D.  SCALE THE 4-20MA INPUT 

 
The 4-20 mA input can be scaled to the appropriate values for a given application. The 4-mA input 
(input 1) should have a corresponding display value (display 1) which represents the low end of the 
process value range being measured by the transmitter. Likewise, the 20-mA input (input 2) should 
have a display value (display 2) which represents the high end of the process value range. 
 

 

Input 

Display 

Input Example 

Display Example 

Typically 04.000 mA 

Value of tank at Empty 

04.000 

0000.0 

Typically 20.000 mA 

Value of tank at Full 

20.000 

0100.0 

 

For example:

 If the meter is used to display the level of a 100 ft tall tank, the transmitter should send a  

4 mA signal when the tank is empty and a 20-mA signal when the tank is full. The meter should be 
programmed to interpret these inputs on a display range of 0-100, so that at 4-mA the meter will display 
0 and at 20-mA the meter will display 100. 
 
A signal source is not needed to scale the meter; simply program the inputs and corresponding display 
value 
 

 

 
In the examples above, the 4 mA/Empty reading could represent 0 Gallons, 0 Feet, 0 Inches or 0.0%. 
The 20 mA/Full reading could represent 5,000 Gallons, 10.00 Feet, 120.0 Inches or 100.0%.  Setting 
4mA for an empty tank and 20 mA for a full tank simplifies configuration. 

 

To set the SCALE function: 

1)  Press 

MENU

 button to bring up the SETUP/Input screen. 

2)  Press 

ENTER

 button to bring up SCALE/Units screen. 

3)  Press 

Right Arrow

 button to bring up SCALE/Input_1 screen. 

4)  Press 

ENTER

 button to bring up INP 1/04.000 screen. 

a.  This is the default of 04.000mA and does not need to be changed. 
b.  If the value needs to changed, use the 

UP Arrow

 to incrementally increase the selected digit and the 

Right Arro

w to move to the next digit.  

5)  Press 

ENTER

 to save the Input 1 setting and to bring up SCALE/Disp_1 screen.  

6)  Press 

ENTER

 to bring up DSP_1/00000000 screen. 

a.  The default is 0000000 and typically does not need to be changed. 
b.  If the value needs to changed, use the 

UP Arrow

 to incrementally increase the selected digit and the 

Right Arro

w to move to the next digit.  

7)  Press 

ENTER

 to save the Display 1 setting and to bring up SCALE/Input_2 screen. 

8)  Press 

ENTER

 to bring up INP_2/20000 screen.   

a.  This is the default of 20.000mA and does not need to be changed. 

Summary of Contents for DataLoop LI23 Series

Page 1: ...I2 ne Inc 10500 Hu 18 Flowline Rights Reser e in USA Data Loop Powere 23 Series umbolt Street Los Inc rved aLoo ed Meters s Quick S Alamitos CA 9072 op Start 20 p 562 598 3015 5 f 562 431 8507 w flowline com QS302100 Rev A A ...

Page 2: ...ed General Purpose Bar graph Two Solid State Relays LI23 1211 Loop Powered General Purpose Bar graph Two Solid State Relays and 4 20mA Analog Output Model Accessories LM91 1001 Single NEMA Box non windowed 1 8 DIN PC LM91 2001 Dual NEMA Box non windowed 1 8 DIN PC LM92 1002 Single NEMA Box Windowed 1 8 DIN PC LM92 2002 Dual NEMA Box Windowed 1 8 DIN PC LM92 3002 Triple NEMA Box Windowed 1 8 DIN PC...

Page 3: ...ure to maintain a minimum panel thickness of 0 04 0 25 1 0 mm 6 4 mm to maintain type 4X rating This would equal 0 06 1 5 mm for a steel panel and 0 16 4 1 mm for a plastic panel Remove the Loop Powered Meter s two mounting brackets Back off the two screws so that there is 6 4 mm or less through the bracket Slide the bracket toward the front of the case and remove it Insert the Loop Powered Meter ...

Page 4: ...talled in bright lighting conditions to reduce the maximum voltage drop to 1 5 V as shown in the following diagram THE LOOP POWERED METER INTERFACE The Loop Powered Meter is factory calibrated to read in milliamps prior to shipment Overview There are no jumpers to set for the meter input selection All setup and programming is performed through the front panel interface After power and input signal...

Page 5: ...f a digit or character ENTER F3 Use this button to access a menu or to accept a setting or programmed digit character value PROGRAMMING THE LOOP POWERED METER To enter the LI23 series Programming menu press the MENU button With the UP arrow or RIGHT arrow you can scroll through four menu options Input Output Advanced and Display Input This selects the units of operation as well as scaling the disp...

Page 6: ... hold the RIGHT Arrow button until all digits reset to zero Press the ENTER button at any time to accept a setting or MENU button to exit without saving changes Note the underscore in the graphic below is provided to show which digit would be flashing A Confirm the Operation Scale for the Application Typically the LI23 series must match the operational span of the transmitter mounted on top of or ...

Page 7: ...accuracy is very good but may not be practical When selecting a decimal point take into account the practical scale for reading the level of liquid To set the Decimal Point 1 Press the MENU button to bring up the SETUP Input screen 2 Press Up Arrow button to bring up SETUP Display screen 3 Press ENTER button to bring up DSPLAY Units screen 4 Press Right Arrow to bring up DSPLAY decpt screen 5 Pres...

Page 8: ...cm meter etc Please determine the units of operation that you want to appear on the display To set the Units of Operation 1 Press MENU button to bring up the SETUP Input screen 2 Press ENTER button to bring up SCALE Units screen 3 Press ENTER to bring up SCALE Height screen 4 Use the Right Arrow or Up Arrow to change the groups between HEIGHT and VOLUME 5 Press ENTER button to select your group 6 ...

Page 9: ...n the examples above the 4 mA Empty reading could represent 0 Gallons 0 Feet 0 Inches or 0 0 The 20 mA Full reading could represent 5 000 Gallons 10 00 Feet 120 0 Inches or 100 0 Setting 4mA for an empty tank and 20 mA for a full tank simplifies configuration To set the SCALE function 1 Press MENU button to bring up the SETUP Input screen 2 Press ENTER button to bring up SCALE Units screen 3 Press...

Page 10: ... value you want to display when the tank is full b To change the value use the UP Arrow to incrementally increase the selected digit and the Right Arrow to move to the next digit c If you are reading the height of the liquid this value will typically be the same value as the Fill Height setting in the Flowline transmitter d If you 11 Press ENTER to save the Display 2 setting and to bring up SAVE s...

Page 11: ...eature can be enabled or disabled using the Bargraph menu BARGRAPH The value displayed on the bar graph can be the percentage of full scale PV PCT or the percentage of a user programmable range PV To set the Bar Graph 1 Press the MENU button to bring up the SETUP Input screen 2 Press Up Arrow button to bring up SETUP Display screen 3 Press UP Arrow or RIGHT Arrow button three 3 times to bring up D...

Page 12: ...hich the original purchaser does not follow the warranty procedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized by Flowline have attempted to repair 5 have been involved in accidents or natural disasters or 6 are damaged during return shi...

Reviews: