FlowLine DataLoop LI23-1001 Instruction Manual Download Page 17

DataLoop™ LI23 Loop-Powered Process Meter

 

Instruction Manual 

 

 

MN302100 Rev 3 

17 

Parameter 

Action/Setting Description 

     

  RLY2 

Start/stop relay 2 timer 

     

   

START 

Start the selected timer output 

     

   

STOP 

Stop the selected timer output 

     

   

STR‐STP 

Start or stop the selected timer 
output 

     

ALARM.FN 

Set the function key or digital input 
to acknowledge an alarm or ac-
cess set points 

     

  ACK 

Acknowledge all active alarms 

     

  SETPOINT 

Access all output set points 

     

  SETPT.OC1 

Access open collector 1 set point 

     

  SETPT.OC2 

Access open collector 2 set point 

     

  SETPT.R1 

Access relay 1 set point 

     

  SETPT.R2 

Access relay 2 set point 

     

SWATCH.FN 

Set the function key or digital input 
to activate stopwatch 

     

  START 

Start the stopwatch 

     

  STOP 

Pause/Stop the stopwatch 

     

  STR‐STP 

Start or stop the stopwatch 

     

TARE.FN 

Set the function key or digital input 
to tare the display 

     

  TARE 

Tare the display value 

     

  RST TARE 

Reset the display value 

     

HOLD FN 

Set the function key or digital input 
to hold an output 

     

  HOLD.OUT 

Hold all outputs 

     

  HLD.UNHLD 

Hold or un-hold all outputs 

     

  OC1+2 

Hold/un-hold open collector out-
puts 

     

  RLY1+2 

Hold/un-hold relay outputs 

     

  mAOUT 

Hold/un-hold 4-20 mA output 

     

   

HOLD 

Hold selected output 

     

   

HLD.UNHLD 

Hold or un-hold selected output 

     

DISABLE 

Disable function key or digital input 

     

RST FN 

Set the function key or digital input 
to reset a value 

     

  RESET 

Reset min, max, or max/min PV 

     

  R MIN.MAX 

Reset max and min PV value 

    HINT 

Display hint text on key press and 
execute action on next key press 

     

OFF 

Turn the hint function off 

     

ON 

Turn the hint function on 

  SYSTEM 

Program system settings 

    AOUTCAL 

Calibrate the analog output 

    DEFAULT 

Reset meter to factory defaults 

    PV 2 

Enable the meter to scale a se-
cond PV based on the mA input 

     

DISABLE 

Disable dual-scale feature (default) 

     

ENABLE 

Enable dual-scale feature 

    BACKLITE 

Enable/disable display backlight 

     

ENABLE 

Enable the backlight (default) 

     

DISABLE 

Disable the backlight 

    INFO 

View meter software, version, and 
model; change the identifier tag 

     

SFT 

The software ID number 

Parameter 

Action/Setting Description 

     

VER 

The software version 

     

MODEL 

The meter model number 

     

ID.TAG 

The meter identifier tag 
Press 

Enter

 to edit tag 

    ICAL 

Internal calibration used for scaling 

DISPLAY 

Program the meter’s display 

  UNITS 

Change the display units within the 
selected unit class 

  DEC.PT 

Change the decimal point location 

  COMMA 

Enable or disable the use of a 
comma on the bottom display 

    ENABLE 

Enable comma (default) 

    DISABLE 

Disable comma 

  BARGRAPH 

Enable or change the bargraph 

    PV

 (

1

 or 

2

)

 

Set the bargraph to display the PV 
percentage of full scale 

    OFF 

Turn the bargraph feature off 

  TOP 

Set what to display on the top line 

    PV

 (

1

 or 

2

)

 

Display the process variable 

    PV+UNIT

 (

1

 or 

2

)

 

Display the process variable and 
units alternating 

    PV+TAG

 (

1

 or 

2

)

 

Display the process variable and 
tag alternating 

    TAG+UNIT 

Display tag and units alternating 

    PV+U+TAG

 (

1

 or 

2

)

 

Display the process variable, unit, 
and tag alternating 

    PV1+PV2 

Display both process variables 
(dual-scale only; see 

PV 2

 under 

advanced features menu) 

    TAG 

Display the tag 

    STPWATCH 

Display the stopwatch 

    TIMR OC1 

Display open collector 1 timer 

    TIMR OC2 

Display open collector 2 timer 

    TIMER R1 

Display relay 1 timer 

    TIMER R2 

Display relay 2 timer 

    MIN 

Display minimum value 

    MAX 

Display maximum value 

    MIN MAX 

Display alternating min and max 

    OFF 

Turn top line off 

    UNITS 

Display the units 

  BOTTOM 

Set what to display on the bottom 
line 

    UNITS 

Display the units 

    PV

 (

1

 or 

2

)

 

Display the process variable 

    PV+UNIT

 (

1

 or 

2

)

 

Display the process variable and 
unit alternating 

    PV+TAG

 (

1

 or 

2

)

 

Display the process variable and 
tag alternating 

    TAG+UNIT 

Display the tag and unit alternating 

    PV+U+TAG

 (

1

 or 

2

)

 

Display the process variable, unit, 
and tag alternating 

    PV1+PV2 

Display both process variables 
(dual-scale only; see 

PV 2

 under 

advanced features menu) 

    TAG 

Display the tag 

    STPWATCH 

Display the stopwatch 

Summary of Contents for DataLoop LI23-1001

Page 1: ...ed Process p 4 5 Volt D ed Backligh P65 Front 40 to 75 anumeric To anumeric Bo Bargraph w oated PCB ollector Ou p Powered 0 mA Analo Alternation y Runtime a Street Los A 507 w flow Meter Drop with B...

Page 2: ...e meter WARNING Risk of elec tric shock or personal injury Warning This product is not recommended for life support applica tions or applications where malfunctioning could result in personal injury o...

Page 3: ...nging What is Displayed TOP and BOTTOM 22 Programming the Bargraph 23 Programming the Outputs OUTPUT 23 Open Collector Outputs OPEN COLLECTR 25 Solid State Relay Outputs RELAY 29 4 20 mA Output 4 20 m...

Page 4: ...resents These loop powered meters can be installed virtually anywhere because they get their power from the 4 20 mA loop and therefore require no separate power source And they only drop 1 5 V 4 5 V w...

Page 5: ...oop Powered General Purpose Bargraph Two Solid State Relays LI23 1211 Loop Powered General Purpose Bargraph Two Solid State Relays and 4 20 mA Analog Output Note All models come with two open collecto...

Page 6: ...sage On or Off user programmable 8 characters maximum Displayed every 10 seconds for 1 second on bottom line Display Update Rate Ambient 10 C 1 Update Second Ambient 20 C 1 Update 2 Seconds From 20 C...

Page 7: ...est Frequency Pulse Output Factor 0 000001 to 999 999 9 Pulse Width 0 5 ms 1 kHz 500 ms 1 Hz 50 duty cycle Pulse Output Frequency 1 000 Hz maximum Quadrature Pulse Output Available for Output 2 90 beh...

Page 8: ...uld be performed only by trained service personnel Service requiring replacement of internal components must be performed at the factory Installation There is no need to remove the meter from its case...

Page 9: ...ackets provided with the meter back off the two screws so that there is 6 4 mm or less through the bracket Slide the bracket toward the front of the case and remove Insert meter into the panel cutout...

Page 10: ...connections hould be perfo state and lo ensure person e meter show onnector La Process w terminal co rea installation 60 C or 60 7 Observe all s ormed in acco ocal codes to p nnel safety ws the locati...

Page 11: ...op There are no switches or jumpers to set up for the input Setup and programming is performed through the front panel buttons or PC based software Figure 5 4 20 mA Input Connection without Backlight...

