2. FIRST START-UP
SER
VICE
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P23
MODULATING PUMP MINIMUM SPEED
(ONLY WITH MODULATING PUMP AND RETURN PROBE CONNECTED)
THROUGH THIS PARAMETER YOU CAN SET THE MINIMUM
SPEED VALUE OF THE MODULATING PUMP DURING A REQUEST
TO OPERATE IN HEATING MODE.
50 - 70
THE VALUE IS EXPRESSED IN
PERCENTAGE
P24
MODULATING PUMP MAXIMUM SPEED
(ONLY WITH MODULATING PUMP AND RETURN PROBE CONNECTED)
THROUGH THIS PARAMETER YOU CAN SET THE MAXIMUM
SPEED VALUE OF THE MODULATING PUMP DURING A REQUEST
TO OPERATE IN HEATING MODE.
70 - 100
THE VALUE IS EXPRESSED IN
PERCENTAGE
P25
D.H.W STORAGE TANK TEMPERATURE SETPOINT
(FOR STORAGE BOILERS ONLY)
THROUGH THIS PARAMETER YOU CAN SET THE PRIORITY
STARTING VALUE OF THE STORAGE TANK, COMPARED TO THE
USER ADJUSTABLE D.H.W SETPOINT.
3 - 9
THE VALUE IS EXPRESSED IN °C
(PRE-SET AT 9°C)
P26
MODBUS ADDRESS
BY MEANS OF THIS PARAMETER, IT IS POSSIBLE TO SET THE
ADDRESS OF THE BOARD ON MODBUS IN ORDER TO PERFORM
A CASCADE SYSTEM.
1 - 16
BOILER NUMBERING FOR
MODBUS
P27
MODBUS COMMUNICATION BAUD RATE
BY MEANS OF THIS PARAMETER, IT IS POSSIBLE TO SELECT
THE MODBUS COMMUNICATION BAUD RATE SUPPORTED BY
THE SAME INTERFACE.
0 - 5
0 = 9600
1 = 1200
2 = 2400
3 = 4800
4 = 9600
5 = 19200
P28
MODBUS MODE
0 - 2
0 = ENABLED
1 = ENABLED WITH LOCAL
SETTINGS
2 = DISABLED (SET BY
DEFAULT)