To use as Independent Relay mode, press the IND soft key and then press
Next.
Independent Relays #5 and #6
•
Enter the Relay #5 ON set point (where Relay
#5will energize) and press Next
•
Enter the Relay #5 OFF set point (where
Relay #5 will de-energize) and press Next
•
Enter the Relay #6 ON set point (where Relay
#6 will energize) and press Next.
•
Enter the Relay #6 OFF set point (where
Relay #6 will de-energize) and press Next.
•
To change to a Duplex mode, press the DUP soft key and then press Next.
Duplex Relays #5 and #6
•
Enter the LEAD ON relay set point (where
the lead relay will energize) and press Next
•
Enter the ALL OFF relay set point (where
both relays will de-energize) and press Next
•
Enter the LAG ON relay set point (where the
lag relay will energize) and press Next.
o
You do not need to provide a value for
Relay #6 OFF.
o
Duplex can be used as a Filling or
Emptying configuration.
o
Always make sure that the LAG ON is
above the LEAD ON for an Empty
configuration or below the LEAD ON for
a Fill configuration.