Page 12: ...A OUT The 4 20 mA output must be powered from an external power supply Figure 8 4 20 mA Output Connections Solid State Relay Connections Relay connections are made to a four terminal connector labeled...

Page 13: ...anual MN302100 Rev 3 13 Open Collector Outputs Open collector output 1 and 2 connections are made to terminals labeled O1 and O1 and O2 and O2 Connect the alarm or pulse input device as shown below Fi...

Page 14: ...ramm d Status ription t Arrow F1 rrow F2 r F3 or exit the Pr button to scro ers during tex ow button w button to ze tton to scroll b s a menu or to Process d prior to ship 0 mA input T e to NIST stan...

Page 15: ...PA Pascal hPA Hectopascal KPA Kilopascal MPA Megapascal CUSTM Custom unit Parameter Action Setting Description WEIGHT Weight unit class gm Grams Kg Kilograms tonnE Tonnes metric oz Ounces 1b Pounds to...

Page 16: ...for square root extrac tion EXPONENT Set meter for programmable expo nent and enter exponent value RH TANK Round horizontal tank dual scale only see PV 2 under advanced features menu Parameter Action...

Page 17: ...ABLE Enable the backlight default DISABLE Disable the backlight INFO View meter software version and model change the identifier tag SFT The software ID number Parameter Action Setting Description VER...

Page 18: ...ssing Enter F3 to confirm the setting or pressing En ter F3 at the SAVE screen when available Setting Numeric Values The numeric values are set using the Right and Up Arrow buttons Press Right Arrow t...

Page 19: ...ay the 4 20 mA input The input is capable of accepting any signal from 4 to 20 mA SETUP INPUT SCALE UNITS SCALE INPUT 1 SCALE DISP 1 UNITS VOLUME HEIGHT TEMP PRESSURE WEIGHT RATE CUSTOM UNIT GAL GAL L...

Page 20: ...ay Rate Units RATE GAL T Gallons per time unit T L T Liters per time unit T IGAL T Imperial gallons per time unit T M3 T Cubic meters per time unit T BBL T Barrels per time unit T BUSH T Bushels per t...

Page 21: ...following submenus Units Decimal Point Comma Bargraph Top and Bottom Changing the Units UNITS It is possible to change the display units within the selected unit class without the need to re scale th...

Page 22: ...d Tag Tag Stopwatch Open Collector 1 or 2 Timer Relay 1 or 2 Timer Minimum Value Maximum Value or Both Off Blank Units The bottom line BOTTOM can display Units Process Value PV Process Value 2 dual sc...

Page 23: ...GRAPH The value displayed on the bargraph can be the percentage of full scale PV PCT or the percentage of a user programmable range PV If the meter is in dual scale mode the bargraph can be assigned t...

Page 24: ...0 Rev 3 Ordering Information on page 5 for details SETUP OUTPUT OPEN COLLECTR OUT RELAY OUT 4 20 mA OUT CONTROL OC OUT OUTPUT1 OC OUT OUTPUT2 RELAY OUTPUT1 RELAY OUTPUT2 RELAY INFO 4 20 PV 4 20 RETRAN...

Page 25: ...the PV value or the digital input The alarm status will show on the display even if the output is not wired A timer output TIMER turns the open collector on and off at the specified time intervals Th...

Page 26: ...r second would be 200 The maximum frequency is 1 000 Hz Setting output 2 to quadrature will duplicate the other open collector output but lag by 90 degrees out of phase The other output should be prog...

Page 27: ...m If the alarm is set to PV a set and reset point must be programmed The set point is the display value at which the alarm will turn on and the reset point is the display value at which the alarm will...

Page 28: ...to 99 hrs 59 min and 59 seconds The stopwatch function may be assigned to any open collector There are three settings needed to use the function effectively 1 Assign stopwatch to either top or bottom...

