LI1 Series

Page 1: ...Display to 199 990 11 Point Linearization Square Root Extraction with Low flow Cutoff 41 2 Digit Extra Zero Type NEMA 4X Front Panel 2 or 4 Relays 4 20 mA Output Options Lockout Feature Non volatile M...

Page 2: ...nt dECPt 21 Select Linear Input L or S 21 Select Number Of Calibration Points no PtS 21 General Calibration Scaling Instructions 22 Scale Using Internal Calibration I Cal 22 Calibrate Using an Externa...

Page 3: ...rs valves etc It is recommended to use this meter in a fail safe system that accommodates the possibility of meter failure or power failure WARNING Hazardous voltages exist within enclosure Installati...

Page 4: ...Cutoff point will CUTOFF result in a display of zero May be set from 1 count to 100 of full scale user selectable 6 11 POINT Input Range Minimum Span LINEARIZATION Between Inputs 4 20 mA 1 6 mA Number...

Page 5: ...POWER SUPPLY OUTPUT LOOP Power supply Min loop Max loop RESISTANCE resistance resistance 24 VDC 10 ohms 600 ohms 35 VDC external 600 ohms 1000 ohms 8 Model LI1X Universal Process Meter Instruction Ma...

Page 6: ...on Manual 11 10 SETUP AND PROGRAMMING Power Signal External Functions Options Connections Disconnect power to the meter before making any connections Do not connect power or earth ground to any unused...

Page 7: ...AC 4 20 mA Transmitter 3 2 1 Signal Input Selection Array Lockout Jumper L L P P S S C H A O L C M D K Signal Input Selection Array Loop Power Supply 4 20 mA Transmitter AC 3 2 1 Lockout Jumper L L P...

Page 8: ...Powered Meters Power Signal External Functions Figure 6 Transmitter and Meter Powered from Same DC Power Supply Figure 7 Transmitter and Meter Powered from Separate DC Power Supplies 14 15 24 VDC Powe...

Page 9: ...tely programmed using just the ENTER button The general method behind SBS is to push ENTER when the meter reads the desired value This value may be a menu title the entire display or just a single dig...

Page 10: ...ore it starts to scroll to accept it 4 If a flashing digit is not OK or if ENTER was not pushed in time to accept it wait for the digit to scroll and push ENTER when OK 5 Digits will scroll until ENTE...

Page 11: ...is necessary to first complete an Initial Calibration see Initial Calibration with External Source If Needed on page 20 Scale or Calibrate the Meter To select a Calibration Method apply power with AC...

Page 12: ...uction Manual 22 23 General Calibration Scaling Instructions Calibration is performed from the front panel using the ENTER but ton It does not require any tools or disassembly of the meter A calibrate...

Page 13: ...ero flow rate usually zero the high flow rate and the Low flow Cutoff point To program the meter for square root extraction push ENTER When L or S appears push ENTER again The meter will flash L or S...

Page 14: ...put option can be programmed without a calibrator This option can be calibrated so that a 4 mA out put is produced for any number displayed by the meter The 20 mA output may be programmed to correspon...

Page 15: ...ct on the alarm status LEDs Automatic Manual Reset Programming There are two ways to reset the relays 1 Automatically when the signal passes through the reset point 2 Automatically manually via the fr...

Page 16: ...ng inductive loads However installing Resistor Capacitor RC Networks improves this performance and prolongs the life of the meter s relay contacts This suppression can be obtained with RC networks ass...

Page 17: ...ur screws and washers 11 Reassemble front covers and install connectors Figure 18 Removing Front Bezel Model LI1X Universal Process Meter Instruction Manual Figure 19 Internal View of Meter Option Car...

Page 18: ...ut 7 set point display 7 Input 8 set point display 8 Input 9 set point display 9 Input 10 set point display 10 Input 11 set point display 11 Alarms Alarm 1 set point reset point Alarm 2 set point rese...

Page 19: ...truction Manual LIM690FL Rev B 6 99 10500 Humbolt Street Los Alamitos CA 90720 Tel 562 598 3015 Fax 562 431 8507 Spec Tech Industrial Electric www spectechind com 888 773 2832 Spec Tech Industrial Ele...

Reviews: