12
9.
CONNECTION OF HYDRAULIC INSTALLATION
SRX VALVES PARAMETERS:
SRX2d 3/4"
– two-way valve 3/4" with an actuator
(fluent modulation 0-10 V).
SRX2d 1 1/4"
– two-way valve 1 1/4" with an actuator (fluent
modulation 0-10 V).
SRX2d:
Class of protection: IP54,
Supply voltage: AC/DC 24 V,
(with a supplied transformer: 230 V), 50 Hz,
Max. medium temperature : +120°C,
Operating pressure: 2,5 MPa,
SRX2d 3/4"
: Water flow range: 220 – 1330 l/h,
SRX2d 1 1/4"
: Water flow range: 550 – 4001 l/h
SRX3d 3/4"
– three-way valve 3/4" with an actuator
(3-point modulation)
SRX3d:
Class of protection: IP40,
Supply voltage: AC 230 V/50 Hz,
Max. medium temperature: +120°C,
Operating pressure: 1,0 MPa,
SRX3d 3/4" Kvs: 6,3 m3/h,
Running time: 140 s
WARNING
1.
Disconnect the curtain power supply before connecting the water system.
2.
The connection should be made without stress. It is recommended to use flexible ducts supplying the
heating medium.
3.
Water supply should be connected to the connector marked with the symbol
↑
IN.
4.
The installation with the heating medium must be protected against the increase of the heating medium
pressure above the permissible value (1.6 MPa).
5.
Before starting the device, check the correct connection of the heating medium and the system for leaks.
6.
During assembly of the installation it is absolutely necessary to immobilize the exchanger's connector pipes
7.
After filling the system with heating medium, check the tightness of the hydraulic connections, including the
built-in vent.
ZK – ball valve
ZO – bleeding valve
ZR – balancing valve
ZD – drainage valve
FS – mesh filter
KP – flexible hoses
ZK – ball valve
ZO – bleeding valve
ZR – balancing valve
ZD – drainage valve
FS – mesh filter
KP – flexible hoses
PIC. 9.1 CONNECTION EXAMPLE OF SRX2D.
PIC. 9.2 CONNECTION EXAMPLE OF SRX3D.
PIC. 9.3 COUNTER
PIC. 9.4 WATER INLET CONNECTION POINT