2. FIRST START-UP
SER
VICE
CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P13
HEATING FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM
SPEED IN HEATING PHASE, THAT CORRESPONDS TO THE
MAXIMUM BURNER POWER DURING A REQUEST TO OPERATE
IN HEATING MODE.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
SEE CHAPTER
‘
H
E
A
T
C A P A C I T Y
D I A G R A M
(KW) –
ELECTRIC FAN
F R E Q U E N C Y
(HZ)’
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P14
STARTING STEP ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED
DURING START-UP
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE
PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER
P02)
SEE CHAPTER
‘
H
E
A
T
C A P A C I T Y
D I A G R A M
(KW) –
ELECTRIC FAN
F R E Q U E N C Y
(HZ)’
THE VALUE IS EXPRESSED IN
HERTZ
(1HZ = 30 RPM)
P15
ANTI-LEGIONELLA FUNCTION
(FOR STORAGE BOILERS ONLY)
THROUGH THIS PARAMETER YOU CAN ACTIVATE/DEACTIVATE
THE “ANTILEGIONELLA” HEAT TREATMENT OF THE STORAGE
TANK. EVERY 7 DAYS THE WATER TEMPERATURE INSIDE THE
STORAGE IS HEATED BEYOND 60 °C THUS GENERATING A
BURNING HAZARD. KEEP UNDER CONTROL SUCH DOMESTICH
HOT WATER TREATMENT (AND INFORM THE USERS) TO AVOID
UNFORSEEABLE DAMAGES TO PERSONS, ANIMALS AND
PROPERTY. A THERMOSTATIC VALVE SHOULD BE INSTALLED
AT THE DOMESTIC HOT WATER OUTLET TO AVOID ANY BURNS.
0 - 1
0 = DISABLED
1 = ENABLED (PRE-SET BY
DEFAULT ON STORAGE BOILERS
ONLY)