Modification for Parallel Operation
It is possible to operate two or three BMR 463 2002 or two or three BMR 464
2002 in parallel by connecting the output voltage connectors together.
For proper performance the connection shall be of low impedance and the
point of connection shall be at the PCB as indicated in Figure 3.1.
As connection power jumpers can be used as shown in Figure 3.2. Note that
the power jumpers shall be attached below the ring nuts of the output voltage
connectors. Alternatively the connection can be made of a piece of thick
copper wire that is soldered directly to the PCB.
Fig 3.1. Connection of output voltage for parallel operation.
Fig 3.2. Connection with power jumpers.
BMR 464
BMR 463
Points of connection