15
Instructions for use
EN
ADDITIONAL AND
SERVICE SETTINGS
INFORMATION GROUP D1 - GENERAL INFORMATION
PARAMETER GROUP P1 - BASIC PARAMETERS
No.
Description
Range
P1.1
TEMPERATURE DISPLAY ROUND-OFF
With this setting, we can determine to what value the meas-
ured Temp. display will be rounded off.
0 - 0.1 °C
1 - 0.2 °C
2 - 0.5 °C
3 - 1.0 °C
P1.2
AUTOMATIC EXIT TIME
This setting determines the time after which the display returns
to basic mode.
3 ÷ 180 s
(
15
)
P1.3
DISPLAY ILLUMINATION SHUT-OFF TIME
This setting determines the time after which display lighting is
reduced or shut off.
10 ÷ 180 s
(
30
)
P1.4
DISPLAY ILLUMINATION OPERATION MODE
This setting determines type of operation of display illumina-
tion.
The following settings are available: 0 - no display illumination.
1- The display has maximum brightness when entering settings
to the room unit. After a delay, display illumination is reduced
to the minimum value.
2- Same as 1, but display illumination is adapted to the amount
of light in the room.
3- Same as 2, but room unit display is completely turned off
in standby mode during night Temp. interval if this occurs
between 6pm and 6am.
0 ÷ 3 (
2
)
No.
Description
d1.1
ROOM UNIT TYPE (RCD2)
d1.2
ROOM UNIT SOFTWARE VERSION
d1.3
TYPE OF CONTROLLER CONNECTED TO ROOM UNIT
W10D = 34 W10 = 35
W20 = 43 K10B = 58
K20 = 52 MWR3 = 101
d1.4
Software version of the controller
d1.5
Hydraulic scheme of the controller
d1.6
LIGHT SENSOR
Measured light of the room where the room unit is installed is displayed.