5
(1) According to ISO 27327-1;
(2) Acoustic pressure level has been measured in a 1500m
3
space with a medium sound absorption coefficient, directional factor: Q=2;
(3) Acoustic power level according to ISO 27327-2;
(4) Power and temperature range specified for the parameters: min. capacity, heating medium temperature 60/40°C temperature at the inlet to the device 18°C - max. efficiency,
heating medium temperature 60/40°C temperature at the inlet to the device 18°C;
4.
DIMENSIONS
5.
INSTALLATION
Air curtains must be installed as close as possible to the door opening and cover:
•
the entire width (applies to horizontal installation),
•
full height (applies to vertical mounting).
CORRECT
WRONG
CORRECT
WRONG
ELiS AX45-
W3R-100
ELiS AX45-
W3R-150
ELiS AX45-
W3R-200
ELiS AX45-
W3R-250
ELiS AX45-
W4R-100
ELiS AX45-
W4R-150
ELiS AX45-
W4R-200
ELiS AX45-
W4R-250
Power supply [V/Hz]
230/50
230/50
230/50
230/50
230/50
230/50
230/50
230/50
Max. current consumption [A]
3,3
4,6
6,4
7,6
3,2
4,5
6,3
7,5
Power consumption [kW]
0,49
0,65
0,99
1,15
0,49
0,65
0,99
1,15
IP
21
Connection stub ['']
3/4
Air volume
(1)
[m
3
/h]
1100-2500
1500-3500
2200-5000 2400-6100
1000-2400
1400-3400
2100-4900 2300-6000
Acoustic pressure level
(2)
[dB(A)]
43-61
44-62
45-64
46-65
42-60
43-61
44-63
45-64
Acoustic power level
(3)
[dB(A)]
59-77
60-78
61-80
62-81
58-76
59-77
60-79
61-80
Heating power
(4)
[kW]
9,3-15,7
13,9-24,1
18,4-31,8
22,1-41,4
10,3-19,1
15,3-28,9
22,2-40,6
25,6-51,3
Temperature increase
(4)
(ΔT ) [°C]
25-18
27-20
24-19
27-20
30-23
32-25
31-24
33-25
Max. water pressure [MPa]
1,6
Max. water temperature [˚C]
60
Device mass [kg]
40,8
55,5
73,7
88,8
42,3
57,8
76,8
92,3
Range
(1)
[m]
4,5
PIC. 4.1 BASIC DIMENSIONS.
PIC. 5.1 HORIZONTAL INSTALLATION.
PIC. 5.2 VERTICAL INSTALLATION.