![flamco WMS 800 Installation And Operating Instructions Manual Download Page 8](http://html1.mh-extra.com/html/flamco/wms-800/wms-800_installation-and-operating-instructions-manual_2302330008.webp)
8
ENG: Installation and operating instructions
Translation of the original operating instructions
5.1 Electrical connection
1
Horn, AC 230 V
2
Blue
3
Brown
4
Black
5
Green-yellow protective
earth (PE) conductor
6
WMS 800 with interlock
7
Switch
8
Release
9
Furnaces
10
Junction box
Figure 4: Electrical connection WMS 800 with interlock
R
Mains voltage is interrupted and secured against switching back on
The WMS 800 includes a two-way contact. Lack of water opens the contact connected in
series with the burner. The previously open contact closes so that a horn can be switched
on.
A 4-core cable, length 1.9 m, is connected to the upper part.
f
Wire any other required connections professionally to a junction box as shown in
Figure 4, Page 9.
f
Implement any connecting pipes/cables, which are not part of the scope of supply, in
min. DN 20 or ¾".
5.2 Starting up the product
f
Press the “Release” button after filling and venting the system.
Ä
The system is switched on.
5.3 5.3 Functional check
The functional check can be performed without reducing the water level.
1.
Press the test button. See Figure 1, Page 6, No. 5.
Ä
The burner shuts off.
2.
Switch on again by pressing the release button.
WMS 800 with interlock: See Figure 1, Page 6, No. 2.
Summary of Contents for WMS 800
Page 11: ...11 ENG 12 2 EC Declaration of Conformity...
Page 21: ...21 DEU 12 Anhang 12 1 Zulassungsunterlagen...
Page 22: ...22 DEU Montage und Betriebsanleitung Orginalbetriebsanleitung 12 2 EG Konformit tserkl rung...
Page 23: ...23 DEU...
Page 33: ...33 NLD 12 2 EG conformiteitsverklaring...
Page 34: ...34 NLD Montage en gebruikshandleiding Vertaling van de oorspronkelijke gebruiksaanwijzing...
Page 43: ...43 FRA 12 Annexe 12 1 Documents d autorisation...
Page 45: ...45 FRA...
Page 46: ...46...
Page 47: ...47...