20
K 2 . 1
9. Adjusting
units
9.1. ADJUSTMENT WITH CI60
CAUTION!
The unit's air supply
MUST be adjusted before the
unit is used for the first time. This
should be done in accordance with
the projection documents. Adjust
the values based on the projected
values.
i
9.1.1. Adjustment
Only stage 2 (NORMAL) needs to be adjusted. Stages
DQGKDYHȴ[HGVHWWLQJVZKLOHVWDJHKDVWREH
adjusted as required in the individual home.
7KHIXQFWLRQRIWKHGLHUHQWVWDJHV
MIN
Must not be used when the home is in use.
0XVWQRWEHXVHGLQWKHȴUVWWZRKHDWLQJ
seasons.
NORMAL
Used under normal conditions. On this setting
the air supply must be adjusted according to
current regulations.
MAX
Used if there is a need for increased air supply
on account of higher occupancy or a raised
humidity level, for example during showering
or when clothes are being dried. This setting is
normally used for limited periods.
The ventilation unit’s air supply is adjusted in speed level
NORMAL using the knobs on the back of the cover. Knob
9 is used for supply air level and knob 8 for extract air
level (see Fig. 13). The adjustment range is 20-100% of
the maximum level according to the scale on the knob.
Factory settings for supply air/extract air:
MIN
ȴ[HG
NORMAL
75% (variable)
MAX
ȴ[HG
9.1.2. Adjusting the temperature
The temperature required for the supply air can be
set with knob 11. The adjustment range is 10 - 30°C.
It should normally be set to around 18°C. Use of the
factory setting is recommended.
If necessary, the ventilation unit’s additional heating can
also be switched ON/OFF with switch 10. In this case
only the rotating heat exchanger is used as a source of
heat. It is best to leave it in ON position, as the unit will
then respond automatically when there is a need for
additional heating.
)LJ
8
9
10
11