PR No
Engineers Code - 4706
Notes
Default
Unit
22
Pressure Alarm Auto
Reset
Toggles High/Low Alarm from being
automatic reset to manual reset/critical
stop
Y
STA
N
D
ARD
O
P
TION
23
All VFC Fail Safe
Toggles all VFC alarms to be energised,
normally closed. Break/open on fault
N
24
Tank Solenoid
Uses High Water contact to activate a
tank topup solenoid
N
25
Tank Solenoid Overrun
Overrun command for filling solenoid
5
Seconds
26
Zero Start
Allows topup unit to start immediately if
switched on and seeing 0 bar (formerly
boost option)
N
27
Cascade
Delay start time for activating both
pumps together [note 0 means that the
pumps will NOT run together, but
operates as duty/standby/auto change
over
0
Seconds
{disabled}
28
Fill system
N
29
Extended Mode
N
30
not used
N
31
Degassing Required Y/N
N
45
Service Reminder Y/N
N
46
Pump1 Max Hours Run
Alarm to change Pump
9000
P
u
m
p
(when set to 0 the alarm is disabled)
47
Pump 2 Max Hours Run
Alarm to change Pump
9000
(when set to 0 the alarm is disabled)
48
ID Number
MODBUS ID number
1
49
Review Logs
N
REVIEW
LOG
M
EN
U
50 (*)
P1 Topup Count
Counter for P1 used for Topup
51 (*)
P1 Topup Hours
Hours Run for P1 Topup
52 (*)
P2 Topup Count
Counter for P2 used for Topup
53 (*)
P2 Topup Hours
Hours Run for P2 Topup
54 (*)
P1 Total Hours
Total Hours run P1 (inc Degassing)
55 (*)
P2 Total Hours
Total Hours run P2 (inc Degassing)
56 (*)
Alarm Count
Alarm Counter
57 (*)
Power Interrupted
Count
Power interrupted counter