MODEL 6700 Downflow - V2.0

Option Setting Level #2

Softener Manufacturer Programming (Cont’d.)

Meter Delayed.

 The control will determine that a 

regeneration is required based on when the available 
volume of treated water drops to or below the reserve 
capacity. Regeneration is to begin immediately at the 
set Regeneration Time only when service flow has 
not been detected. Regeneration is to be to delayed, 
in two 10 minute sections, for up to an additional 20 
minutes, with service flow. Regeneration then to 
begin immediately. There will not be a delay if the 
Volume Remaining is zero.

Example:  [7 - - - - - 3]

Regeneration Type #4

Example:  [7 - - - - - 4] This option setting is not 
typically used with downflow regeneration valves.

Sensor Immediate.

 The control will monitor 

conditioner status by means of a sensor. 
Regeneration will begin immediately after a signal 
from the sensor is received. When this regeneration 
type is selected, one additional display will follow. 
Depress the program button once more to view the 
second display. This display selects the amount of 
time required for a sensor input signal to be present 
before the signal is considered to be valid. This 
second display will only be able to be viewed when 
this option selected.

Example:  

[7 - - - - - 

5] Initial Display
Sensor Input Signal Minimum On Time -  [7 - 5 - - 
5.0] 
5.0 Minutes

Sensor Delayed.

 The control will monitor conditioner 

status by means of a sensor. Regeneration will begin 
at the set Regeneration Time after a signal from the 
sensor is received. When this regeneration type is 

selected, one additional display will follow. Depress 
the program button once more to view the second 
display. This display selects the amount of time 
required for a sensor input signal to be present before 
the signal is considered to be valid. This second 
display will only be able to be viewed when this option 
selected.

Example:  

[7 - - - - - 

6] Initial Display
Sensor Input Signal Minimum On Time -  [7 - 6 - - 
5.0] 
5 Minutes

Regeneration Type #7

Example:   [7 - - - - - 7] This option setting is not 
typically used.

Regeneration Type #8

Example:   [7 - - - - - 8] This option setting is not 
currently used.

The UP and DOWN Set Buttons adjust this value.

16. Flow Meter Size (F)

Depress the Program Button. The display is used to 
set the size of the valve flow meter. This setting will 
not be viewed on non-metered valves.

Examples: [F - - - - - 0] Option Not Typically Used

[F - - - - - 1] Standard 3/4” Flow Meter
[F - - - - - 2] Option Not Typically Used
[F - - - - - 3] Option Not Typically Used
[F - - - - - 4] Option Not Typically Used
[F - - - - - 5] Option Not Typically Used
[F - - - - - 6] Option Not Typically Used

The UP and DOWN Set Buttons will adjust this 
value.

Summary of Contents for 6700 Downflow

Page 1: ...P 10 Note This display only viewed with metric display formats U2 U4 System Capacity Example 20 000 Grain Capacity 20 Regeneration Time Example 2 00 A M 2 00 Regeneration Cycle Step 1 Backwash Exampl...

Page 2: ...entified by the red LED next to the Water Hardness label Example 25 grains 25 The UP and DOWN Set Buttons will adjust this value 2 Water Hardness After Mixing Valve P Depress the Program Button The ne...

Page 3: ...lue 25 gpm or black 5 gpm rate of refill in gpm times your timer setting Then using one gallon of fresh water dissolving approximately 3 lbs of salt calculate your refill time Valves equipped for Vari...

Page 4: ...lay Example 5 Days d 5 Prior Service Volume Used Display Example 858 Gallons E 858 Reserve Capacity Display Example 158 Gallons rc 158 Previous Days Water Usage Display Example 258 Gallons Pd 258 Cycl...

Page 5: ...Or Valves Without Meters Chemical Pump Output Volume Count Setting Example Turn On In Service Every 100 Gallons 100 Regeneration Day Override Example Override Every 7 Days A 7 Volume Override Example...

Page 6: ...lly Used F 3 Option Not Typically Used F 4 Option Not Typically Used F 5 Option Not Typically Used F 6 Mixing Valve Location Examples No Mixing Valve 8 1 Mixing Valve Before Flow Meter 8 2 Mixing Valv...

Page 7: ...s Depending on current pro gramming certain displays or option settings will not be viewed 1 Flow Rate Display Fr The first display viewed is the current flow rate of treated water through the softene...

Page 8: ...tual control of power to a chlorinator is handled independently of this setting using a microswitch or Timed Auxiliary Output Examples No Chlorinator Installed J OFF Chlorinator to turn on during Step...

Page 9: ...r every 200 gallons n P Pulse Mode 500 Cancel setting n OFF The UP and DOWN Set Buttons will adjust these settings 11 Regeneration Day Override A Depress the Program Button The next display is used to...

Page 10: ...be P P M mg liter or g m3 and Capacity in grams Regeneration Types 7 and 8 will not be displayed Example U 4 The Japanese Metric Format uses liters for volume and liters per minute for flow rate relat...

Page 11: ...will only be able to be viewed when this option selected Example 7 5 Initial Display Sensor Input Signal Minimum On Time 7 5 5 0 5 0 Minutes Sensor Delayed The control will monitor conditioner status...

Page 12: ...d 9 9 Option Not Typically Used The UP and DOWN Set Buttons will adjust this value 19 Program Lock PL Depress the Program Button The display is used to prevent certain displays from being viewed or se...

Reviews: