Printed in U.S.A.
Page 5B
MODEL 6700 Downflow - V2.0
Option Setting Level #2
Softener Manufacturer Programming (Cont’d.)
3.
Prior Service Volume Used Display (E)
Depress the Program Button. The next display viewed
is not an option setting. This display is used as an aid
to the service person in diagnosing a valve
malfunction. The amount of water used the last time
the softener was in service is recorded in this display
by the control. The unit of measurement used is
gallons/liters/cubic meters.
Example: 850 Gallons - [E - - - 850]
4.
Reserve Capacity Display (rc)
Depress the Program Button. The next display viewed
is not an option setting. This display is used as an aid
to the service person in diagnosing a valve
malfunction. The calculated reserve capacity (in
gallons/liters/cubic meters) for the present day is
recorded in this display by the control.
Example: 277 gallons - [rc - - 277]
5.
Previous Days Water Usage Display (Pd)
Depress the Program Button. The next display viewed
is not an option setting. This display is used as an aid
to the service person in diagnosing a valve
malfunction. The previous day’s water usage (in
gallons/liters/cubic meters) is recorded in this display
by the control.
Example: 200 gallons - [Pd - - 200]
6.
Cycle Step Location For Chlorination Indicator (J)
Depress the Program Button. The next display viewed
is an option setting. This display is used to set the
desired regeneration cycle step where the chlorinator
indicator (C) will turn on in the regeneration display.
Actual control of power to a chlorinator is handled
independently of this setting using a microswitch or
Timed Auxiliary Output.
Examples: No Chlorinator Installed -[J - - - OFF]
Chlorinator to turn on during Step #2 - [J -
- - - - 2]
The UP and DOWN Set Buttons will adjust this
value.
7.
Time Auxiliary Output Programming (y) (r) (n)
Depress the Program Button. The next 3 displays
viewed are part of a series of option settings used to
program the optional relay output. These displays will
not be viewed if the optional relay output is not
installed. The first two settings (y and r) turn the
output on / off during Regeneration only. The third (n)
turns the output on during Service only, when a set
volume of water used has accumulated. This setting
will not be viewed on non-metered systems.
Note:
When more than one of these settings is used, it will
be up to the operator to supply the switching logic
necessary to operate two or three separate pieces of
equipment at a time from a single relay output.
8.
Time Auxiliary Output Window #1 Setting (y)
This option setting consists of two displays. The first
display is used to set the turn on time of the output,
referenced to the start of Backwash. The second
display is used to set the output turn off time,
referenced again to the start of Backwash. An OFF
setting cancels this setting. A set on time with a set
off time of S will turn the output off at the start of
Service. All settings are in minutes and output timing
is synchronized with regeneration cycle timing.
Examples: Activate output at start of Step #1/
Deactivate after 10 minutes -[y - - - - - 0] (Start Time
Display)
[ 10.0] (Stop Time Display)
Cancel setting - [y - - -OFF]
The UP and DOWN Set Buttons will adjust this
value.