FTS 371 SMART USER MANUAL
Flash Technology, LLC
Revision 4 – 9/7/2021
11
SECTION 2 – OUTLINE, MOUNTING AND INSTALLATION INSTRUC TIONS
UNPACKING
Inspect shipping cartons for signs of damage before opening. Check package contents against the packing list and
inspect each item for visible damage.
Promptly report damage claims to the freight handler.
TOOLS
1/8” non-flared flat blade screw driver
Digital volt-ohm meter
#2 Phillips® head screwdriver
Wire strippers
Level
Tin Snips
Mounting hardware for controller (if not provided in the system kit)
Various drill bits (to create openings in the bottom of the controller for cable runs)
CONTROLLER INSTALLATION AND GROUNDING
Locate the FTS 371 FTC SMART controller in an area that will allow proper access to the enclosure. Ensure the
mounting location does not interfere with the quick-release latch that secures the enclosure’s door. Release the
latch to open the door for internal access.
Use the following guidelines for mounting the controller:
Ensure that adequate space exists around the equipment for access during installation, maintenance and
servicing.
Allow space for airflow around the controller. Recommended 3-4” of space allowed on each side of the
controller. Flash Technology does not furnish mounting hardware unless it is ordered as part of an
installation kit.
Flash Technology recommends using flexible conduit for all cable runs with the exception of the beacon
cable and jacketed ground wires.
Ground the controller using a 2 AWG insulated wire. Route all ground conductors down and away from
the energized equipment and ensure there are no bends less than 8 inches. If installed outdoors, bond the
system controller to the site grounding grid (via exothermic welding). If installed inside a shelter or
building, route the 2 AWG insulated ground wire to the nearest down-link and attach using a compression
fitting (c-tap).
Use the following guidelines for installing the photodiode:
Locate the photodiode where it has an unobstructed view of the polar sky (north).
It must not view direct or reflected artificial light.
Support the photodiode vertically at the top end of a vertical length of rigid conduit to prevent moisture
intrusion.
If possible, mount the photodiode in a location that will allow easy access for future testing.