4.  TABELA MOCY GRZEWCZYCH 

4. HEATING CAPACITY 

 

ELiS C-W 200

 

Tp1 

PT 

Qw 

pw 

Tp2 

PT 

Qw 

pw 

Tp2 

PT 

Qw 

pw 

Tp2 

PT 

Qw 

pw 

Tp2 

°C 

kW 

l/h 

kPa 

°C 

kW 

l/h 

kPa 

°C 

kW 

l/h 

kPa 

°C 

kW 

l/h 

kPa 

°C 

 

Tw1/Tw2 = 90/70°C 

Tw1/Tw2 = 80/60°C 

Tw1/Tw2 = 70/50°C 

Tw1/Tw2 = 60/40°C 

 

V1 = 2300 m

3

/h 

31,4 

1386 

39,4 

40,5 

27,2 

1194 

30,9 

35,0 

22,9 

1003 

23,3 

29,5 

18,7 

813 

16,6 

24,0 

29,5 

1301 

35,1 

43,0 

25,2 

1108 

27,0 

37,5 

21,0 

917 

19,8 

32,0 

16,7 

727 

13,6 

26,5 

10 

27,5 

1215 

31,0 

45,0 

23,3 

1022 

23,3 

40,0 

19,0 

830 

16,6 

34,5 

14,7 

639 

10,8 

29,0 

15 

25,6 

1128 

27,1 

47,5 

21,3 

935 

19,9 

42,0 

17,0 

743 

13,6 

36,5 

12,6 

550 

8,3 

31,0 

20 

23,6 

1040 

23,4 

50,0 

19,3 

847 

16,6 

44,5 

14,9 

654 

10,8 

39,0 

10,6 

460 

6,0 

33,5 

 

V2=2600 m

3

/h 

34,0 

1498 

45,4 

38,5 

29,4 

1290 

35,6 

33,5 

24,8 

1084 

26,8 

28,0 

20,2 

879 

19,1 

23,0 

31,9 

1406 

40,5 

41,0 

27,3 

1198 

31,1 

36,0 

22,7 

991 

22,8 

30,5 

18,0 

786 

15,6 

25,5 

10 

29,8 

1313 

35,7 

43,5 

25,1 

1105 

26,9 

38,5 

20,5 

897 

19,1 

33,0 

15,9 

691 

12,4 

28,0 

15 

27,6 

1219 

31,2 

46,0 

23,0 

1010 

22,9 

41,0 

18,3 

802 

15,6 

35,5 

13,6 

595 

9,5 

30,5 

20 

25,5 

1125 

26,9 

48,5 

20,8 

915 

19,1 

43,5 

16,1 

706 

12,4 

38,0 

11,4 

497 

6,9 

33,0 

 

V3 = 3000 m

3

/h 

37,1 

1638 

53,5 

36,5 

32,1 

1411 

41,9 

31,5 

27,1 

1185 

31,5 

26,5 

22,0 

961 

22,4 

22,0 

34,8 

1538 

47,6 

39,5 

29,8 

1310 

36,6 

34,5 

24,8 

1084 

26,8 

29,5 

19,7 

859 

18,3 

24,5 

10 

32,5 

1436 

42,0 

42,0 

27,5 

1207 

31,6 

37,0 

22,4 

981 

22,4 

32,0 

17,3 

755 

14,5 

27,0 

15 

30,2 

1333 

36,7 

44,5 

25,1 

1104 

26,8 

39,5 

20,0 

877 

18,2 

34,5 

14,9 

650 

11,1 

29,5 

20 

27,9 

1229 

31,7 

47,0 

22,8 

1000 

22,4 

42,0 

17,6 

772 

14,6 

37,0 

12,5 

543 

8,1 

32,0 

 

V

 – airflow | przep

ł

yw powietrza  

PT 

– heat capacity | moc grzewcza  

Tp1

 – inlet air temp. | temperatura powietrza na wlocie do aparatu  

Tp2

 – outlet air temp. | temperatura powietrza na wylocie z aparatu  

 

Tw1

 – inlet water temp. | temperatura wody na zasilaniu wymiennika  

Tw2

 – outlet water temp. | temperatura wody na powrocie z wymiennika  

Qw 

– water flow rate | strumie

ń

 przep

ł

ywu wody grzewczej | Heizwasserstrom  

Δ

pw

– pressure drop of water | spadek ci

ś

nienia wody w wymienniku  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for ELiS C

Page 1: ...ELiS C DTR ELiS C 03 26 v 3 PLEN PL KURTYNA POWIETRZNA DOKUMENTACJA TECHNICZNA EN AIR CURTAIN TECHNICAL DOCUMENTATION OPERATION MANUAL ...

Page 2: ...tyna z wodnym wymiennikiem ciepła ELiS C W 150 kurtyna z wodnym wymiennikiem ciepła ELiS C W 200 kurtyna z wodnym wymiennikiem ciepła ELiS C E 100 kurtyna z grzałkami elektrycznymi ELiS C E 150 kurtyna z grzałkami elektrycznymi ELiS C E 200 kurtyna z grzałkami elektrycznymi ELiS C W E 100 150 200 kurtyny w standardzie wyposażone w 3 biegowy wentylator oraz płytę montażową The ELiS C device group i...

Page 3: ...44 5 46 5 48 5 46 5 48 5 50 5 48 5 50 5 52 5 Max temp wody grzewczej o C Max heating water temperature o C 90 90 90 Max ciśnienie robocze MPa Max operating pressure MPa 1 2 1 2 1 2 Przyłącze gwint wewnętrzny Internal thread connection Zasięg m Range m 3 3 3 Max temp pracy o C Max working temperature o C 60 60 60 Masa urządzenia kg Device mass kg 19 27 5 35 1 Temperature increase at inlet air 10 o ...

Page 4: ...Insulation class 21 F 21 F 21 F Max poziom ciśnienia akustycznego dB A Max acoustic pressure level dB A 44 5 46 5 48 5 46 5 48 5 50 5 48 5 50 5 52 5 Zasięg m Range m 3 3 3 Max temp pracy o C Max working temperature o C 60 60 60 Masa urządzenia kg Device mass kg 14 5 19 9 25 1 Temperature increase at inlet air 10 o C Przyrost dla temp powietrza na wlocie 10 o C Poziom ciśnienia akustycznego podano ...

Page 5: ... 0 12 3 538 12 5 26 0 9 9 432 8 8 21 0 5 15 9 703 19 0 38 5 13 6 596 14 5 33 5 11 2 491 10 6 28 5 8 8 385 7 1 23 5 10 14 9 655 16 7 41 0 12 5 549 12 5 36 5 10 1 443 8 8 31 5 7 7 337 5 6 26 5 15 13 8 608 14 6 44 0 11 4 501 10 6 39 0 9 0 395 7 2 34 0 6 6 288 4 3 29 0 20 12 7 560 12 6 46 5 10 3 453 8 9 41 5 7 9 346 5 7 36 5 5 5 238 3 1 31 5 ELiS C W 150 Tp1 PT Qw pw Tp2 PT Qw pw Tp2 PT Qw pw Tp2 PT Q...

Page 6: ...105 26 9 38 5 20 5 897 19 1 33 0 15 9 691 12 4 28 0 15 27 6 1219 31 2 46 0 23 0 1010 22 9 41 0 18 3 802 15 6 35 5 13 6 595 9 5 30 5 20 25 5 1125 26 9 48 5 20 8 915 19 1 43 5 16 1 706 12 4 38 0 11 4 497 6 9 33 0 V3 3000 m 3 h 0 37 1 1638 53 5 36 5 32 1 1411 41 9 31 5 27 1 1185 31 5 26 5 22 0 961 22 4 22 0 5 34 8 1538 47 6 39 5 29 8 1310 36 6 34 5 24 8 1084 26 8 29 5 19 7 859 18 3 24 5 10 32 5 1436 ...

Page 7: ...nting bracket 2 2 Wspornik należy zamontować do przegrody pionowej za pomocą 4 śrub M8 Rozstaw otworów płyty montażowej model rozstaw C W E 100 90x440 mm C W E 150 200 90x840 mm 2 Bracket should be mounted to the wall with 4 screws M8 Hole spacing model spacing C W E 100 90x440 mm C W E 150 200 90x840 mm 3 3 Założyć kurtynę na wsporniku montażowym 3 Put the curtain on the bracket 4 4 Po zamontowan...

Page 8: ...ączenie zasilania oraz sterowania do kurtyny ELiS C należy zdemontować pokrywę odkręcić 4 śruby znajdującą się w górnej części kurtyny To connect the control system and power supply to the ELIS C curtain remove the cover unscrew 4 screws located at the top of the unit ...

Page 9: ...kurtyny Return pipe water supply 6 SCHEMAT PODŁĄCZENIA ELiS C E 6 CONNECTION DIAGRAM ELiS C E zasilanie Power supply 3x400V 50Hz ELiS C E 100 5x2 5 mm 2 wyłącznik naprądowy B16 Overcurrent breaker B16 ELiS C E 150 5x2 5 mm 2 wyłącznik naprądowy B20 Overcurrent breaker B20 ELiS C E 200 5x4 0 mm 2 wyłącznik naprądowy B25 Overcurrent breaker B25 3 stopniowy regulator obrotów z termostatem Air curtain...

Page 10: ...uted in a way which does not induce stresses It is recommended to use flex pipes to connect the stubs It is recommended to install vent valves at the highest point of the system The system should be executed so that in the case of a failure it is possible to disassemble the device For this purpose it is best to use shut off valves just by the device The system with the heating medium must be prote...

Page 11: ...aty za urządzenie zastępcze zgodnie z wystawioną fakturą Ograniczenia gwarancji 1 W skład świadczeń gwarancyjnych nie wchodzą montaż i instalacja urządzeń prace konserwacyjne usuwanie usterek spowodowanych brakiem wiedzy na temat obsługi urządzenia 2 Gwarancja nie obowiązuje w przypadku wystąpienia niżej wymienionych usterek uszkodzenia lub zniszczenia produktu powstałe w rezultacie niewłaściwej e...

Page 12: ...12 www flowair com ...

Reviews: