1) THE ELECTROPUMP DOES
NOT PUMP WATER, THE
MOTOR DOES NOT RUN
2) THE PUMP DOES NOT SUP-
PLY WATER BUT THE MOTOR
IS RUNNING
3) THE PUMP SUPPLIES A
LIMITED AMOUNT OF WATER
4) INTERMITTENT OPERATION
10
PROBLEM
POSSIBLE CAUSE
REMEDY
1) No electricity.
2) Plug inserted incorrectly.
3) Enabled safety switch.
4) Blocked impeller.
5) Damaged motor or condenser.
2) Verify that voltage is present and that the
plug is correctly inserted.
3) Reset the safety switch.If the safety switch
is once more enabled, contact a specialised
electrician.
4) Contact the Customer Assistance Service.
5) Contact the Customer Assistance Service.
1) Obstructed suction grid.
2) Blocked check valve.
3) Air in impeller body (air bubbles).
4) The water level is below the start-up
level.
1) Clean the grid.
2) Clean or replace the valve.
3) Perform several start-ups in order to remove
all the air.
4) Fill the pump with water using the quick
closing standard fitting.
1) Partially obstructed suction grid.
2) Obstructed pipe.
3) Worn impeller.
1) Clean the grid.
2) Remove the obstructions.
3) Contact the Customer Assistance Service.
1) Solid particles prevent the free
rotation of the impeller.
2) The temperature of the fluid is too
high.
3) Voltage out of range.
4) The fluid is too dense.
5) Faulty motor.
1) Remove the foreign particles.
3) Supply the pump in accordance with
nameplate data.
4) Dilute the pumped fluid.
5) Contact the Customer Assistance Service.
GB
5
5) THE PUMP DOES NOT START
AND STOP IN AUTOMATIC
MODE
1) The pump is not placed in a vertical
position.
2) The integrated floating switch is
blocked.
1) Place the pump in a straight position.
2) Clean the floating switch.
If, after performing these operations, the problem persists, contact your retailer (customer assistance service).
GB
TRANSLATION FROM ORIGINAL INSTRUCTIONS
Distributed in NZ By:
Freephone 0508 634 34
1
7 Monier Pl, Mt Wellington, Auckland 1060, New
Zealand