We reserve the right to change designs and technical specifications of our products.
6
2. Technical Specifications
The standard models of the Flamco compact heat storage are supplied with PCM58 and these heat storage can be used in combination with any
heat source which can run at flow temperature greater than 65 °C. The discharge temperature from these standard compact heat storage models
will be between 52 and 55 °C.
The overall dimensions and weights of the compact heat storage models in the FlexTherm Eco range are listed in table 2.1 and their technical
specification is listed in table 2.2. The pressure loss characteristics of the compact heat storage are tabulated in tables 2.3a, 2.3b, 2.3c.
Table 2.1. Overall dimensions and weights of FlexTherm Eco compact heat storage range
Overall dimensions [mm]
Weight
[1]
Width
Depth
Height
[kg]
FlexTherm Eco 3E
360
570
445
70
FlexTherm Eco 6E
360
570
645
120
FlexTherm Eco 9E
360
570
880
170
[1]
The PCM in standard heat storage has a phase transition temperature of 58 °C
Table 2.2: Technical specification of FlexTherm Eco heat storage range
Size 3
Size 6
Size 9
Storage capacity –
Standard storage with
PCM58 [1]
[kWh]
3.5
7.0
10.5
Water content – Low
power circuit (LPC)
[3]
Water content – High
power circuit (HPC)
[4]
[L]
[L]
1.30
2.24
2.36
4.48
3.46
6.76
Equivalent hot water
cylinder size
[5]
[L]
71
142
212
V
40
, Volume of hot water
available at 40°C
[6]
[L]
85
185
300
•
Heat loss rate
•
Heat loss rate
•
ErP Rating class –
Hot water storage vessel
[kWh/24h]
[W]
[ - ]
0.449
18.7
A+
0.649
27.0
A+
0.738
30.7
A+
Recommended
maximum HW flow rate
[L/min]
6
15
20
Minimum cold water
supply pressure at inlet
to the heat storage
[bar]
[MPa]
1.00
0.10
1.50
0.15
1.50
0.15
Maximum working
pressure:
High power (HPC) and
Low power (LPC) circuits
[bar]
[MPa]
10.0
1.0
10.0
1.0
10.0
1.0
Pressure loss
characteristics
(See tables 2.3)
• KV Value for the Low
power circuit (LPC)
• KV Value for the High
power circuit (HPC)
[ - ]
[ - ]
1.623
2.871
1.255
2.356
1.066
1.951
ENG