Page 29: ...utput TIMER turns the relay on and off at the specified time intervals The timer can be set as single shot or continuous timer The stopwatch output STPWATCH allows the relay to be manually activated b...

Page 30: ...alarm If the alarm is set to PV a set and reset point must be programmed The set point is the display value at which the alarm will turn on and the reset point is the display value at which the alarm...

Page 31: ...tely This prevents excessive wear and overheating of one pump over the lack of use of the other pump Pump alternation uses both relays in tandem to alternate between two similar pumps The ALTERN menu...

Page 32: ...der to delay the activation or deactivation of the relays by a certain number of seconds after reaching either the on point or off point For pumps that typically remain on extensively the alternation...

Page 33: ...aphics provide a visual representation of a typical pump alternation application 1 Relay 2 turns the main pump on at 6000 gallons and turns it off at 1000 gallons 2 With the Pump Alternation feature a...

Page 34: ...l up to 99 hrs 59 min and 59 seconds The stopwatch function may be assigned to any relay There are three settings needed to use the function effectively 4 Assign stopwatch to either top or bottom disp...

Page 35: ...ly program two display values and corresponding mA output signals Process Variable PV To scale the analog output enter display value 1 and a corresponding analog output value for this display and ente...

Page 36: ...anced features include advanced PV setup cutoff filter pass word function key programming and system settings SETUP ADVANCED ADV PV SETUP CUTOFF FILTER PASSWRD USER SYSTEM PV FUNCTION PV SCALE CAL CUT...

Page 37: ...PV1 and PV2 under the linear function Multi point linearization can be used to linear ize the display for non linear signals such as those from level transmitters used to measure volume in odd shaped...

Page 38: ...variable then press Enter For information on units see Available Unit Classes and Units on page 20 3 The meter displays INP 1 Apply a known signal and press Enter The display will flash while acceptin...

Page 39: ...se filter bypass may be set between 0 1 and 99 9 of full scale Enabling Password Protection PASSWRD The Password menu is used for programming security to prevent unauthorized changes to the pro gramme...

Page 40: ...ALL Start all timers STOP ALL Stop all timers S STP ALL Start or stop all timers OC1 Start stop open collector 1 timer OC2 Start stop open collector 2 timer RLY1 Start stop relay 1 timer RLY2 Start st...

Page 41: ...level applications such as displaying the height and volume of a tank it is possible to enable a second PV which can be scaled to display a different value based on the same 4 20 mA input This is acc...

Page 42: ...s part of the Advanced menu Internal Calibration is performed as follows 1 Press the Menu button to enter Programming Mode 2 Press the Up Arrow button twice and press Enter to access the Advanced menu...

Page 43: ...ngs alley reached the F1 key de menu essing the En ain to unlock tons and the factory to dis button to acce rs to reset Units units within th AY menu allow L s and the a custom un UNITS on page Proces...

Page 44: ...to access the Advanced menu 3 Press the Up Arrow button and press Enter to access the System menu 4 Press the Right Arrow button and press Enter to access the Default menu 5 Press Enter twice in quick...

Page 45: ...0 Alarm On Delay DELAY ON 0 seconds Alarm Off Delay DELAY OFF 0 seconds Alarm Failsafe FAILSAFE OFF Red LED RED ON Flash PV FLASH ON Alarm Message MSG ON Message Text MSG EDIT ALARM 3 Pump Ctrl On ON...

Page 46: ...nd bypass values increase Display response is too slow Check filter and bypass values Display reading is not accurate Check 1 Signal input conditioner selected Linear square root etc 2 Scaling or cali...

Page 47: ...DataLoop LI23 Loop Powered Process Meter Instruction Manual MN302100 Rev 3 47 This Page Intentionally Left Blank...

Page 48: ...d above 2 have been sub jected to electrical mechanical or chemical damage due to improper accidental or negligent use 3 have been modified or altered 4 anyone other than service personnel authorized...