Flo Fab GPA-IV Series Installation And Operation Manual Download Page 2

OI. Read the installation  manual

carefully  before installation  and

use.

11. Some models are not suitable for

drinking 

water.

02. The manufacturer 

will not be liable

for any personal injury, pump
damage and other property

damage due to failure  to comply

with contents specified  in safety

warning 

signs.

12. The liquid  may be  high-temperature

and high-pressure;  therefore,  the
liquid  in  the  system 

m ust  be

completely drained or the shut-off

valves on both sides must be

closed 

before 

moving 

a nd

dismantling the  pump to  prevent

buming.

03. The installers and operators must

comply  with  local safety regulations.

04. The user must confirm that  only

q ua lified 

personnel 

with

professionalcertification  and
proficiency  of this  manual  is

allowed to install and maintain this

product

13. If removing the exhaust bolt, high-

temperature and high-pressure

liquid will be overflew. Therefore.
it is necessary to insure  that  the

outflow  liquid  will  not  cause
personalinjury or damage other
para.

05. The pump must not be installed in a

place that  is damp or may be

splashed 

by water.

14. Ventilation  must be ensured in

summer or  high ambient

t e m p e rature  period  to  avoid

condensation  that  may  cause
electrical 

malfunctions.

06. F=6r 

convenient 

access 

of maintaince.

a shutoff valve 

shall be installed 

on

each side of the pump

15. In winter, the pump system does

not work or when the ambient

temperature drops  below O "C

liquid in the system shall be

completely drained so as to avoid

frost cracking 

of pump body.

07. The power supply of the pump shall

be cut  off before installation and

maintainace.

08. For domestic hot water, copper or

stainless  steel pump body shall  be

used.

16. If the pump is left unused for a long

time, please close the pir)e valve in
the inlet and outlet of the pump and
cut  off the  power supply.

09. Heatsupply  pipelines shall  not be

frequently filled with  non-softened

water so as to avoid increasing

calcium  in the  circulating water

inside the pipeline. which may thus
block the  impeller.

17.If he flexible  cord of  cable ist

damaged. it must be replaced by a

qualified 

person.

10.  Do not start  the pump without  liquid.

18. Please 

close the valve at the inlet of

the pump and cut off  power of the

pump immediately if overheating

01

Summary of Contents for GPA-IV Series

Page 1: ......

Page 2: ...a place that is damp or may be splashed bywater 14 Ventilation must be ensured in summer or high ambient t e m p e rature period to avoid condensation that may cause electrical malfunctions 06 F 6r c...

Page 3: ...lventilated and cool place under room temperature Warning Beforeinstallation you mustcarefully readthe installation and operation manual The installation and useof the equipment must comply with local...

Page 4: ...pply system Heat supplysystem with night mode HVAC system Lowoperationalnoise of motor pump and whole system Low energy consumption Compared with traditional circulation motor pumps it has lower energ...

Page 5: ...ture 3 4 System Pressure Maximum pressure LOMpa IObar 3 S Degreeof Protection IP42 3 6 Inlet Pressure 3 7 Pumping Liquid Thepumping liquid includes thin clean non corrosiveand non explosive I iquid wh...

Page 6: ...PA IVseriescirculating pump thearrowon motorpump case Indicates the flow direction of liquid through the pump A hen installnghhinlet andoutlet the pipeline two suppliedgaskets must During theinstallat...

Page 7: ...ion of junction box are as follows I Close thevalves at theinlet and outlet and releasethe pressure 2 Unscrewand removethefoursockethead screwsthat fastenthepump body 3 Rotate themotor to theexpected...

Page 8: ...ermallnsulation of Motor PumpBody r Limiting theheat loss of motor Pumpbody and pipeline Motor pump body and pipeline should be thermally reduce theirheat loss insulated to Do not isolate or cover the...

Page 9: ...5 Electrical Connection 08...

Page 10: ...e betweenallthe electrodesis3mm GPA IVseries circulating motor pump needs no protection from externalmotor Check if the supply voltage and frequency are thesameas parameters indicated on the nameplate...

Page 11: ...ed area displaying hgh are always lit with flashing lights indicatingthe pump 2flashir problem corresponding fault are a 3flas follows 4 If is detected the 5flashin oH After the troubleisaddressed re...

Page 12: ...ds interval the motor pump setting mode will change once A cycle is constituted of every four presses on the button For details please referto Section 6 2 7 Motor Pump Setting 7 1 Motor Pump Setting B...

Page 13: ...Igor the relationsbetween motor pump setting and performance curve 7 2 Control of Motor Pump il l emotorpumpisControlled according to ressureControl BL or Constant J T 7 ProportionalPressureControl b...

Page 14: ...0000000 0 i0 l P 0 M e w WUw C I I I lll le AUO Chapter 7 Bypass valve Thepurpose of bypassvalve whenallthe valves and or temperature sensingvalvesof heatradiator in the floor heatingloop aro closed I...

Page 15: ...WhenalJ valv t U l M i cbl L T HK U n 8 2Manually operated Bypass Valve In accordance with thofollowing procedures Follow IhalonowiCg paceSS Valve temperature sensingtypo gU nnHH 14...

Page 16: ...GP4 lV 9 3Vent the heating system 10 Motor Pump Setting and Performance lO IRelations between Motor Pump Settingand Performance oar from I to 9 Ihesliadov ena to gear from lt0 9 ald the yeHolr 15...

Page 17: ...e Power withWatt asthe unit powerconsumption of motorpumpin given Q H curve 11 2Curveconditions GPAIVseriesmanual e applicable tothe performancecurvespecified in the Test liquid air free water lW KK T...

Page 18: ...ar from t to 9 1heshadow are ol blue one is automatic gear the green one b ntb gear from I to 9 and the yellow on8 is constant pressur gear from I i0 9 Constant pressure mode performance curve 0 1 3 C...

Page 19: ...12 Features 12 1Nameplate Instructions a D 1 GPA2S H R g n 14021Z0001 I I lll I b No l 2 3 Power Watt 4 Current Amo 5 6 Dale...

Page 20: ...onomitted z Inlia n9elort8i l tHietiomRillympis N stainless steelmaterialof pump body B steel materialof pumpbody cast iloi pump body omitted Maximumheadof delivery of pump m P plastic materialof pump...

Page 21: ...System LoadBearing 1 0MPa Suction Port Pressure Temperature IMinimum InletPressure 85 C 0 005 Mpa 90 C 0 028Mpa 110 c O 100MPa EN61000 6 1 and EN61000 6 3 j 112111essure even ofpump islower than 43dB...

Page 22: ...13 21nstallation Dimensions GP4 lV Product Model w LI GPA25 10 M 1 90 185 GPA32 10 M 1 90 Dimension mm L2 B2 H2 H G 80 160 199 2 44 80 160 144 199 2 21...

Page 23: ...cessively high flow rate Air exists inthe motorpump excessively low inlet pressure poor performance of motor CorrectiveAction Replace thefuse connect thecircuit breaker Replacethemotor pump inspectwhe...

Reviews: