VESDA-E VEP-A00-P Product Guide
www.xtralis.com
57
Command
Description
Execute From
A button
on the
Detector
Xtralis VSC
Software
Start Minor Fault Test
Generates a minor fault on the detector and de-
energizes the fault relay for 2 minutes.
Start Alarm Test
Simulates full scale smoke level which causes the
Alert, Action , Fire 1 and Fire 2 alarm conditions to
occur.
Alarm relays will energize unless the detector is
disabled.
Start Air Flow Fault Test Tests the air flow sensing system by shutting down
the aspirator.
Start Relay Test
Tests the available relays by activating and
deactivating as required.
Start LED Test
Tests each LED by cycling through all LEDs on the
detector display panel.
Return to Factory
Defaults
Restores the configuration of the detector to the
initial factory default values.
Set System Date and
Time
Sets the detector date and time.